Fault · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2LEAVING CHILLED LIQUID - LOW TEMPERATURE

On the display

The control center shows LEAVING CHILLED LIQUID - LOW TEMPERATURE. The manuals print the message only in this wording. It is classified with the cycling shutdown messages, and the manuals list it among the events that initiate a soft shutdown while the chiller is running.

What it means

The Leaving Chilled Liquid Temperature has decreased to the programmed Shutdown Temperature Setpoint, the low limit defined for the leaving chilled liquid. If the chiller is running when this occurs, a soft shutdown is performed. During a soft shutdown the drive speed is ramped to 0 Hz and the chiller then transitions to coastdown. The chiller is not left down: it restarts automatically at the programmed Restart Temperature Setpoint (see reset below).

Why it appears

  • The Leaving Chilled Liquid Temperature fell to the programmed Shutdown Temperature Setpoint — the offset below the leaving chilled liquid temperature setpoint that establishes the minimum allowed temperature for the leaving chilled liquid and prevents over-cooling of the building.
  • The shutdown offset in effect can change automatically so the leaving chilled liquid temperature never goes below the minimum allowed value (36°F for water, 34°F for water with Smart Freeze enabled, 6°F for brine). A shutdown can therefore occur at a higher temperature than the programmed offset alone suggests.

What to check

  1. On the evaporator screen of the control center, read the Temperature Setpoints - Shutdown display: it shows the leaving chilled liquid temperature at which the chiller shuts down on this cycling shutdown, calculated automatically from the temperature setpoint minus the shutdown offset and limited to the chiller minimum.
  2. Read the Effective Offset display, which shows the present value of the leaving chilled liquid temperature shutdown offset in effect, limited by the chiller minimum temperature.
  3. Read the Temperature Setpoints - Restart display — the leaving chilled liquid temperature at which the chiller will restart after this shutdown — together with its restart offset.
  4. If the chiller tripped at a temperature above the programmed shutdown value, check whether the Leaving Chilled Liquid Temperature setpoint was increased within the last 10 minutes: the shutdown threshold is held at 36.0°F (water), 34.0°F (Smart Freeze) or 6.0°F (brine) for the next 10 minutes after such an increase, and only then becomes the programmed setpoint value.

Setpoints and thresholds

  • Leaving Chilled Liquid Temperature Cycling Offset - Shutdown (OPERATOR access): defines the shutdown temperature as an offset below the Leaving Chilled Liquid Temperature setpoint, programmable over a range of 1°F to 64°F below the setpoint.
  • Minimum cutout: 36°F for water, 34°F for water with Smart Freeze enabled, 6°F for brine. Smart Freeze is switched Off/On at SERVICE access and is only available if the chiller is not in Brine mode.
  • Hold after a setpoint change: anytime the Leaving Chilled Liquid Temperature setpoint is increased, the shutdown threshold is 36.0°F (water) or 6.0°F (brine) — 34.0°F with Smart Freeze enabled — for the next 10 minutes; after 10 minutes have elapsed, the shutdown threshold becomes the programmed setpoint value.
  • Leaving Chilled Liquid Temperature Cycling Offset - Restart (OPERATOR access): defines the restart temperature as an offset above the setpoint, programmable over a range of 0°F to 80°F above the setpoint, to a maximum restart value of 80°F. The chiller automatically restarts when this temperature is reached; delaying the restart until the cooling load has increased is a way to reduce chiller cycling.
  • Related displays: Temperature Setpoints - Restart shows the restart temperature with its offset; Effective Offset shows the shutdown offset in effect; the shutdown temperature itself is calculated from the temperature setpoint minus the shutdown offset setpoint.
  • Heat pump operation in heating mode: the heating-mode shutdown temperature defaults to the leaving condenser liquid temperature setpoint minus 60°F, its low limit is the higher of the leaving condenser liquid temperature setpoint minus 86°F or the cooling-mode shutdown temperature, and the heat pump restarts when the leaving chilled liquid temperature exceeds the shutdown temperature by 5°F.

Reset and restart

The manual gives no operator reset for this fault — it is a cycling shutdown, so the unit comes back on its own. The chiller will automatically restart when the temperature increases to the programmed Restart Temperature Setpoint. That restart temperature is programmed as an offset above the Leaving Chilled Liquid Temperature setpoint, so the restart can be delayed until the cooling load has increased, which the manual notes is a way to reduce chiller cycling.

Questions engineers ask

Why does my YORK YMC2 shut down on LEAVING CHILLED LIQUID - LOW TEMPERATURE?

The Leaving Chilled Liquid Temperature decreased to the programmed Shutdown Temperature Setpoint — the low limit set by the shutdown offset below the chilled liquid temperature setpoint. If the chiller was running when this occurred, a soft shutdown is performed.

Will the YMC2 restart by itself after this low temperature shutdown?

Yes. It is a cycling shutdown: the chiller automatically restarts once the leaving chilled liquid temperature increases to the programmed Restart Temperature Setpoint, with no operator action.

What is the lowest allowed leaving chilled liquid temperature on the YMC2?

The minimum cutout is 36°F for water, 34°F for water with Smart Freeze enabled and 6°F for brine. After the chilled liquid setpoint is increased, the shutdown threshold is held at 36.0°F, 34.0°F or 6.0°F respectively for the next 10 minutes.

How do I stop the chiller from short-cycling on this fault?

Raise the Leaving Chilled Liquid Temperature Cycling Offset - Restart, programmable from 0°F to 80°F above the setpoint up to a maximum restart value of 80°F, so the restart is delayed until the cooling load has increased.

Messages next to this one

The same message on other models

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: