YMC2 Mod A Centrifugal Chiller with OptiView Control Center, Unit Operation Guide

Document typeOperation Guide
Document number160.78-O1
EquipmentYMC2 Magnetic Bearing Centrifugal Chiller
BrandYORK
Revised2025-04-25
File size1.5 MB

Fault codes in this document

Compressor

Code / displayMeaningCauseActionPage
Control panel warns of excessive landings of the magnetic bearing motorNotify the nearest Johnson Controls office to request the presence of a Johnson Controls Service Technician. The technician can assess the condition of the touchdown bearings using electronic tools.22

Symptom: abnormally high discharge pressure

Code / displayMeaningCauseActionPage
Temperature difference between condensing temperature and water off condenser higher then normalCondenser tubes dirty or scaled• Clean condenser tubes
• Check water conditioning
24
Temperature difference between condensing temperature and water off condenser higher then normalCondenser tubes dirty or scaled• Clean condenser tubes
• Check water conditioning
24
High discharge pressureHigh condenser water temperature• Reduce condenser water inlet temperature
• Check cooling tower and water circulation
24
Temperature diffrence between condenser water on and water off higher than normal, with normal discharge temperatureInsufficient condensing water flowIncrease the quantity of water through the condenser to the correct value24

Symptom: abnormally low suction pressure

Code / displayMeaningCauseActionPage
Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature.Variable orifice problemRemove obstruction24
Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperatureEvaporator tubes dirty or restrictedClean evaporator tubes24
Temperature of chilled water too low with low motor amperesInsufficient load for system capacityCheck capacity control operation and setting of low water temperature shutdown setpoint24

Symptom: high evaporator pressure

Code / displayMeaningCauseActionPage
High chilled water temperatureSystem overloadEnsure that the capacity control devices and speed increased (without overloading the motor) until the load decreases24