On the display
The panel shows WARNING - MBC - HIGH RADIAL OSCILLATOR VOLTAGE. The manual prints this exact wording as the only variant. It appears in two listings of the same manual — as a manual reset warning and among the safety shutdown messages — with the same description in both places.
What it means
The internal oscillator that drives the radial position sensor coil has been overloaded for one continuous second. This oscillator feeds the coil of the sensor that reports the radial position of the shaft, so the message concerns that sensing circuit. While the condition is set, the MBC Fault contacts open. The manual treats the message as a manual reset warning: releasing it requires both a normal oscillator voltage and a reset action by the operator.
Why it appears
- An opening in the connection to the shaft position sensor — the cause the manual names as typical.
- A failure of the MBC control board.
Setpoints and thresholds
- The overload must last one continuous second for the message to be set; the manual prints no adjustable setpoint for this warning.
Reset and restart
The oscillator voltage has to return to normal before anything else. The manual then gives the reset path: this message will clear when the voltage is normal and the warning reset key is pressed in operator (or higher) access mode
. In the safety shutdown description, the condition is released when the oscillator voltage drop is normal, and the chiller can be started when the condition is released and the OptiView panel clear faults button is pressed
.
Questions engineers ask
What does WARNING - MBC - HIGH RADIAL OSCILLATOR VOLTAGE mean on a YORK YMC2?
The internal oscillator that drives the radial position sensor coil was overloaded for one continuous second. While the message is set, the MBC Fault contacts open.
What causes the MBC high radial oscillator voltage warning on a YMC2?
Typically an opening in the connection to the shaft position sensor. The manual also names a failure of the MBC control board as a possible cause.
How do I clear the MBC high radial oscillator voltage warning?
Once the oscillator voltage is normal, press the warning reset key in operator (or higher) access mode. The chiller can be started when the condition is released and the clear faults button on the OptiView panel is pressed.
When can the YMC2 be restarted after this MBC warning?
The condition is released when the oscillator voltage drop is normal. After that, the chiller can be started once the clear faults button on the OptiView panel is pressed.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: