Warning · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2WARNING - CONDENSER OR EVAPORATOR XDCR ERROR

On the display

The panel displays WARNING - CONDENSER OR EVAPORATOR XDCR ERROR, printed exactly in this wording and capitalisation. It is listed among the warning messages of the YMC2 control panel; the action the manual assigns to it concerns only the display of the message and its release with a warning reset. In its description of this message the manual ties it to the evaporator and condenser pressure transducers.

What it means

The warning means that the evaporator pressure transducer reads a higher pressure than the condenser pressure transducer. The manual calls such a crossed reading indicative of a Condenser or Evaporator Transducer failure — one of the two pressure transducers is no longer reporting a believable pressure, so the panel flags a suspected transducer fault.

Why it appears

  • After the chiller has been running for 10 minutes, the evaporator pressure transducer is indicating a higher pressure than the condenser pressure transducer; this crossed reading is the condition the warning reports.
  • The manual attributes the crossed reading to a failure of the condenser or evaporator pressure transducer and gives no other cause.

Setpoints and thresholds

  • Detection time: the comparison between the two transducers that raises this warning is made after the chiller has been running for 10 minutes.
  • Brine mode: the manual notes that this condition is not checked in Brine mode.

Reset and restart

The message leaves the display only when two things have happened: the underlying condition has cleared, and the warning has been reset from the keypad. The manual states: This message will be displayed until the condition clears and the WARNING RESET Keypad button is pressed in OPERATOR (or higher) access mode. Pressing the WARNING RESET keypad button therefore requires at least OPERATOR access level, and the manual describes no other reset or recovery procedure for this warning.

Questions engineers ask

What does WARNING - CONDENSER OR EVAPORATOR XDCR ERROR mean on a YORK YMC2?

The evaporator pressure transducer is reading a higher pressure than the condenser pressure transducer after the chiller has been running for 10 minutes, which the manual calls indicative of a condenser or evaporator transducer failure.

How do I clear the CONDENSER OR EVAPORATOR XDCR ERROR warning?

Once the condition clears, press the WARNING RESET keypad button in OPERATOR or higher access mode. The message stays on the display until both the condition has cleared and the reset has been pressed.

Why does the warning appear only after the chiller has been running for a while?

The comparison between the evaporator and condenser pressure transducers is made after the chiller has been running for 10 minutes, so the crossed reading is only detected from that point on.

Is the evaporator versus condenser transducer check active in Brine mode?

No. The manual notes that this condition is not checked in Brine mode.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: