Safety shutdown · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2VSD - PHASE A MOTOR DCCT

On the display

The panel shows VSD - PHASE A MOTOR DCCT. The manuals print the message in this exact wording and capitalisation, with no other variants, and it is one of the unit's safety shutdown messages.

What it means

This is the VSD's check that current is genuinely flowing to the motor once a start is commanded; the fault table sums it up as a failed check of the motor phase A DCCT cable and current. At the beginning of the run command the VSD measures the motor current in each phase. The reading at that instant should be very low, and it is kept as the zero current value for the rest of the run time. The VSD then monitors the current for the next 1.5 seconds to make sure a minimum amount of current is flowing to the motor. If a minimum of 25 amps peak is not detected by the end of that window, the shutdown is generated. Because the test waits for that first rise of current, it also tells the control whether the cable at the motor DCCT is connected.

Why it appears

  • The shutdown exists to determine if the cable at the motor DCCT is connected — a cable that is not connected is the condition it is designed to detect.
  • The shutdown is generated 1.5 seconds after the motor run command if the motor current does not exceed 25 A.

What to check

  1. Check that the cable at the motor DCCT is connected — this is the condition the shutdown is designed to determine.

Setpoints and thresholds

  • 25 amps peak — the minimum motor current that must be detected within the monitoring window; below it, the shutdown is generated.
  • 1.5 seconds — the monitoring window that follows the motor run command.

Reset and restart

The shutdown stands until the condition clears. When the condition clears, the chiller can be started after the clear faults button is pressed. That is the only recovery step the manuals give for this message.

Questions engineers ask

What does VSD - PHASE A MOTOR DCCT mean on a York YMC2?

It is a safety shutdown meaning the motor phase A DCCT cable/current check failed: within 1.5 seconds of the motor run command the VSD did not detect a minimum of 25 amps peak flowing to the motor.

Why does my YMC2 trip on VSD - PHASE A MOTOR DCCT?

The shutdown is there to determine whether the cable at the motor DCCT is connected. It is generated 1.5 seconds after the motor run command if the motor current does not exceed 25 A.

How much motor current avoids this trip?

A minimum of 25 amps peak must be detected during the 1.5 seconds after the motor run command; if that minimum is not reached, the shutdown is generated.

How do I clear VSD - PHASE A MOTOR DCCT?

Let the condition clear first, then press the clear faults button; after that the chiller can be started again.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: