| Document type | Operation Guide |
|---|---|
| Document number | 160.78-O1 |
| Equipment | YMC2 Magnetic Bearing Centrifugal Chiller |
| Brand | YORK |
| Revised | 2025-04-25 |
| File size | 1.5 MB |
Fault codes in this document
Compressor
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Control panel warns of excessive landings of the magnetic bearing motor | Notify the nearest Johnson Controls office to request the presence of a Johnson Controls Service Technician. The technician can assess the condition of the touchdown bearings using electronic tools. | 22 |
Symptom: abnormally high discharge pressure
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Temperature difference between condensing temperature and water off condenser higher then normal | Condenser tubes dirty or scaled | • Clean condenser tubes • Check water conditioning | 24 | |
| Temperature difference between condensing temperature and water off condenser higher then normal | Condenser tubes dirty or scaled | • Clean condenser tubes • Check water conditioning | 24 | |
| High discharge pressure | High condenser water temperature | • Reduce condenser water inlet temperature • Check cooling tower and water circulation | 24 | |
| Temperature diffrence between condenser water on and water off higher than normal, with normal discharge temperature | Insufficient condensing water flow | Increase the quantity of water through the condenser to the correct value | 24 |
Symptom: abnormally low suction pressure
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature. | Variable orifice problem | Remove obstruction | 24 | |
| Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature | Evaporator tubes dirty or restricted | Clean evaporator tubes | 24 | |
| Temperature of chilled water too low with low motor amperes | Insufficient load for system capacity | Check capacity control operation and setting of low water temperature shutdown setpoint | 24 |
Symptom: high evaporator pressure
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| High chilled water temperature | System overload | Ensure that the capacity control devices and speed increased (without overloading the motor) until the load decreases | 24 |
Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication. The short table of all YORK YMC2 messages: fault codes.
Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.