Safety shutdown · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2MBC - HIGH AMPLIFIER TEMPERATURE

On the display

The panel shows MBC - HIGH AMPLIFIER TEMPERATURE. The manuals print the message in this single form, with no variants. It is listed both among the Cycling shutdown messages and among the Safety shutdown messages of the chiller, so the same display text covers a cycling-level and a safety-level amplifier overtemperature trip.

What it means

The message reports an overtemperature condition on the MBC amplifier board. At cycling level, the shutdown is set when the amplifier temperature rises above its trip value; the control software detects the condition from the amplifier-temperature data that arrives over the serial comms. At safety level, the shutdown is set when the temperature of the MBC amplifier rises above 158°F (70°C) and stays there for 1 second continuous — one of the fault tables instead describes the safety trip as a 2-second continuous condition. When the safety shutdown is set, the fault contacts of the MBC open; the other table calls them the MBC ESD Fault contacts. After the safety trip, the MBC keeps the motor shaft levitated until the VSD rotation signal shows less than 10 Hz, and it then de-levitates the rotor.

Why it appears

  • The amplifier temperature rises above the cycling trip value; the control software evaluates this from the amplifier-temperature data sent over the serial comms.
  • The amplifier temperature rises above 158°F (70°C) and is held there for 1 second continuous, which sets the safety shutdown.
  • In a second fault-table description, the safety shutdown is set when the amplifier temperature is sustained above its trip value for 2 seconds continuous.

What to check

  1. Check the connection between the board and the heatsink.
  2. Check how the temperature sensor on the board responds.

Setpoints and thresholds

  • Safety-level trip: the MBC amplifier trip is reached at 158°F (70°C), held for 1 second continuous.
  • Second fault-table description: the safety trip is a 2-second continuous condition on the amplifier trip value.
  • De-levitation point: the rotor is de-levitated once the VSD rotation signal is under 10 Hz.

Reset and restart

Once the safety shutdown has tripped, it is released when the amplifier temperature has fallen back below the trip value. After the condition is released, press the CLEAR FAULTS button on the panel; the chiller can then be started.

Questions engineers ask

What temperature triggers MBC - HIGH AMPLIFIER TEMPERATURE on a YORK YMC2?

The safety shutdown is set when the MBC amplifier temperature rises above 158°F (70°C) and stays there for 1 second continuous. The fault tables also carry a cycling-level trip on amplifier temperature, which the control software evaluates from the data arriving over the serial comms.

How do I clear MBC - HIGH AMPLIFIER TEMPERATURE?

Wait until the amplifier temperature has fallen back below the trip value, which releases the shutdown. Then press the CLEAR FAULTS button on the panel, and the chiller can be started.

What should I check when this message appears?

The manual names two checks: the connection between the board and the heatsink, and the response of the temperature sensor on the board.

What happens to the motor shaft when the safety shutdown trips?

The MBC opens its fault contacts and keeps the shaft levitated until the VSD rotation signal drops below 10 Hz. The MBC then de-levitates the rotor.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: