| Document type | Service Information Letter |
|---|
| Document number | SI0554 |
|---|
| Equipment | YMC2 Magnetic Bearing Centrifugal Chiller |
|---|
| Brand | YORK |
|---|
| File size | 0.2 MB |
|---|
Fault codes in this document
1 of these messages are explained on a page of their own — cause, what to check, reset — written from this manual:
York Chiller Access Manager
| Code / display | Meaning | Cause | Action | Page |
| You do not have the correct access level to make the change. | Access-level denial message shown when an attempted change is rejected. | Displayed in error when pressing the Maintenance Acknowledge button in Enhanced access with the correct password entered, so the warning could not be cleared. | Corrected in this software release. | 2 |
| Your Access Level Doesn’t Allow This. | Message shown when the current access level does not permit the attempted action. | Displayed in error when pressing the Page Down button on the Access Log screen in Enhanced access, so the next page would not display. | Corrected in this software release. | 2 |
VSD/MBC Initialization
| Code / display | Meaning | Cause | Action | Page |
| VSD – Initialization In Progress Start Inhibit | Start inhibit displayed while VSD initialization is in progress. | Appeared after bootup and could not be cleared when updating software (earlier software versions). | This has been corrected in this software release. | 3 |
| MBC – Initialization in Progress Start Inhibit | Start inhibit displayed while MBC initialization is in progress. | Appeared after bootup and could not be cleared when updating software (earlier software versions); either this inhibit or the VSD one could appear. | This has been corrected in this software release. | 3 |
MBC
| Code / display | Meaning | Cause | Action | Page |
| MBC – POWER FAIL LANDING | Fault set on the MBC. | | Cleared using the Clear Fault button. Earlier software did not always display the Clear Fault button when this fault was set; this has been corrected in this software release. | 3 |