Fault · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2VSD - PRECHARGE - LOW DC BUS VOLTAGE 1

On the display

The display reads VSD - PRECHARGE - LOW DC BUS VOLTAGE 1, exactly as the manuals print it; no alternate variants are listed. The YMC2 manual places the message among the cycling shutdown messages, and it belongs to the pre-charge stage of the VSD.

What it means

This cycling shutdown is generated by the VSD when a pre-charge attempt does not bring the DC bus voltage up in time. During pre-charge, the DC bus voltage must reach the minimum threshold determined by the Line Voltage Setpoint within 4 seconds after the pre-charge signal has been commanded. If the voltage does not meet that condition within those 4 seconds, this shutdown is generated.

Why it appears

  • The DC bus voltage did not reach at least the low threshold, which is determined by the Line Voltage Setpoint, within 4 seconds after the pre-charge signal was commanded.

Setpoints and thresholds

  • Minimum DC bus voltage threshold during pre-charge, by Line Voltage Setpoint: 460 V — 50 V; 380/415 V — 41 V; 230 V — 25 V.
  • Time allowed to reach the threshold after the pre-charge signal is commanded: 4 seconds.
  • Wait before the fault is cleared and another pre-charge is allowed: 10 seconds.
  • Consecutive pre-charge-related faults allowed before the safety shutdown: three.

Reset and restart

Recovery from this shutdown is automatic and timed by the VSD logic board. The logic board waits 10 seconds before clearing the fault and allowing another pre-charge to start; during that time the VFD's fan(s) and water pump(s) remain energized. If pre-charge fails again, the cycle repeats — up to three consecutive pre-charge-related faults are allowed. After the third consecutive pre-charge-related fault, the Safety Shutdown message VSD - PRECHARGE LOCKOUT is generated.

Questions engineers ask

What does VSD - PRECHARGE - LOW DC BUS VOLTAGE 1 mean on a YORK YMC2?

It is a cycling shutdown: the DC bus voltage failed to reach the minimum pre-charge threshold, which is set by the Line Voltage Setpoint, within 4 seconds after the pre-charge signal was commanded.

What are the low DC bus voltage thresholds for pre-charge?

50 V with a 460 V Line Voltage Setpoint, 41 V with 380/415 V, and 25 V with 230 V, according to the manual's table.

Will the chiller try pre-charge again after this shutdown?

Yes. The VSD logic board waits 10 seconds before clearing the fault and allowing another pre-charge to start, and the VFD's fan(s) and water pump(s) remain energized during the wait.

How many pre-charge faults happen before lockout?

Up to three consecutive pre-charge-related faults are allowed. After the third consecutive pre-charge-related fault, the Safety Shutdown message VSD - PRECHARGE LOCKOUT is generated.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:

All YORK YMC2 messages: fault codes · YORK YMC2 documentation · YORK manuals