On the display
The panel shows WARNING - EVAPORATOR - LOW PRESSURE LIMIT, in exactly this wording. The manual lists no other variant of this message. It appears in the group of warning messages for this chiller.
What it means
The evaporator pressure has decreased to the Warning threshold. While this condition is in effect, the chiller capacity control is in override to increase suction pressure — the control deliberately shifts capacity to bring the suction pressure back up. The condition ends on its own: when the evaporator pressure increases to the reset value, the message clears automatically and normal LCHLT capacity control is restored. No other response of the machine to this warning is described in the manual.
Why it appears
- The evaporator pressure has decreased to the Warning threshold — the manual gives no other cause for this message. Which numeric threshold that is depends on the refrigerant and on whether the application is Water cooling or Brine cooling (see the thresholds below).
Setpoints and thresholds
The manual prints warning and reset thresholds in psig for each refrigerant, separately for Water cooling and Brine cooling applications. In Water cooling applications the values are fixed. In Brine applications the values are offsets above the programmable safety shutdown threshold (Safety setpoint), and that Safety threshold is determined by the brine solution at the YORK Factory — so the actual pressures are these offsets above the safety setpoint configured for the brine in the machine.
- R-134a — Water: warning 27.8 psig, reset 28.8 psig. Brine: warning 1.7 psig above Safety setpoint, reset 2.7 psig above Safety setpoint.
- R-513A — Water: warning 32.0 psig, reset 33.0 psig. Brine: warning 1.8 psig above Safety setpoint, reset 2.8 psig above Safety setpoint.
- R-1234ze — Water: warning 16.7 psig, reset 17.7 psig. Brine: warning 1.3 psig above Safety setpoint, reset 2.3 psig above Safety setpoint.
- R-515B — Water: warning 16.5 psig, reset 17.5 psig. Brine: warning 1.3 psig above Safety setpoint, reset 2.3 psig above Safety setpoint.
Reset and restart
Recovery is automatic; the manual describes no manual clearing or acknowledgment step for this warning. This message automatically clears and normal LCHLT capacity control restored when the Evaporator pressure increases to the reset value.
Once the evaporator pressure has risen to the reset threshold that matches the refrigerant and application listed above, the override ends and normal LCHLT capacity control resumes.
Questions engineers ask
What does WARNING - EVAPORATOR - LOW PRESSURE LIMIT mean on a YORK YMC2?
It means the evaporator pressure has decreased to the Warning threshold. While the condition lasts, the chiller capacity control is in override to increase suction pressure.
How do I clear or reset this warning on the YMC2?
No manual reset is described — the message clears itself. It automatically clears and normal LCHLT capacity control is restored as soon as the evaporator pressure increases to the reset threshold for the refrigerant in the machine.
What are the warning and reset pressures for R-134a?
In Water cooling applications the warning threshold is 27.8 psig and the reset threshold is 28.8 psig. In Brine applications the warning threshold is 1.7 psig and the reset threshold 2.7 psig above the Safety setpoint.
Why is no fixed pressure value given for brine applications?
Because in Brine applications the warning threshold is a fixed amount above the programmable safety shutdown threshold, and that Safety threshold is determined by the brine solution at the YORK Factory. The offsets above it for each refrigerant are listed on this page.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: