On the display
The control center shows the message exactly as MBC SHUTDOWN - REQUESTING FAULT DATA. It is a short-lived message: serial communications with the MBC start up every 2 seconds, so it normally stays on the display for only a few seconds. The panel then switches to the particular MBC fault message that applies.
What it means
The MBC has shut the chiller down, but at the moment this message appears the control center does not yet know why: the fault cause has not yet come over the serial communications link from the MBC. The control center's microboard therefore asks the MBC control board, over that link, to send the cause. This message covers that short wait, and once the answer arrives the display moves on to the specific MBC fault message.
Why it appears
- The MBC shutdown itself is the trigger: the message appears because the cause of that shutdown has not yet reached the control center over the serial link.
- One manual describes the path the shutdown takes:
The MBC shuts down the chiller by opening the MBC Emergency Shutdown (ESD) contacts (located on the MBC control board and connected between TB6-15 and TB6-53 in the control center).
- The other manual gives the same event through different contacts:
The MBC shuts down the chiller by opening the MBC Fault contacts (located on the MBC control board and connected to TB3-70 in the control center).
What to check
- Let the exchange run: the control center and the MBC start their serial exchange every 2 seconds, so the request for the fault cause goes out while this message is on the display.
- Read the MBC fault message that replaces this one — it carries the fault cause the control center was waiting for.
Reset and restart
Both manuals place this message in the cycling shutdown messages group. The action given for it reads: Cycling shutdown: the chiller will automatically restart when the cycling condition clears.
On the display the message clears by itself: after a few seconds the panel shows the specific MBC fault message instead.
Questions engineers ask
What does MBC SHUTDOWN - REQUESTING FAULT DATA mean on a YORK YMC2?
The MBC has shut the chiller down, and the control center is still waiting for the MBC to send the fault cause over the serial link. The control center's microboard asks the MBC control board for that cause.
Why does the message only show for a few seconds?
The control center and the MBC begin their serial exchange every 2 seconds, so the fault cause normally arrives within seconds and the display switches to the specific MBC fault message.
Will the chiller restart by itself after this message?
Yes. The manual lists this message as a cycling shutdown, and the chiller restarts automatically once the cycling condition clears.
Which contacts does the MBC open when it shuts the chiller down?
One manual describes the MBC Emergency Shutdown (ESD) contacts, connected in the control center between TB6-15 and TB6-53; the other describes MBC Fault contacts connected in the control center to TB3-70. Both contact sets sit on the MBC control board.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: