YMC2 Mod B Software Changes V11

Document typeService Information Letter
Document numberSI0457
EquipmentYMC2 Magnetic Bearing Centrifugal Chiller
BrandYORK
File size4.3 MB

Fault codes in this document

1 of these messages are explained on a page of their own — cause, what to check, reset — written from this manual:

FAULTS & WARNINGS

Code / displayMeaningCauseActionPage
WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI Quarterly Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 330. GPIC Warning Code: 145. Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when Days Since Last Quarterly Service >= 90 Days. Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Quarterly Service Required Warning Reset”. Days Since Last Quarterly Service is set to 0 when this warning is cleared. Clear/Disable: Quarterly Service Warning is Disabled. 2
WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI Yearly Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 331. GPIC Warning Code: 146. Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when all of the following are true:
• Days Since Last Yearly Service >= 365 Days
• Operating Hours Since Last Yearly Service > 2,890 Hours (33% of a year’s run hours = 24*365*0.33)
Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Yearly Service Required Warning Reset”. When this warning is cleared: Days Since Last Yearly Service is set to 0, Operating Hours Since Last Yearly Service is set to 0, and Purge Count Since Last Filter-Drier Replacement is set to 0. Clear/Disable: Yearly Service Warning is Disabled. 3
WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI 3 Year Service Required Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 332. GPIC Warning Code: 147. Enable: Always. Allowed States: All. Bypass Time: None. Trip Time: Instantaneous. Set Event: Set when Days Since Last 3 Year Service >= 1095 Days. Release Event: Release after set. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “3 Year Service Required Warning Reset”. Days Since Last 3 Year Service is set to 0 when this warning is cleared. Clear/Disable: 3 Year Service Warning is Disabled. 3
WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE Condenser High Small Temp Difference — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: 13. GPIC Warning Code: 149. Enable: Always. Allowed States: Running. Bypass Time: None. Trip Time: 30 Minutes. Set Event: Set when Condenser Small Temp Difference > Condenser Small Temp Difference Warning Threshold. Release Event: Release when Condenser Small Temp Difference <= Condenser Small Temp Difference Warning Threshold. Manual reset required; Reset Password: 0726. Manual Reset of this warning shall be added into the Security Log with the message of “Condenser High Small Temp Difference Warning Reset”. Clear/Disable: Condenser High Small Temp Difference Warning is Disabled. 4

PANEL FAULTS & WARNINGS

Code / displayMeaningCauseActionPage
MBC - HIGH ROTOR ELONGATION RATE MBC High Rotor Elongation Rate Fault — Safety Fault, Immediate shutdown. Event Code: N/A. GPIC Safety Fault Code: 83. Enable: When Rotor Elongation > 350 µm. Allowed States: Running, Soft Shutdown. Bypass Time: 1 Minute. Trip Time: 1 Minute / 3 Minutes (see set criteria). Set Event: Set when either of the following are true:
• Rotor Elongation Rate > Rotor Elongation Fault Low Rate for 3 Minutes
• Rotor Elongation Rate > Rotor Elongation Fault High Rate for 1 Minute
Immediate shutdown. Release Event: Release when set criteria is not true. Clear/Disable: Never. Reset Password: None. Special Handling: None. 9

VSD COOLING PROTECTION — FAULTS & WARNINGS

Code / displayMeaningCauseActionPage
WARNING - VSD - HIGH HX APPROACH TEMPERATURE VSD High HX Approach Temperature Warning — Manual Reset Warning, no shutdown (Shutdown Type: None). Event Code: N/A. GPIC Warning Code: 45. Enable: Always. Allowed States: Running, Soft Shutdown. Bypass Time: 20 Minutes. Trip Time: 10 Minutes. Set Event: Set when VSD HX Approach Temp > Expected VSD HX Approach Temp + VSD HX Approach Temp Warning Offset. Release Event: Release when set criteria not true. Reset Password: None. Special Handling: None. Clear/Disable: VSD Cooling Protection is Disabled. 12
VSD - HIGH HX APPROACH TEMPERATURE VSD High HX Approach Temperature Fault — Safety Fault, Immediate shutdown. Event Code: N/A. GPIC Safety Fault Code: 94. Enable: Always. Allowed States: Running, Soft Shutdown. Bypass Time: 20 Minutes. Trip Time: 10 Minutes. Set Event: Set when VSD HX Approach Temp > Expected VSD HX Approach Temp + VSD HX Approach Temp Fault Offset. Immediate shutdown. Release Event: Release when set criteria is not true. Reset Password: None. Special Handling: None. Clear/Disable: VSD Cooling Protection is Disabled. 13

UNIT WARNING CODES (SC.4)

Code / displayMeaningCauseActionPage
6WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI7
7WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI7
8WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI7
9WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE7
45WARNING - VSD - HIGH HX APPROACH TEMPERATURE18

UNIT SAFETY FAULT CODES (SC.2)

Code / displayMeaningCauseActionPage
83MBC - HIGH ROTOR ELONGATION RATE11
94VSD - HIGH HX APPROACH TEMPERATURE18

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication. The short table of all YORK YMC2 messages: fault codes.