YMC² Mod A 3630 OptiView Software V11

Document typeService Information Letter
Document numberSI0555
EquipmentYMC2 Magnetic Bearing Centrifugal Chiller
BrandYORK
File size0.2 MB

Fault codes in this document

1 of these messages are explained on a page of their own — cause, what to check, reset — written from this manual:

Fault Values

Code / displayMeaningCauseActionPage
WARNING – CONDENSER OR VGD SENSOR FAILURE Manual Reset Warning. Shutdown Type: None. (In software V11 this warning was corrected so that it is set whenever the set condition is satisfied.) Set when the difference between the Condenser Pressure and Discharge Pressure is > 21 PSID or < -21 PSID. Enable: Always; Clear/Disable: Never. Allowed States: Running. Bypass Time: None; Trip Time: 3 minutes. Release Event: releases when the set condition is not true. As a Manual Reset Warning, it must be manually reset. 3