| Document type | Service Information Letter |
|---|---|
| Document number | SI0457 |
| Equipment | YMC2 Magnetic Bearing Centrifugal Chiller |
| Brand | YORK |
| File size | 4.3 MB |
Fault codes in this document
FAULTS & WARNINGS
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI | Quarterly Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 330. GPIC Warning Code: 145. | Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when Days Since Last Quarterly Service >= 90 Days. | Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Quarterly Service Required Warning Reset”. Days Since Last Quarterly Service is set to 0 when this warning is cleared. Clear/Disable: Quarterly Service Warning is Disabled. | 2 |
| WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI | Yearly Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 331. GPIC Warning Code: 146. | Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when all of the following are true: • Days Since Last Yearly Service >= 365 Days • Operating Hours Since Last Yearly Service > 2,890 Hours (33% of a year’s run hours = 24*365*0.33) |
Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Yearly Service Required Warning Reset”. When this warning is cleared: Days Since Last Yearly Service is set to 0, Operating Hours Since Last Yearly Service is set to 0, and Purge Count Since Last Filter-Drier Replacement is set to 0. Clear/Disable: Yearly Service Warning is Disabled. | 3 |
| WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI | 3 Year Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 332. GPIC Warning Code: 147. | Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when Days Since Last 3 Year Service >= 1095 Days. | Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “3 Year Service Required Warning Reset”. Days Since Last 3 Year Service is set to 0 when this warning is cleared. Clear/Disable: 3 Year Service Warning is Disabled. | 3 |
| WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE | Condenser High Small Temp Difference — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 13. GPIC Warning Code: 149. | Enable: Always. Allowed States: Running. Bypass Time: None. Trip Time: 30 Minutes. Set Event: Set when Condenser Small Temp Difference > Condenser Small Temp Difference Warning Threshold. | Release Event: Release when Condenser Small Temp Difference <= Condenser Small Temp Difference Warning Threshold. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Condenser High Small Temp Difference Warning Reset”. Clear/Disable: Condenser High Small Temp Difference Warning is Disabled. | 4 |
PANEL FAULTS & WARNINGS
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| MBC - HIGH ROTOR ELONGATION RATE | MBC High Rotor Elongation Rate Fault — Safety Fault, Immediate shutdown. Event Code: N/A. GPIC Safety Fault Code: 83. | Enable: When Rotor Elongation > 350 µm. Allowed States: Running, Soft Shutdown. Bypass Time: 1 Minute. Trip Time: 1 Minute / 3 Minutes (see set criteria). Set Event: Set when either of the following are true: • Rotor Elongation Rate > Rotor Elongation Fault Low Rate for 3 Minutes • Rotor Elongation Rate > Rotor Elongation Fault High Rate for 1 Minute |
Immediate shutdown. Release Event: Release when set criteria is not true. Clear/Disable: Never. Reset Password: None. Special Handling: None. | 9 |
VSD COOLING PROTECTION — FAULTS & WARNINGS
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| WARNING - VSD - HIGH HX APPROACH TEMPERATURE | VSD High HX Approach Temperature Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: N/A. GPIC Warning Code: 45. | Enable: Always. Allowed States: Running, Soft Shutdown. Bypass Time: 20 Minutes. Trip Time: 10 Minutes. Set Event: Set when VSD HX Approach Temp > Expected VSD HX Approach Temp + VSD HX Approach Temp Warning Offset. | Release Event: Release when set criteria not true. Reset Password: None. Special Handling: None. Clear/Disable: VSD Cooling Protection is Disabled. | 12 |
| VSD - HIGH HX APPROACH TEMPERATURE | VSD High HX Approach Temperature Fault — Safety Fault, Immediate shutdown. Event Code: N/A. GPIC Safety Fault Code: 94. | Enable: Always. Allowed States: Running, Soft Shutdown. Bypass Time: 20 Minutes. Trip Time: 10 Minutes. Set Event: Set when VSD HX Approach Temp > Expected VSD HX Approach Temp + VSD HX Approach Temp Fault Offset. | Immediate shutdown. Release Event: Release when set criteria is not true. Reset Password: None. Special Handling: None. Clear/Disable: VSD Cooling Protection is Disabled. | 13 |
UNIT WARNING CODES (SC.4)
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| 6 | WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI | 7 | ||
| 7 | WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI | 7 | ||
| 8 | WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI | 7 | ||
| 9 | WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE | 7 | ||
| 45 | WARNING - VSD - HIGH HX APPROACH TEMPERATURE | 18 |
UNIT SAFETY FAULT CODES (SC.2)
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| 83 | MBC - HIGH ROTOR ELONGATION RATE | 11 | ||
| 94 | VSD - HIGH HX APPROACH TEMPERATURE | 18 |