YORK YMC2 — fault codes

229 fault, warning and safety-shutdown messages documented by the manufacturer for the YORK YMC2, from 10 manuals. A message in bold has a page of its own: what it means, why it appears, what to check and how the unit restarts — from the manual that documents it. The others link to their row in the manual, with the page it was taken from.

Run messages

Message on the displayWhat it meansManual
WARNING - VSD DC BUS ACTIVENon-annunciating alert that the DC Bus is precharged or pre-regulated for a state outside of…160.78-O2 p.114

Start inhibit messages

Message on the displayWhat it meansManual
LINE FREQUENCY NOT SETChiller prevented from starting because the Line Frequency setpoint is invalid.160.78-O2 p.114
LINE VOLTAGE NOT SETChiller prevented from starting because the Line Voltage setpoint is invalid.160.78-O2 p.114
PRV NOT CALIBRATEDStart inhibited because the Pre-rotation vanes calibration has not been done.160.78-O2 p.114
VGD NOT CALIBRATEDStart inhibited because the Variable Geometry Diffuser calibration has not been done.160.78-O2 p.114
VGD STROKE NOT CALIBRATEDThe VGD stroke calibration procedure has not yet been performed.160.84-OM1 p.94
VGD FEEDBACK NOT CALIBRATEDThe VGD feedback calibration has not yet been performed since last stroke calibration.160.84-OM1 p.94
MBC - INITIALIZATION FAILUREOptiView was unable to read a valid validation key code over serial communications from the MBC…160.84-OM1 p.94

Warning messages

Message on the displayWhat it meansManual
WARNING - MBC - LANDING COUNTER HIGHMBC landing counter has reached its warning threshold of shaft landing events.160.78-O2 p.115
WARNING - MBC - ROTATION MODE OFFMBC reports Rotation Mode OFF while the microboard is commanding it ON.160.78-O2 p.115
WARNING - MOTOR - HIGH CURRENT LIMITMotor current has reached the Motor Overload current limit; capacity control is overriding to…160.78-O2 p.115
WARNING - CONDENSER - HIGH PRESSURE LIMITCondenser pressure exceeds the High Pressure Warning Setpoint; capacity override active.160.78-O2 p.115
WARNING - CONDENSER OR EVAPORATOR XDCR ERROREvaporator pressure transducer reads higher than the condenser transducer - indicative of a…160.78-O2 p.115
WARNING - CONDENSER OR VGD SENSOR FAILUREStall (discharge) pressure transducer and condenser pressure transducer outputs disagree; VGD held…160.78-O2 p.115
WARNING - EVAPORATOR - LOW PRESSURE LIMITEvaporator pressure has fallen to the warning threshold; capacity control overriding to raise…160.78-O2 p.115
WARNING - EXCESS SURGE DETECTEDSurge Window Count has exceeded the Count Limit (applies only if Surge Protection SHUTDOWN is…160.78-O2 p.116
WARNING - MOTOR - HIGH HOUSING TEMPERATUREMotor housing temperature at or above the warning level.160.78-O2 p.116
WARNING - MOTOR - HIGH WINDING TEMPERATUREAn enabled motor winding temperature has exceeded the warning threshold.160.78-O2 p.116
WARNING - REAL TIME CLOCK FAILUREBRAM / real-time clock failed its power-up test.160.78-O2 p.116
WARNING - SETPOINT OVERRIDEBlank or failed BRAM detected at power-up; all setpoints reverted to defaults.160.78-O2 p.116
WARNING - VSD - INPUT VOLTAGE IMBALANCESupply line-to-line voltage imbalance above 5%.160.78-O2 p.116
WARNING - CONDENSER FREEZE THREAT FROM LOW PRESSUREWhile the chiller state is Stopped, the Saturated Condenser Temperature decreased below 35.0°F…160.84-OM1 p.95
WARNING - LIQUID LEVEL SETPOINT NOT ACHIEVEDThe chiller is running and Refrigerant Level > (Refrigerant Level setpoint +15%) or Refrigerant…160.84-OM1 p.96
WARNING - LOSS OF SUBCOOLER LIQUID SEALThe chiller is running greater than 30 minutes and the Subcooler Effectiveness value decreased less…160.84-OM1 p.96
WARNING - MBC - HIGH AXIAL OSCILLATOR VOLTAGEManual reset warning set when the internal oscillator that drives the axial position sensor coil is…160.84-OM1 p.96
WARNING - MBC - HIGH RADIAL OSCILLATOR VOLTAGEManual reset warning set when the internal oscillator that drives the radial position sensor coil…160.84-OM1 p.96
WARNING - MBC - CHECKSUM CENTERINGAppears when the MBC Axial Centering process was never performed, or not correctly realized…160.84-OM1 p.96
WARNING - MBC - DSP WATCHDOGA software reboot has occurred on the control board due to processor problem, but reset with the…160.84-OM1 p.96
WARNING - MBC - AMP WATCHDOGA software reboot has occurred on the amplifier (power) board due to processor problem, but reset…160.84-OM1 p.96
WARNING - MBC - INTERNAL ALARMThe MBC experienced an unsatisfactory condition detected internally to the control system.160.84-OM1 p.96
WARNING - MOTOR - HIGH ROTOR TEMPERATUREOccurs when the estimated rotor temperature exceeds 230°F (110°C) for 3 continuous seconds.160.84-OM1 p.97
WARNING - UPS - BATTERY NOT CONNECTEDAuto reset warning. The minimum and maximum Battery Voltage within each 10 second window is stored;…160.84-OM1 p.97
WARNING - UPS - CHECK BATTERY CONNECTIONManual reset warning set when Battery Voltage > 16.0 V (indicates only the UPS output is connected…160.84-OM1 p.98
WARNING - UPS - LINE LOW BATTERY VOLTAGEAuto reset warning set when all of the following are true: Control Voltage digital input is high…160.84-OM1 p.104
WARNING - UPS - NOT CHARGINGAuto reset warning set when all of the following are true for 5 continuous seconds: Control Voltage…160.84-OM1 p.98

Cycling shutdown messages

Message on the displayWhat it meansManual
CHILLED LIQUID - FLOW SWITCH OPENLoss of chilled liquid flow signal while running or starting.160.78-O2 p.117
CONDENSER - FLOW SWITCH OPENLoss of condenser liquid flow signal while running.160.78-O2 p.117
CONTROL PANEL - LOSS OF CONTROL VOLTAGEControl power input signal low.160.78-O2 p.117
CONTROL PANEL - POWER FAILUREControl power failure occurred (cycling version when displayed in orange).160.78-O2 p.117
CONTROL PANEL - SCHEDULEChiller shut down by its programmed daily schedule.160.78-O2 p.117
EVAPORATOR - LOW PRESSUREEvaporator (suction) pressure fell to the cycling shutdown threshold.160.78-O2 p.118
EXPANSION I/O - SERIAL COMMUNICATIONSCommunication between microboard and expansion I/O board lost.160.78-O2 p.118
LEAVING CHILLED LIQUID - LOW TEMPERATURELeaving chilled liquid fell to the programmed shutdown temperature.160.78-O2 p.118
MBC - HIGH AMPLIFIER TEMPERATUREMBC amplifier board overtemperature (cycling level).160.78-O2 p.118
MBC - HIGH DC/DC TEMPERATUREMBC DC/DC converter board overtemperature (cycling level).160.78-O2 p.118
MBC - SERIAL COMMUNICATIONSInvalid or missing responses from the MBC over Modbus.160.78-O2 p.118
MBC SHUTDOWN - REQUESTING FAULT DATAMBC shut the chiller down; cause not yet received over the serial link.160.78-O2 p.118
MBC - SPEED SIGNAL FAULTMBC lost the speed signal from the VSD during Rotation Mode.160.78-O2 p.119
MBC - STARTUP FAILUREChiller failed to exit the MBC startup state within 60 seconds.160.78-O2 p.119
MBC - STOP (FAULT) CONTACTS OPENMBC ESD fault cause not received within 10 seconds.160.78-O2 p.119
MBC - V13 LOW FREQUENCY DISPLACEMENTExcessive low-frequency shaft displacement at the impeller-end radial bearing, V axis.160.78-O2 p.119
MBC - V13 POSITIONShaft displacement out of position at the impeller-end radial bearing, V axis.160.78-O2 p.119
MBC - V24 LOW FREQUENCY DISPLACEMENTExcessive low-frequency shaft displacement at the opposite-impeller-end radial bearing, V axis.160.78-O2 p.119
MBC - V24 POSITIONShaft displacement out of position at the opposite-impeller-end radial bearing, V axis.160.78-O2 p.119
MBC - W13 LOW FREQUENCY DISPLACEMENTExcessive low-frequency shaft displacement at the impeller-end radial bearing, W axis.160.78-O2 p.119
MBC - W13 POSITIONShaft displacement out of position at the impeller-end radial bearing, W axis.160.78-O2 p.120
MBC - W24 LOW FREQUENCY DISPLACEMENTExcessive low-frequency shaft displacement at the opposite-impeller-end radial bearing, W axis.160.78-O2 p.120
MBC - W24 POSITIONShaft displacement out of position at the opposite-impeller-end radial bearing, W axis.160.78-O2 p.120
MBC - VW13 VIBRATIONSynchronous shaft vibration above limit at the impeller-end radial bearing.160.78-O2 p.120
MBC - VW24 VIBRATIONSynchronous shaft vibration above limit at the opposite-impeller-end radial bearing.160.78-O2 p.120
MBC - Z12 LOW FREQUENCY DISPLACEMENTExcessive axial shaft displacement over a 7-second window.160.78-O2 p.120
MBC - Z12 POSITIONAxial shaft displacement out of position.160.78-O2 p.120
MULTIUNIT CYCLING - CONTACTS OPENExternal multi-unit cycling contacts opened.160.78-O2 p.120
SYSTEM CYCLING - CONTACTS OPENExternal system cycling contacts opened.160.78-O2 p.121
VSD - DC BUS PRE-REGULATIONDC link failed to reach the regulated setpoint after boost control was enabled.160.78-O2 p.121
VSD - HIGH DC BUS VOLTAGEDC link over-voltage.160.78-O2 p.121
VSD - HIGH INTERNAL AMBIENT TEMPERATUREVSD enclosure ambient overtemperature.160.78-O2 p.121
VSD - HIGH PHASE A INPUT CURRENTInput phase A instantaneous overcurrent.160.78-O2 p.121
VSD - HIGH PHASE B INPUT CURRENTInput phase B instantaneous overcurrent.160.78-O2 p.121
VSD - HIGH PHASE C INPUT CURRENTInput phase C instantaneous overcurrent.160.78-O2 p.121
VSD - HIGH PHASE A MOTOR CURRENTMotor phase A instantaneous overcurrent.160.78-O2 p.121
VSD - HIGH PHASE B MOTOR CURRENTMotor phase B instantaneous overcurrent.160.78-O2 p.122
VSD - HIGH PHASE C MOTOR CURRENTMotor phase C instantaneous overcurrent.160.78-O2 p.122
VSD INITIALIZATION FAILEDVSD boards failed power-up initialization.160.78-O2 p.122
VSD - LOGIC BOARD POWER SUPPLYVSD logic board low-voltage supplies out of limits.160.78-O2 p.122
VSD - LOGIC BOARD PROCESSORCommunication failure between the two VSD logic board microprocessors.160.78-O2 p.122
VSD - LOW DC BUS VOLTAGEDC link under-voltage after successful pre-charge.160.78-O2 p.122
VSD - LOW PHASE A INPUT BASEPLATE TEMPERATUREInput rectifier phase A IGBT module too cold.160.78-O2 p.122
VSD - LOW PHASE B INPUT BASEPLATE TEMPERATUREInput rectifier phase B IGBT module too cold.160.78-O2 p.122
VSD - LOW PHASE C INPUT BASEPLATE TEMPERATUREInput rectifier phase C IGBT module too cold.160.78-O2 p.122
VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATUREInverter phase A IGBT module too cold.160.78-O2 p.122
VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATUREInverter phase B IGBT module too cold.160.78-O2 p.122
VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATUREInverter phase C IGBT module too cold.160.78-O2 p.122
VSD - NOT RUNNINGVSD not reporting run state while a run command is issued.160.78-O2 p.122
VSD - PHASE A INPUT DCCT OFFSETInput DCCT offset out of range at pre-charge initiation.160.78-O2 p.123
VSD - PHASE B INPUT DCCT OFFSETInput DCCT offset out of range at pre-charge initiation.160.78-O2 p.123
VSD - PHASE C INPUT DCCT OFFSETInput DCCT offset out of range at pre-charge initiation.160.78-O2 p.123
VSD - PHASE A INPUT GATE DRIVERBoost rectifier phase A gate driver fault.160.78-O2 p.123
VSD - PHASE B INPUT GATE DRIVERBoost rectifier phase B gate driver fault.160.78-O2 p.123
VSD - PHASE C INPUT GATE DRIVERBoost rectifier phase C gate driver fault.160.78-O2 p.123
VSD - PHASE A MOTOR GATE DRIVERInverter phase A gate driver fault.160.78-O2 p.123
VSD - PHASE B MOTOR GATE DRIVERInverter phase B gate driver fault.160.78-O2 p.123
VSD - PHASE C MOTOR GATE DRIVERInverter phase C gate driver fault.160.78-O2 p.123
VSD - PRECHARGE - LOW DC BUS VOLTAGE 1DC bus did not reach the low pre-charge threshold in time.160.78-O2 p.123
VSD - PRECHARGE - LOW DC BUS VOLTAGE 2DC bus did not reach the high pre-charge threshold in time.160.78-O2 p.123
VSD - RUN SIGNALRedundant run commands not both received within 5 seconds.160.78-O2 p.124
VSD - SERIAL COMMUNICATIONSNo response from the VSD logic board over three consecutive attempts.160.78-O2 p.124
VSD - SERIAL RECEIVEVSD not receiving valid communication from the control panel.160.78-O2 p.124
VSD SHUTDOWN - REQUESTING FAULT DATAVSD shut the chiller down; cause not yet received over the serial link.160.78-O2 p.124
VSD - SINGLE PHASE INPUT POWEROne line-to-line input voltage fell below 200 Vrms.160.78-O2 p.124
VSD - STOP (FAULT) CONTACTS OPENVSD fault cause not received within 20 seconds.160.78-O2 p.124
CONDENSER -FREEZE THREAT-FLOW SWITCH OPENSet when all of the following are true: Chiller State is Stopped; Saturated Condenser Temperature <…160.84-OM1 p.99
ISOLATION VALVES - NOT CLOSEDThe optional brine freeze protection motorized isolation valves Close output is energized > 40…160.84-OM1 p.100
MBC - FAULT CONTACTS OPENSee MBC Shutdown - Requesting Fault Data. If the control center's microboard does not receive the…160.84-OM1 p.100
MBC - LOW INPUT VOLTAGEMain DC supply voltage to the MBC decreased below 135 VDC (150%-10%).160.84-OM1 p.100
MBC - UNKNOWN PARAMETER FILESet when the bearing setup parameter file received from Opti-View is not an expected file format.…160.84-OM1 p.101
MBC - Z12 VIBRATIONThe MBC has measured a vibration in axial position at 1 times the rotating frequency whose…160.84-OM1 p.103
UPS - LINE LOW BATTERY VOLTAGEThis cycling fault initiates a soft shutdown if set while the chiller state is Running. Set during…160.84-OM1 p.104
VSD - DC BUS PRE- REGULATIONThe DC Bus voltage has not increased to a value of +/- 50 volts of the DC Bus voltage setpoint of…160.84-OM1 p.104
VSD - INVALID SETPOINTSThe VSD Logic Board is able to determine which model of drive can run which model of motor. If the…160.84-OM1 p.106

Safety shutdown messages

Message on the displayWhat it meansManual
AUXILIARY SAFETY - CONTACTS CLOSEDUser-defined auxiliary safety input tripped.160.78-O2 p.125
CONDENSER - HIGH PRESSURE CONTACTS OPENElectromechanical high pressure safety switch tripped.160.78-O2 p.125
CONDENSER - PRESSURE TRANSDUCER OUT OF RANGECondenser pressure transducer signal outside its valid range.160.78-O2 p.125
DISCHARGE - LOW TEMPERATUREDischarge temperature below 30°F.160.78-O2 p.125
EVAPORATOR - LOW PRESSURE - SMART FREEZESmart Freeze protection timed out with the evaporator below the freeze threshold.160.78-O2 p.126
EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBEEvaporator pressure and leaving chilled liquid readings inconsistent - probable transducer or…160.78-O2 p.126
EVAPORATOR - TRANSDUCER OR TEMPERATURE SENSOREvaporator pressure and refrigerant temperature readings inconsistent - probable sensor defect.160.78-O2 p.127
MBC - CABLE FAULTSupervisory jumper continuity lost in a main cable assembly.160.78-O2 p.127
MBC - CUSTOMER SERIAL LINK DISABLEDMBC serial setting changed away from panel control.160.78-O2 p.127
MBC - DATA ACQUISITION FAULTInternal communication problem on the AMB control board.160.78-O2 p.127
MBC - DSP COMMUNICATIONCommunication error across circuit boards in the MBC.160.78-O2 p.127
MBC - DSP INITIALIZATIONMBC control board software failed to initialize.160.78-O2 p.127
MBC - DSP INTEGRITYInternal problem on the AMB control board.160.78-O2 p.128
MBC - DSP WATCHDOGLapse in MBC microprocessor activity detected by the watchdog.160.78-O2 p.128
MBC - EEPROMData discrepancy with the EPROM on the AMB control board.160.78-O2 p.128
MBC - EXCESSIVE SHUTDOWNSThree MBC cycling shutdowns within 15 minutes.160.78-O2 p.128
MBC - FLASH MEMORY CLEARInternal problem with the memory chip on the AMB control board.160.78-O2 p.128
MBC - FLASH MEMORY WRITEInternal problem with the memory chip on the AMB control board.160.78-O2 p.128
MBC - HIGH BEARING CURRENTMagnetic bearing excitation current above the power amplifier rating.160.78-O2 p.128
MBC - HIGH BEARING Z1 TEMPERATUREImpeller-end axial bearing overtemperature.160.78-O2 p.129
MBC - HIGH BEARING Z2 TEMPERATUREOpposite-impeller-end axial bearing overtemperature.160.78-O2 p.129
MBC - NO LEVITATIONLevitation commanded but the Rotation Allowed input is not high.160.78-O2 p.129
MBC - OSCILLATOR FAULTPosition sensor oscillator overloaded.160.78-O2 p.129
MBC - OVERSPEED FAULTRotor speed above the 458 Hz setpoint.160.78-O2 p.129
MBC - POWER SUPPLY FAULTPower supply board overload or abnormal DC/DC converter voltage.160.78-O2 p.129
MBC - ROTOR ELONGATIONAxial displacement difference above the interpolated limit.160.78-O2 p.130
SAFETY STOPPanel safety stop pushbutton depressed.160.78-O2 p.130
MBC - UNAUTHORIZED ROTATIONRotor speed signal present while Levitation Mode is not activated.160.78-O2 p.130
MOTOR - HIGH WINDING TEMPERATUREMotor winding temperature above the shutdown threshold.160.78-O2 p.130
MOTOR - HIGH HOUSING TEMPERATUREMotor housing temperature at or above 185°F.160.78-O2 p.130
SALES ORDER - INVALID COMPRESSOR MODELCompressor Model field does not conform to the required format.160.78-O2 p.131
SURGE PROTECTION - EXCESS SURGESurge count exceeded the limit with shutdown enabled.160.78-O2 p.131
WATCHDOG - SOFTWARE REBOOTMicroboard software watchdog reset the processor.160.78-O2 p.131
VSD - DC BUS LOCKOUT - DO NOT CYCLE POWERDC bus voltage present while the unit is stopped with no energize command.160.78-O2 p.131
VSD - DC BUS PRE-REGULATION LOCKOUTThird consecutive pre-charge/pre-regulation fault.160.78-O2 p.131
VSD - GROUND FAULTGround fault current above the shutdown value.160.78-O2 p.132
VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATUREInput rectifier phase A baseplate overtemperature.160.78-O2 p.132
VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATUREInput rectifier phase B baseplate overtemperature.160.78-O2 p.132
VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATUREInput rectifier phase C baseplate overtemperature.160.78-O2 p.132
VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATUREMotor baseplate overtemperature (phase A).160.78-O2 p.132
VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATUREMotor baseplate overtemperature (phase B).160.78-O2 p.132
VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATUREMotor baseplate overtemperature (phase C).160.78-O2 p.132
VSD - HIGH TOTAL DEMAND DISTORTIONInput current TDD above 25%.160.78-O2 p.132
VSD - INVERTER PROGRAM FAULTInverter internal code exception.160.78-O2 p.132
VSD - INPUT CURRENT OVERLOADInput RMS current above the 116.7% threshold for 10 seconds.160.78-O2 p.133
VSD - INPUT DCCT OFFSET LOCKOUTThree consecutive input DCCT offset cycling faults.160.78-O2 p.133
VSD - LOGIC BOARD PLUGRectifier or inverter DCCT plug not installed.160.78-O2 p.133
VSD - MOTOR CURRENT IMBALANCEMotor phase current imbalance above 30%.160.78-O2 p.133
VSD - 105% MOTOR CURRENT OVERLOADMotor RMS current above 105% of the 525 A limit for 40 seconds.160.78-O2 p.133
VSD - MOTOR CURRENT THD FAULTMotor current THD above limit.160.78-O2 p.133
VSD - PHASE A INPUT DCCTInput phase A current below the minimum during precharge.160.78-O2 p.133
VSD - PHASE B INPUT DCCTInput phase B current below the minimum during precharge.160.78-O2 p.133
VSD - PHASE C INPUT DCCTInput phase C current below the minimum during precharge.160.78-O2 p.133
VSD - PHASE A MOTOR DCCTMotor phase A DCCT cable/current check failed.160.78-O2 p.133
VSD - PHASE B MOTOR DCCTMotor phase B DCCT cable/current check failed.160.78-O2 p.133
VSD - PHASE C MOTOR DCCTMotor phase C DCCT cable/current check failed.160.78-O2 p.133
VSD - PRECHARGE LOCKOUTThird consecutive pre-charge fault.160.78-O2 p.134
VSD - RECTIFIER PROGRAM FAULTRectifier internal code exception.160.78-O2 p.134
VSD - LINE VOLTAGE PHASE LOCK LOOPDrive cannot determine the input voltage frequency (50/60 Hz).160.78-O2 p.134
VSD - LINE VOLTAGE PHASE ROTATIONInternal phase rotation determinations disagree.160.78-O2 p.134
CONDENSER - HIGH PRESSUREThe condenser pressure, as sensed by the Condenser Transducer, has increased to greater than 200…160.84-OM1 p.108
CONDENSER - HIGH PRESSURE - STOPPEDThe condenser pressure exceeded 170 psig for shells with 235 psig DWP and 264 psig for shells with…160.84-OM1 p.109
CONTROL PANEL - INVALID BRAMOn bootup, the panel shall determine whether a 512K BRAM module is installed by a sequence of tests…160.84-OM1 p.109
DISCHARGE - HIGH TEMPERATUREThe discharge temperature, as sensed by the Discharge Temperature Thermistor, has increased to…160.84-OM1 p.109
INTERNAL ERROR - INVALID BRAMBRAM is detected to be a size other than 512K.160.84-OM1 p.111
ISOLATION VALVES - NOT OPENEDThe optional brine freeze protection motorized isolation valves Open output is energized > 40…160.84-OM1 p.111
MBC - AMP COMMUNICATIONSet when the MBC control board detects a communication error between the control and amplifier…160.84-OM1 p.112
MBC - AMP WATCHDOGSet when the MBC determines a lapse in internal microprocessor activity on the Amplifier Board…160.84-OM1 p.112
MBC - HIGH INPUT VOLTAGEMain DC supply voltage to the MBC exceeded 165 VDC (150+ 10%).160.84-OM1 p.112
MBC - LOW RADIAL OSCILLATOR VOLTAGESet when the internal oscillator that drives the radial position sensor coil is low for one…160.84-OM1 p.113
MBC - HIGH AXIAL OSCILLATOR VOLTAGESet when the internal oscillator that drives the axial position sensor coil is overloaded for one…160.84-OM1 p.113
MBC - LOW AXIAL OSCILLATOR VOLTAGESet when the internal oscillator that drives the axial position sensor coil is low for one…160.84-OM1 p.113
MBC - POWER FAIL LANDINGSet when the panel boots up after a power loss has occurred and the buffer data prior to the…160.84-OM1 p.113
MBC - ROTOR CONTRACTIONSet when the MBC has calculated the algebraic difference between the displacement at shaft impeller…160.84-OM1 p.113
MBC - SPV UNAUTHORIZED ROTATIONSet when the MBC is commanded to Rotation mode while it is not indicating acceptable to rotate. The…160.84-OM1 p.114
MBC - DSP UNAUTHORIZED ROTATIONSet when the MBC detects a rotor speed signal from the VSD while the Levitation Mode is not…160.84-OM1 p.114
MOTOR - HIGH ROTOR TEMPERATUREOccurs when the estimated rotor temperature exceeds 250°F (121°C) for 3 continuous seconds.160.84-OM1 p.114
UPS - BATTERY NOT CONNECTEDInitiates a soft shutdown if set while the chiller state is Running. Set during chiller state…160.84-OM1 p.116
UPS - INVERTER LOW BATTERY VOLTAGESet when all of the following are true for 5 continuous seconds: Battery Voltage Faults is Enabled;…160.84-OM1 p.116
VGD ACTUATOR FAULTThe VGD actuator fault digital input has lost voltage either by wiring issue or fault indicated at…160.84-OM1 p.116
VGD POSITIONING FAULTThe VGD Position feedback indicates greater or less than the VGD command by 5% for 1 minute…160.84-OM1 p.116
VGD FEEDBACK FAULTThe VGD Feedback voltage is below 0.4 VDC or above 4.6 VDC.160.84-OM1 p.116
VSD - LOGIC BOARD HARDWAREAfter power is applied to the chiller, the VSD logic board performs several internal tests to…160.84-OM1 p.119
VSD - PHASE LOCKED LOOPThe VSD must be able to determine the input voltage frequency from the input voltage measurement.…160.84-OM1 p.120

Compressor

Message on the displayWhat it meansManual
Control panel warns of excessive landings of the magnetic bearing motorNotify the nearest Johnson Controls office to request the presence of a Johnson Controls Service…160.78-O1 p.22

Symptom: abnormally high discharge pressure

Message on the displayWhat it meansManual
Temperature difference between condensing temperature and water off condenser higher then normalCondenser tubes dirty or scaled160.78-O1 p.24
High discharge pressureHigh condenser water temperature160.78-O1 p.24
Temperature diffrence between condenser water on and water off higher than normal, with normal discharge temperatureInsufficient condensing water flow160.78-O1 p.24

Symptom: abnormally low suction pressure

Symptom: high evaporator pressure

Message on the displayWhat it meansManual
High chilled water temperatureSystem overload160.78-O1 p.24

Automatic battery health test during shutdown

Message on the displayWhat it meansManual
UPS Battery Health Test Failed - Step XDisplayed when the battery health test fails; X is the step that failed. Fail results occur if: the…160.84-OM1 p.144
Warning - UPS - Battery Test FailedWarning active when the UPS battery health test has failed.160.84-OM1 p.144

FAULTS & WARNINGS

Message on the displayWhat it meansManual
WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI Event Code: 330 GPIC Warning Code: 145Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: All.SI0461 p.2
WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI Event Code: 331 GPIC Warning Code: 146Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: All.SI0461 p.3
WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI Event Code: 332 GPIC Warning Code: 147Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: All.SI0461 p.3
WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE Event Code: 13 GPIC Warning Code: 149Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: Running.SI0461 p.4
WARNING - SYSTEM - REPLACE FILTER-DRIER Event Code: 333 GPIC Warning Code: 150Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: All.SI0461 p.8
WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCIQuarterly Service Required Warning - Manual Reset Warning, no shutdown (Shutdown Type: None). Event…SI0457 p.2
WARNING - YEARLY SERVICE REQUIRED - CONTACT JCIYearly Service Required Warning - Manual Reset Warning, no shutdown (Shutdown Type: None). Event…SI0457 p.3
WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI3 Year Service Required Warning - Manual Reset Warning, no shutdown (Shutdown Type: None). Event…SI0457 p.3
WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCECondenser High Small Temp Difference - Manual Reset Warning, no shutdown (Shutdown Type: None).…SI0457 p.4

PANEL FAULTS & WARNINGS

Message on the displayWhat it meansManual
MBC - HIGH ROTOR ELONGATION RATE Event Code: N/A GPIC Safety Fault Code: 83Safety Fault. Shutdown Type: Immediate. Enable: When Rotor Elongation > 350 µm. Allowed States:…SI0461 p.12
MBC - HIGH ROTOR ELONGATION RATEMBC High Rotor Elongation Rate Fault - Safety Fault, Immediate shutdown. Event Code: N/A. GPIC…SI0457 p.9

VSD COOLING PROTECTION - FAULTS & WARNINGS

Message on the displayWhat it meansManual
WARNING - VSD - HIGH HX APPROACH TEMPERATURE Event Code: N/A GPIC Warning Code: 45Manual Reset Warning. Shutdown Type: None. Enable: Always. Allowed States: Running, Soft Shutdown.SI0461 p.16
VSD - HIGH HX APPROACH TEMPERATURE Event Code: N/A GPIC Safety Fault Code: 94Safety Fault. Shutdown Type: Immediate. Enable: Always. Allowed States: Running, Soft Shutdown.SI0461 p.16
WARNING - VSD - HIGH HX APPROACH TEMPERATUREVSD High HX Approach Temperature Warning - Manual Reset Warning, no shutdown (Shutdown Type: None).…SI0457 p.12
VSD - HIGH HX APPROACH TEMPERATUREVSD High HX Approach Temperature Fault - Safety Fault, Immediate shutdown. Event Code: N/A. GPIC…SI0457 p.13

OUTPUT LINE VOLTAGE ISOLATION BOARD SYMPTOMS

Message on the displayWhat it meansManual
High Phase (A B or C) Motor CurrentHigh motor current at 4 seconds into run.SI0401 p.1
WARNING - VSD - DC Bus ActiveWarning displayed anytime the DC bus voltage is greater than 50 volts and the drive is not in the…SI0401 p.1
Incorrect Voltage Values on the VSD Details ScreenIncorrect values shown on the VSD details screen. Phase A output voltage signal is used for the…SI0401 p.2

Expansion I/O - Serial Communication Fault

Message on the displayWhat it meansManual
Serial Communication FaultLoss of serial communications with the Expansion I/O LTC I/O Board. In this software version the…SI0256 p.1

MOTOR COOLING

Message on the displayWhat it meansManual
MOTOR - LOW WINDING TEMPERATURENew low winding temperature fault added to prevent the chiller from running.SI0393 p.1

LOSS OF SUBCOOLER LIQUID SEAL WARNING

Message on the displayWhat it meansManual
LOSS OF SUBCOOLER LIQUID SEAL WARNINGProgram changed to only check for Loss of Subcooler Liquid Seal when the chiller is loaded above…SI0393 p.2

York Chiller Access Manager

Message on the displayWhat it meansManual
You do not have the correct access level to make the change.Access-level denial message shown when an attempted change is rejected.SI0554 p.2
Your Access Level Doesn't Allow This.Message shown when the current access level does not permit the attempted action.SI0554 p.2

VSD/MBC Initialization

Message on the displayWhat it meansManual
VSD - Initialization In Progress Start InhibitStart inhibit displayed while VSD initialization is in progress.SI0554 p.3
MBC - Initialization in Progress Start InhibitStart inhibit displayed while MBC initialization is in progress.SI0554 p.3

76 of 229 messages have a page of their own. Other documentation for this model: commissioning and checklists · installation · operation · parts lists · service bulletins · specifications · wiring diagrams. All YORK models: YORK manuals.