Safety shutdown · YORK YMC2 · Magnetic bearing centrifugal chiller

YORK YMC2VSD - PRECHARGE LOCKOUT

On the display

The control center shows VSD - PRECHARGE LOCKOUT. The manual lists it among the safety shutdown messages for this model and prints it in one form only, so there are no display variants to look for.

What it means

This shutdown is generated after the third consecutive pre-charge fault. The fault table gives the meaning as: third consecutive pre-charge fault. The VSD logic board allows up to three consecutive pre-charge-related faults; the first two faults are each cleared after a delay and a new pre-charge attempt, and only the third consecutive fault produces this lockout.

Why it appears

  • The unit fails to complete pre-charge. The manual names two messages as the reasons a pre-charge attempt fails: VSD - PRECHARGE - LOW DC BUS VOLTAGE or VSD - PRECHARGE - HIGH DC BUS VOLTAGE.
  • After each such fault, the VSD logic board times 10 seconds before clearing the fault and allowing another pre-charge to start; the unit's fan(s) and water pump(s) remain energized during this time.
  • The VSD allows up to three consecutive pre-charge-related faults; after the third consecutive pre-charge-related fault, this shutdown is generated.

What to check

  1. Identify which pre-charge-related message preceded the lockout — VSD - PRECHARGE - LOW DC BUS VOLTAGE or VSD - PRECHARGE - HIGH DC BUS VOLTAGE. One of these is the reason each pre-charge attempt failed.
  2. Confirm the condition that produced the pre-charge faults has cleared; the manual permits a start only when the condition clears, so the lockout remains in place until then.

Reset and restart

The manual's action for this safety shutdown is: When the condition clears, the chiller can be started after the CLEAR FAULTS button is pressed. The unit therefore does not come back on its own: once the underlying pre-charge condition has cleared, press the CLEAR FAULTS button and start the chiller.

Questions engineers ask

What does VSD - PRECHARGE LOCKOUT mean on a YORK YMC2?

It is a safety shutdown generated after the third consecutive pre-charge fault. The VSD logic board allows up to three consecutive pre-charge-related faults, and the third one produces this lockout.

Why does pre-charge fail on the YMC2?

The manual names two messages behind failed pre-charge attempts: VSD - PRECHARGE - LOW DC BUS VOLTAGE and VSD - PRECHARGE - HIGH DC BUS VOLTAGE. Each failure is followed by a 10-second wait before the VSD clears the fault and allows another pre-charge to start.

How do I reset VSD - PRECHARGE LOCKOUT on a YMC2?

When the condition that caused the pre-charge faults has cleared, press the CLEAR FAULTS button and start the chiller. Until the condition clears, the unit cannot be started.

What happens to the fans and pumps during the pre-charge faults?

They stay energized. The unit's fan(s) and water pump(s) remain energized during the 10 seconds the VSD times before clearing each fault and allowing another pre-charge to start.

Messages next to this one

The same message on other models

Source

Written from the manufacturer's manuals for the YORK YMC2; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: