On the display
The panel reads VSD - DC BUS PRE-REGULATION — the manual prints it only this way, with no spelling variants. It is one of the chiller's cycling shutdown messages, and it appears during the start sequence, in the phase the manual calls pre-regulation: after the boost rectifier's closed-loop control has been enabled and while the VSD is bringing the DC link voltage up to its setpoint.
What it means
The DC link voltage did not attain a value within ±50 V of the DC link voltage setpoint — 750 V for YMC2, a setpoint defined by the motor and line voltages — within 2 seconds after the boost rectifier's closed-loop control was enabled. Pre-regulation therefore did not complete inside the time the VSD logic board allows. While the fault is present, the VSD logic board disables the boost rectifier's IGBT gating signals.
Why it appears
- The DC link voltage failed to come within ±50 V of the DC link voltage setpoint (750 V for YMC2) within 2 seconds after the boost rectifier's closed-loop control was enabled — this is the only cause the manual gives for the message.
Setpoints and thresholds
- DC link voltage setpoint: 750 V for YMC2, defined by the motor and line voltages.
- Attainment window: within ±50 V of that setpoint.
- Time allowed: 2 seconds after the boost rectifier's closed-loop control is enabled.
- Retry wait: 10 seconds before the fault is cleared and another pre-charge may start.
- Attempt limit: up to three consecutive pre-charge-related or pre-regulation-related faults before the lockout safety shutdown.
Reset and restart
The manual describes no reset action at the panel — the fault clears on its own timer. The VSD logic board shall time 10 seconds before clearing the fault and allowing another pre-charge to start.
The VFD's fan(s) and water pump(s) remain energized during that wait. Because the unit failed to complete pre-regulation, it must repeat pre-charge in order to attempt another pre-regulation. Up to three consecutive pre-charge-related or pre-regulation-related faults are allowed; after the third, the safety shutdown message VSD - DC BUS PRE-REGULATION LOCKOUT is generated.
Questions engineers ask
What does VSD - DC BUS PRE-REGULATION mean on a YORK YMC2?
It is a cycling shutdown message: the DC link voltage did not attain a value within ±50 V of the DC link voltage setpoint (750 V for YMC2) within 2 seconds after the boost rectifier's closed-loop control was enabled.
How many times will the YMC2 retry after this fault?
Up to three consecutive pre-charge-related or pre-regulation-related faults are allowed. After the third, the safety shutdown message VSD - DC BUS PRE-REGULATION LOCKOUT is generated.
How long until the YMC2 retries after a VSD - DC BUS PRE-REGULATION fault?
The VSD logic board times 10 seconds before clearing the fault and allowing another pre-charge to start; the VFD's fan(s) and water pump(s) remain energized during the wait.
What is the DC link voltage setpoint on a YMC2?
750 V, defined by the motor and line voltages. The fault trips if the DC link does not get within ±50 V of that value within 2 seconds of boost control being enabled.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: