What it means
F30011 is raised when, at the power unit, the DC link voltage ripple has exceeded the permissible limit value. The drive reports this condition under the title “Power unit: Line phase failure in main circuit”, but the ripple can have several root causes besides a genuinely failed line phase — the list below follows the manual.
Why it appears
- A line phase has failed.
- The 3 line phases are inadmissibly asymmetrical.
- The capacitance of the DC link capacitor forms a resonance frequency with the line inductance and the reactor integrated in the power unit.
- The fuse of a phase of the main circuit has ruptured.
- A motor phase has failed.
- Where the manual describes the S120/S150 power units there is one further possible cause: for power units operated on a single phase, the permissible active power was exceeded.
What to check
- Check the main circuit fuses.
- Check whether a single-phase load is distorting the line voltages.
- If the cause is the resonance between the DC link capacitance and the line inductance, detune the resonant frequency by using an upstream line reactor.
- Alternatively, dampen the resonant frequency by switching over the DC link voltage compensation in the software (p1810) or by increasing the smoothing (p1806). The manual warns that this can have a negative impact on the torque ripple at the motor output.
- Check the motor feeder cables.
- For the G115D the short fault table condenses the remedy to: check the line cables. For the G120C it says: check the motor cables.
Reading the message value
- The drive stores the fault value in r0949, to be interpreted as a decimal number.
- The manual gives no decoding for on-site use; it states:
Only for internal Siemens troubleshooting.
Parameters the manual names
- r0949 — holds the fault value of this message (read as decimal); the manual reserves it for internal Siemens troubleshooting, so it does not help with on-site diagnosis.
- p1810 — used to switch over the DC link voltage compensation in order to dampen the resonant frequency with the line inductance.
- p1806 — increasing this raises the smoothing; the manual notes the possible negative impact on the torque ripple at the motor output.
Acknowledging and restarting
The drive reacts with OFF2 (OFF1), so the drive coasts down and stays off until the fault has been cleared; the message is acknowledged IMMEDIATELY. Eliminate the cause first, then acknowledge the fault and restart the drive.
What differs between the drive families
Straight from the manuals' own fields — F30011 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 (OFF1) | IMMEDIATELY | Network fault (2) | Power Module | SINAMICS S120, S150 List Manual · p. 2940 |
| G130, G150 | OFF2 (OFF1) | IMMEDIATELY | Network fault (2) | Power Module | SINAMICS G130, G150 List Manual · p. 1652 |
| G120 | OFF2 (OFF1) | IMMEDIATELY | Network fault (2) | — | SINAMICS G120 · p. 906 |
| G120XA | OFF2 (OFF1) | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1153 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 396 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 387 |
The drives this code lives on
F30011 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30011 mean on a SINAMICS drive?
It means that at the power unit the DC link voltage ripple has exceeded the permissible limit value, which the drive reports as a line phase failure in the main circuit.
What causes F30011?
The manual lists a failed line phase, an inadmissibly asymmetrical 3-phase supply, a resonance between the DC link capacitance and the line inductance, a ruptured main circuit fuse, or a failed motor phase. For S120/S150 power units operated on a single phase, exceeding the permissible active power is also listed.
How do I clear and restart after F30011?
Fix the cause first — fuses, supply distortion, resonance or cables — then acknowledge IMMEDIATELY and restart. Because the drive reacts with OFF2 (OFF1), it stays off until the fault is acknowledged.
What does the fault value in r0949 show for F30011?
The value is interpreted as a decimal number, but the manual states it is only for internal Siemens troubleshooting, so no on-site decoding is given.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F30xxx group · SINAMICS manuals · Siemens manuals