YORK YMC2WARNING - VSD - INPUT VOLTAGE IMBALANCE

On the display

The panel reads WARNING - VSD - INPUT VOLTAGE IMBALANCE — this exact wording, in this capitalisation, is the only form the manuals print. Both manuals place it among the warning messages, not among the shutdown messages, and both tie it to the input voltage of the VSD: the line-to-line voltages the control receives from the drive.

What it means

The supply line-to-line voltage imbalance is above 5%. On every VSD communications cycle the control takes the three line-to-line total RMS voltages Vab, Vbc and Vca received from the drive, averages them into Vavg, and calculates the imbalance as Vimb% = max(|Vab-Vavg|,|Vbc-Vavg|,|Vca-Vavg|) x 100%/Vavg — in words, how far the worst of the three line-to-line voltages sits from that average, expressed as a percentage of it; the max function simply selects the largest of its arguments. If Vimb% exceeds 5% continuously for 45 seconds, the warning is displayed.

Why it appears

  • Line voltage imbalance above 5%, sustained continuously for 45 seconds. The imbalance is recalculated on every VSD communications cycle from the line-to-line RMS voltages (Vab, Vbc, Vca) that the drive reports; the manuals list no other cause for this warning.

Setpoints and thresholds

  • Warning threshold: line voltage imbalance above 5% of the average line-to-line voltage.
  • Warning delay: 45 seconds of continuous exceedance, evaluated on every VSD communications cycle.
  • Inputs used: the line-to-line total RMS voltages Vab, Vbc and Vca received from the drive.
  • Clear condition: three consecutive imbalance readings below the 5% threshold.

Reset and restart

No manual reset step is described for this warning — it clears by itself once the condition goes away. The manuals state: The 45 second timer shall reset and the warning shall clear if three consecutive imbalance readings fall below the 5% threshold. The supply imbalance therefore has to stay below 5% across three successive readings before the message leaves the display.

Questions engineers ask

What does WARNING - VSD - INPUT VOLTAGE IMBALANCE mean on a YORK YMC2?

That the supply line-to-line voltage imbalance measured at the VSD is above 5%. The control calculates the imbalance on every VSD communications cycle from the line-to-line total RMS voltages (Vab, Vbc, Vca) received from the drive.

How is the input voltage imbalance calculated?

Vimb% = max(|Vab-Vavg|,|Vbc-Vavg|,|Vca-Vavg|) x 100%/Vavg, where Vavg is the average of the three line-to-line voltages. The warning displays if Vimb% exceeds 5% continuously for 45 seconds.

How does the VSD input voltage imbalance warning clear?

It clears automatically: the 45 second timer resets and the warning clears once three consecutive imbalance readings fall below the 5% threshold. No manual reset step is described for this warning.

Why does the warning stay on?

Because the readings keep exceeding 5%. The warning can only clear when three consecutive readings come in below the 5% threshold.