On the display
The panel prints CONTROL PANEL - LOSS OF CONTROL VOLTAGE. The manuals give this single wording only — no other spelling or variant is listed — so this exact text is what appears on the display. The message is documented in the cycling shutdown messages and the safety shutdown messages groups of the manuals.
What it means
The message means that the control power input signal at I/O board TB3-81 was low for 1 second continuous. The operations manual for this model words the same monitored input as the line power input signal at TB3-81, so the two manuals name one signal at the same terminal differently. The panel watches this signal to determine when the digital inputs are affected by a panel or line power loss versus an actual condition for their devices — it is how the control center separates a power-loss situation from a genuine device event reported on a digital input.
One limitation printed with the fault matters when you read the display: This fault is not expected on an actual loss of microboard power from the critical load bus, because the processor will be off before the fault delay.
A true loss of microboard power takes the processor down before the 1-second detection time elapses, so this message is not the expected response to that event.
Why it appears
- The control power input signal at I/O board TB3-81 was low for 1 second continuous. (The operations manual prints the identical cause as a low line power input signal at the same terminal.)
- An actual loss of microboard power — including from the critical load bus — is not an expected trigger of this message, because the processor will be off before the fault delay.
Setpoints and thresholds
- Monitored input: control power (line power) input signal at I/O board TB3-81.
- Fault trigger: the signal low for 1 second continuous.
- Restart behaviour: cycling (auto-restart after power failure) or safety (manual restart after power failure) shutdown, per control center configuration.
Reset and restart
The restart path depends on the control center configuration. The operations manual states that this message can indicate a Cycling (auto-restart after power failure) or Safety (manual restart after power failure) shutdown, depending upon control center configuration.
For the cycling path, the other manual's fault table gives the automatic recovery: The chiller will automatically restart when the cycling condition clears.
The safety path is the manual-restart case after a power failure. No separate key-by-key reset procedure is described for this message.
Questions engineers ask
What does CONTROL PANEL - LOSS OF CONTROL VOLTAGE mean on a YORK YMC2?
It means the control power input signal at I/O board TB3-81 was low for 1 second continuous. The panel uses that signal to tell when the digital inputs are affected by a panel or line power loss rather than by an actual condition of their devices.
Will this fault appear when the panel power really fails?
The manuals state it is not expected on an actual loss of microboard power (from the critical load bus), because the processor will be off before the 1-second fault delay elapses.
How does the chiller come back after CONTROL PANEL - LOSS OF CONTROL VOLTAGE?
Depending on the control center configuration it stands for a Cycling shutdown, which auto-restarts after the power failure, or a Safety shutdown, which needs a manual restart after the power failure. In the automatic case the chiller restarts when the cycling condition clears.
Which input does this fault monitor?
The control power (line power) input signal, read at terminal TB3-81 of the I/O board.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YMC2 messages: fault codes · YORK YMC2 documentation · YORK manuals