Fault · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2MBC - W24 POSITION

On the display

The control center displays the message MBC - W24 POSITION. The manuals print it in this form only, so this is the exact text to expect on the panel. It belongs to the unit's cycling shutdown messages, and the manual text treats it as a shutdown rather than a warning.

What it means

MBC - W24 POSITION means that the MBC has measured shaft displacement greater than the trip threshold from center in the orthogonal radial axis designated W at the opposite-impeller-end radial magnetic bearing, during Levitation or Rotation mode. How far that is from the touchdown bearing is printed two ways: approximately half of the air gap space to the touchdown bearing at the 75 µm threshold, and approximately 2/3 of the air gap space to the touchdown bearing at the 100 micron threshold. When the limit is exceeded, the MBC fault contacts open — the manual that gives the 75 µm value calls them the MBC ESD Fault contacts. The shaft does not drop at once: the MBC remains in Levitation mode with the motor shaft levitated until it is commanded to de-levitate over serial comms or, in that manual, until the VSD DC buss power depletes.

Why it appears

  • Shaft displacement greater than the trip threshold from center in the orthogonal radial axis designated W at the opposite-impeller-end radial magnetic bearing, while the machine is in Levitation or Rotation mode. The manuals give no other cause and no contributing conditions for this message.

Setpoints and thresholds

  • Trip threshold, one manual: displacement greater than 75 µm from center in the W axis — approximately half of the air gap space to the touchdown bearing.
  • Trip threshold, other manual: displacement greater than 100 micron from center in the W axis — approximately 2/3 of the air gap space to the touchdown bearing.
  • Release point: the shutdown is released when displacement is less than 75 µm in the first manual, and less than 100 micron in the second.

Reset and restart

No manual reset procedure is described for this message. The shutdown releases itself when the measured displacement falls back below the value that tripped it — less than 75 µm in one manual, less than 100 micron in the other. Until then the MBC stays in Levitation mode with the motor shaft levitated, and it leaves Levitation mode only when commanded to de-levitate over serial comms or, per the manual with the 75 µm value, when the VSD DC buss power depletes.

Questions engineers ask

What does MBC - W24 POSITION mean on a YORK YMC2?

It is a cycling shutdown message: the MBC has measured shaft displacement beyond the limit from center in the W axis at the opposite-impeller-end radial magnetic bearing during Levitation or Rotation mode, and the MBC fault contacts open.

What is the displacement limit for MBC - W24 POSITION?

The manuals print 75 µm, approximately half of the air gap space to the touchdown bearing, and 100 micron, approximately 2/3 of that air gap. The shutdown releases when displacement falls below the same value.

How do I clear MBC - W24 POSITION on a YMC2?

No manual reset is described. The message releases itself once displacement is below the threshold, and the MBC de-levitates when commanded over serial comms or when the VSD DC buss power depletes.

Why is the shaft still levitated after an MBC - W24 POSITION shutdown?

Because the MBC remains in Levitation mode with the motor shaft levitated until it is commanded to de-levitate over serial comms or the VSD DC buss power depletes, as the manual states.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: