On the display
The panel shows WARNING - EXCESS SURGE DETECTED. The manuals print this message in a single form only; there are no other variants. It is a warning, not a safety shutdown: the chiller continues to run under the same conditions while the message is displayed. The message stays on the display until it is manually reset.
What it means
The Surge Window Count has exceeded the Count Limit. Both manuals state that this warning applies only if the Surge Protection SHUTDOWN feature is Disabled — that is the mode in which an excess surge condition is signalled by this warning while the chiller keeps running. If the Shutdown setpoint is Enabled, an excess surge condition performs a safety shutdown instead of showing this warning.
Why it appears
- The Surge Window Count has exceeded the Count Limit.
- The Surge Protection SHUTDOWN feature is Disabled: the warning is defined only for this mode, since with the feature Enabled an excess surge condition produces a safety shutdown instead.
Setpoints and thresholds
- Surge Protection SHUTDOWN — the feature (also referred to as the Shutdown setpoint) that decides how an excess surge condition is handled: Enabled, it performs a safety shutdown; Disabled, the chiller keeps running and this warning is displayed.
- Count Limit — the threshold the Surge Window Count is compared against. The warning can be cleared only once the count is less than or equal to it; the manuals give no numeric value for it in the description of this warning.
Reset and restart
The warning does not clear by itself; it displays until a manual reset. Clearing is possible once any one of the following is true: the Surge Window Count is less than or equal to the Count Limit, the Surge Protection SHUTDOWN feature is Enabled, or the chiller is stopped. Then: To clear message press WARNING RESET button on HOME Screen when logged in at OPERATOR (or higher) access level.
The operation manual names the same control the Warning Reset key and ties the reset to the operator access level.
Questions engineers ask
What does WARNING - EXCESS SURGE DETECTED mean on a YORK YMC2?
It means the Surge Window Count has exceeded the Count Limit. The warning applies only when the Surge Protection SHUTDOWN feature is Disabled, and the chiller keeps running while it is displayed.
How do I clear the EXCESS SURGE DETECTED warning?
Clear it once the Surge Window Count is less than or equal to the Count Limit, the SHUTDOWN feature is Enabled, or the chiller is stopped: press the WARNING RESET button on the HOME Screen while logged in at OPERATOR or higher access level.
Why is my YMC2 still running with a surge warning on the display?
Because the Surge Protection SHUTDOWN feature is Disabled. With that setpoint Enabled, an excess surge condition would perform a safety shutdown instead of showing this warning.
Why will the surge warning not reset?
The reset only works after the Surge Window Count has fallen to the Count Limit or below, or the SHUTDOWN feature has been Enabled, or the chiller has been stopped — and it must be done with the WARNING RESET button on the HOME Screen at OPERATOR (or higher) access level.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YMC2 messages: fault codes · YORK YMC2 documentation · YORK manuals