On the display
The panel shows VSD - INVERTER PROGRAM FAULT in this exact wording; the manuals print no other variant of the message. It belongs to the YMC2's safety shutdown messages, so the unit trips when it becomes active.
What it means
The manuals give this shutdown two meanings. The first is an inverter internal code exception: when the inverter hits something like a divide-by-zero or an out-of-range parameter, the unit trips. The HYP logic board then indicates the inverter program fault and passes the error information — including the module number and the line number — over the communications link. The second meaning is a failed validation of the inverter software against the motor design: the VSD software contains a verification process that confirms the correct set of software is installed in the VSD logic board for the application, and the shutdown occurs when that verification does not pass. The drive is used on two different motor designs, which is why the software must be validated for the one actually fitted.
Why it appears
- An internal code exception inside the inverter, such as a divide-by-zero or an out-of-range parameter.
- The inverter software does not match the motor design of the application: the three pieces of data that must state that the correct inverter software is installed in the VSDF logic board do not agree.
What to check
- Take the error information the HYP logic board reports over the communications link; it includes the module number and the line number of the code exception.
- Confirm the three pieces of data that must state that the correct inverter software is installed in the VSDF logic board.
- Check that the software in the VSD logic board U38 matches the condition on J2 pin 14.
- Check that the software in the VSD logic board U38 also matches the programmed motor selection from the chiller control center; all three must agree for this shutdown not to occur.
Reset and restart
The chiller stays shut down until the condition clears. When it does, the chiller can be started after the CLEAR FAULTS button is pressed
. The manuals repeat this action for both meanings of the message, and it is the only reset step they describe.
Questions engineers ask
What does VSD - INVERTER PROGRAM FAULT mean on a YORK YMC2?
It is a safety shutdown: either the inverter hit an internal code exception such as a divide-by-zero or an out-of-range parameter, or the inverter software failed the verification that confirms the correct software for the motor design is installed. The unit trips when it occurs.
How is VSD - INVERTER PROGRAM FAULT reset on the YMC2?
Wait until the condition clears, then press the CLEAR FAULTS button; the chiller can then be started. That is the only reset step the manuals describe for this message.
What must match so the YMC2 does not trip on this fault?
Three pieces of data must state that the correct inverter software is installed: the software in the VSD logic board U38, the condition on J2 pin 14, and the programmed motor selection from the chiller control center.
What extra information comes with this fault?
The HYP logic board indicates the inverter program fault and the error information, including the module number and the line number, via the communications link.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: