What it means
F30004 is raised when the temperature of the power unit heat sink exceeds the permissible limit value. The manuals describe the fault identically across the G115D, G120, G120C, G120XA, G130, G150, S120 and S150 under the title "Power unit: Overtemperature heat sink AC inverter"; in the short fault tables of the G115D and G120C instruction manuals it appears simply as "Converter overtemperature". The condition is detected in the Power Module of the affected inverter, and the drive stores the measured heat sink temperature as the fault value in r0949, so the number you read there tells you how hot the heat sink actually was.
Why it appears
- Cooling is insufficient or a fan has failed.
- The power unit is overloaded.
- The ambient temperature is too high.
- The pulse frequency is set too high.
What to check
- Check whether the fan is running.
- Check the fan elements.
- Check that the ambient temperature is within the permissible range.
- Check the motor load.
- If the set pulse frequency is above the rated pulse frequency, reduce it — the entry for this fault points to p1800 for this.
Reading the message value
- The drive writes the heat sink temperature into r0949 as the fault value.
- Read the value as a decimal number; its resolution is 0.01 °C (the manuals print the resolution as "1 bit = 0.01 °C").
Parameters the manual names
- r0949 — read the fault value here: for F30004 it contains the heat sink temperature, interpreted as a decimal number in steps of 0.01 °C.
- p1800 (pulse frequency setpoint) — use it to lower the pulse frequency if the check shows it is set above the rated pulse frequency.
Acknowledging and restarting
The drive trips with OFF2: pulses are suppressed, the motor coasts to a standstill, and the fault must be acknowledged before the drive will start again. The heat sink must first have cooled down, because This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Once the temperature is back below that threshold, acknowledge the fault and restart the drive.
What differs between the drive families
Straight from the manuals' own fields — F30004 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY | Power electronics faulted (5) | Power Module | SINAMICS S120, S150 List Manual · p. 2938 |
| G130, G150 | OFF2 | IMMEDIATELY | Power electronics faulted (5) | Power Module | SINAMICS G130, G150 List Manual · p. 1650 |
| G120 | OFF2 | IMMEDIATELY | Power electronics faulted (5) | — | SINAMICS G120 · p. 905 |
| G120XA | OFF2 | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1152 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 396 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 387 |
The drives this code lives on
F30004 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30004 mean on a SINAMICS drive?
The temperature of the power unit heat sink has exceeded the permissible limit value. The drive trips with OFF2 and stores the measured temperature as the fault value in r0949.
Why can I not acknowledge F30004?
The fault can only be acknowledged once the heat sink has cooled below the alarm threshold of alarm A05000. Remove the cause, let the drive cool down, then acknowledge.
How do I fix fault F30004?
Check that the fan is running, check the fan elements, make sure the ambient temperature is in the permissible range and check the motor load. If the pulse frequency is set above the rated value, reduce it via p1800, then acknowledge the fault.
What is stored in r0949 after F30004?
The heat sink temperature. Read the value as a decimal number; each step is 0.01 °C.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.