On the display
The control center displays this message exactly as EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBE. Both manuals print this single wording, so there are no display variants. It is one of the safety shutdown messages: when it is triggered, the chiller is shut down. Note that it is a different message from EVAPORATOR - TRANSDUCER OR TEMPERATURE SENSOR, which the same manuals list separately for this model.
What it means
The message means the evaporator pressure reading and the Leaving Chilled Liquid temperature reading are no longer in the correct relationship to each other. The control center converts the evaporator pressure to a Saturated Temperature value and compares it with the Leaving Chilled Liquid temperature. When the two readings fall out of the relationship the control expects, it treats one of the measuring devices as probably defective and initiates this safety shutdown.
Why it appears
- The Evaporator pressure Transducer may be defective.
- The Leaving Chilled Liquid temperature Thermistor may be defective.
What to check
- Read the evaporator pressure and the Leaving Chilled Liquid temperature at the control center; the control converts the pressure into a Saturated Temperature value for the comparison.
- Apply the manual's accuracy statement: with accurate devices, the Evaporator Saturated temperature is no more than 2.5°F (1.4°C) warmer and no more than 25.0°F (13.89°C) colder than the leaving chilled liquid temperature.
- Check whether the difference is outside the acceptable range; the shutdown is initiated only after the difference has been outside the range continuously for 10 minutes.
- Treat the Evaporator pressure Transducer and the Leaving Chilled Liquid temperature Thermistor as the devices to suspect — the manual names these two devices and no others for this message.
Setpoints and thresholds
- Compared values: the Saturated Temperature converted from the evaporator pressure versus the Leaving Chilled Liquid temperature.
- Difference definition:
difference = chilled liquid temp - evaporator saturated temp
. - Acceptable range: the difference should not be outside -2.5°F (-1.4°C) to +25.0°F (+13.89°C).
- Accuracy statement: with accurate devices, the Evaporator Saturated temperature is no more than 2.5°F (1.4°C) warmer and no more than 25.0°F (13.89°C) colder than the leaving chilled liquid temperature.
- Shutdown timer: the difference must be outside the acceptable range continuously for 10 minutes before the shutdown is initiated.
Reset and restart
This is a safety shutdown, and the manual gives one recovery action: The chiller can be started after the CLEAR FAULT button is pressed.
No other reset procedure is described for this message.
Questions engineers ask
What does EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBE mean on a YORK YMC2?
The evaporator pressure and the Leaving Chilled Liquid temperature readings are no longer in the correct relationship to each other. The control center therefore treats the Evaporator pressure Transducer or the Leaving Chilled Liquid temperature Thermistor as possibly defective and initiates a safety shutdown.
How do I reset the EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBE fault on a YMC2?
Press the CLEAR FAULT button; the manual states that the chiller can be started after the CLEAR FAULT button is pressed. No other reset procedure is described for this message.
What difference between evaporator saturated temperature and leaving chilled liquid temperature is acceptable on the YMC2?
The control forms the difference as chilled liquid temp minus evaporator saturated temp, and it should stay between -2.5°F (-1.4°C) and +25.0°F (+13.89°C). If it is outside that range continuously for 10 minutes, the shutdown is initiated.
Which devices cause EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBE on a YMC2?
The manual names two possible defective devices: the Evaporator pressure Transducer and the Leaving Chilled Liquid temperature Thermistor. No other cause is given for this message.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: