On the display
The panel shows VSD - HIGH PHASE A INPUT CURRENT. The manuals print the message in this single form, with no variants. It is listed among the cycling shutdown messages of the unit.
What it means
This is an instantaneous overcurrent message for Phase A of the drive input. The three input currents are monitored with Hall-effect current sensors, and their instantaneous values — the readings at that moment — are compared to the limit. When the Phase A input current exceeds the value that applies to the model of drive installed, the unit responds with a cycling shutdown. The trip point is not one fixed number: each drive model has its own input current fault value, listed in the settings section. The message concerns the input current of the drive; a separate message exists for high Phase A motor current.
Why it appears
- The instantaneous Phase A input current exceeded the input current fault value printed for the installed model of drive.
Setpoints and thresholds
- The limit is the input current fault value for the model of drive installed:
- 0490 — 886 Amps
- 0490A — 942 Amps
- 0612A — 1418 Amps
- 0730A — 1418 Amps
- 0774 — 1446 Amps
- 1278A (380-415 VAC) — 3304 Amps
- 1278A (460 VAC) — 2796 Amps
- A second manual for this model prints the same table as drive amp ratings with instantaneous current values, listing 490 at 886, 0490A at 942 and 744 at 1446.
Reset and restart
A single occurrence of this message is a cycling shutdown. It escalates when it repeats: if three high input current cycling shutdown faults occur on any phase within 90 minutes, the third fault in that 90 minute period causes a Safety Shutdown. Until that third fault occurs, the event remains a cycling shutdown rather than a Safety Shutdown. When a Safety Shutdown has occurred, the chiller can be restarted after the CLEAR FAULTS button is pressed
.
Questions engineers ask
What does VSD - HIGH PHASE A INPUT CURRENT mean on a YORK YMC2?
It is a cycling shutdown message: the instantaneous Phase A input current of the drive exceeded the input current fault value that applies to the installed model of drive.
At what current does VSD - HIGH PHASE A INPUT CURRENT trip?
The value depends on the drive model: 886 Amps on the 0490, 942 Amps on the 0490A, 1418 Amps on the 0612A and 0730A, 1446 Amps on the 0774, 3304 Amps on the 1278A (380-415 VAC) and 2796 Amps on the 1278A (460 VAC).
How is VSD - HIGH PHASE A INPUT CURRENT cleared?
One occurrence is a cycling shutdown. If three high input current cycling shutdown faults occur within 90 minutes on any phase, the third one causes a Safety Shutdown, and the restart path then is the CLEAR FAULTS button.
How does the drive detect high input current?
The three input currents are monitored with Hall-effect current sensors, and their instantaneous values are compared to the limit for the drive model.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YMC2 messages: fault codes · YORK YMC2 documentation · YORK manuals