List Manual
SINAMICS
SINAMICS G120
Control Units CU240B-2/CU240E-2
Edition 09/2020 www.siemens.com/drives
s Fundamental safety
instructions 1
Parameters 2
SINAMICS Function diagrams 3
SINAMICS G120 Faults and alarms 4
Control Units
CU240B-2/CU240E-2 Appendix A
List Manual
Index
Valid for
Control Units Firmware version
CU240B-2 4.7 SP13
CU240B-2_DP 4.7 SP13
CU240E-2 4.7 SP13
CU240E-2_DP 4.7 SP13
CU240E-2_DP_F 4.7 SP13
CU240E-2_F 4.7 SP13
CU240E-2_PN 4.7 SP13
CU240E-2_PN_F 4.7 SP13
09/2020
A5E33839529
Legal information
Warning concept
This Manual contains information which you must observe to ensure your own personal safety as well as to avoid
material damage. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to equipment damage have no safety alert symbol. Depending on the hazard level,
warnings are indicated in a descending order as follows:
DANGER
indicates that death or serious injury will result if proper precautions are not taken.
WARNING
indicates that death or serious injury could result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one level of danger is simultaneously applicable, the warning notice for the highest level is used. A
notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified personnel
The product/system described in this documentation may only be operated by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety
instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying
risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products are only permitted to be used for the applications envisaged in the catalog and in the associated
technical documentation. If third-party products and components are to be used, they must be recommended or
approved by Siemens. These products can only function correctly and safely if they are transported, stored, set up,
mounted, installed, commissioned, operated and maintained correctly. The permissible ambient conditions must be
adhered to. Information in the associated documentation must be observed.
Trademarks
All names identified with ® are registered trademarks of Siemens AG. Any other names used in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of liability
We have verified that the contents of this document correspond to the hardware and software described. Since
variance cannot be precluded entirely, we cannot guarantee full consistency. The information given in this document
is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent editions.
Siemens AG Article number: A5E33839529 Copyright © Siemens AG 2009 - 2020.
Division Digital Industries 09/2020 Subject to change without prior notice All rights reserved
P.O. Box 48 48
90026 NUREMBERG
GERMANY
Preface
SINAMICS documentation
The SINAMICS documentation is organized in the following categories:
• General documentation/catalogs
• Manufacturer/service documentation
Additional information
Information on the following topics is available under the link:
• Ordering documentation / overview of documentation
• Additional links to download documents
• Using documentation online (browse and search in manuals/information).
http://www.siemens.com/motioncontrol/docu
Please send any questions about the technical documentation (e. g. suggestions for
improvement, corrections) to the following e-mail address:
docu.motioncontrol@siemens.com
My Documentation Manager
Information on how to produce individual contents for your own machine documentation based
on Siemens contents is available under the link:
http://www.siemens.com/mdm
Training
Information about SITRAIN (Siemens Training on products, systems and solutions for
automation) is available under the following link:
http://www.siemens.com/sitrain
FAQs
You can find Frequently Asked Questions in the Service&Support pages under Product
Support:
http://support.automation.siemens.com
SINAMICS
You can find information on SINAMICS at:
http://www.siemens.com/sinamics
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 5
Preface
Target group
This documentation is intended for machine manufacturers, commissioning engineers, and
service personnel who use the SINAMICS drive system.
Benefits
This documentation contains comprehensive information about parameters, function diagrams
and faults and alarms required to commission and service the system.
This manual should be used in addition to the other manuals and tools provided for the product.
Standard scope
The scope of the functionality described in this document can differ from the scope of the
functionality of the drive system that is actually supplied.
• Other functions not described in this documentation might be able to be executed in the
drive system. This does not, however, represent an obligation to supply such functions with
a new controller or when servicing.
• The documentation can also contain descriptions of functions that are not available in a
particular product version of the drive system. The functionalities of the supplied drive
system should only be taken from the ordering documentation.
• Extensions or changes made by the machine manufacturer must be documented by the
machine manufacturer.
For reasons of clarity, this documentation does not contain all of the detailed information about
all of the product types, This documentation cannot take into consideration every conceivable
type of installation, operation and service/maintenance.
Search guides
The following tools are provided to help you locate information in this manual:
1. Table of contents
– Table of contents for the complete manual (Page 9)
– Table of contents for function diagrams (Page 590)
2. List of abbreviations (Page 941)
3. Index (Page 951)
Technical Support
Country-specific telephone numbers for technical support are provided at the following Internet
address:
http://www.siemens.com/automation/service&support
SINAMICS G120 Control Units CU240B-2/CU240E-2
6 List Manual, 09/2020, A5E33839529
Preface
EC Declaration of Conformity
The EC Declaration of Conformity for the EMC Directive can be found on the Internet at:
https://support.industry.siemens.com/cs/products?dtp=Certificate&mfn=ps&pnid=13223&lc=d
e-WW
Alternatively, you can contact the Siemens office in your region in order to obtain the EC
Declaration of Conformity.
Compliance with the General Data Protection Regulation
Siemens respects the principles of data protection, in particular the data minimization rules
(privacy by design).
For this product, this means:
The product does not process neither store any person-related data, only technical function
data (e.g. time stamps). If the user links these data with other data (e.g. shift plans) or if he
stores person-related data on the same data medium (e.g. hard disk), thus personalizing these
data, he has to ensure compliance with the applicable data protection stipulations.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 7
Preface
SINAMICS G120 Control Units CU240B-2/CU240E-2
8 List Manual, 09/2020, A5E33839529
Table of contents
1 Fundamental safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 General safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2 Warranty and liability for application examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.3 Security information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Overview of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.1.1 Explanation of the parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.1.2 Number ranges of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.2 List of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.3 Parameters for data sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563
2.3.1 Command Data Sets (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563
2.3.2 Drive Data Sets (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
2.4 BICO parameters (connectors/binectors). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 574
2.4.1 Binector inputs (BI). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 574
2.4.2 Connector inputs (CI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576
2.4.3 Binector outputs (BO). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 578
2.4.4 Connector outputs (CO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 580
2.4.5 Connector/binector outputs (CO/BO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 583
2.5 Parameters for write protection and know-how protection . . . . . . . . . . . . . . . . . . . . . . . . . . 585
2.5.1 Parameters with "WRITE_NO_LOCK". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 585
2.5.2 Parameters with "KHP_WRITE_NO_LOCK" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 585
2.5.3 Parameters with "KHP_ACTIVE_READ" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 586
2.6 Quick commissioning (p0010 = 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 587
3 Function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589
3.1 Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590
3.2 Explanations of the function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 597
3.3 Input/output terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602
3.4 PROFIenergy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 617
3.5 Communication PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP. . . . . . . . . . . . . . . . . . 620
3.6 Communication fieldbus interface (USS, Modbus) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 636
3.7 Internal control/status words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 643
3.8 Brake control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 662
3.9 Safety Integrated Basic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 664
3.10 Safety Integrated Extended Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 671
3.11 Safety Integrated PROFIsafe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 681
3.12 Setpoint channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 9
Table of contents
3.13 Vector control / U/f control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 695
3.14 U/f control, Standard Drive Control (p0096 = 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 727
3.15 Vector control, Dynamic Drive Control (p0096 = 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 733
3.16 Technology functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 753
3.17 Free function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 756
3.18 Technology controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 777
3.19 Signals and monitoring functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 783
3.20 Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 797
3.21 Data sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 803
4 Faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 807
4.1 Overview of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 808
4.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 808
4.1.2 Explanation of the list of faults and alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 812
4.1.3 Number ranges of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 817
4.2 List of faults and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 819
A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 937
A.1 ASCII table (characters that can be displayed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 938
A.2 List of abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 941
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 951
SINAMICS G120 Control Units CU240B-2/CU240E-2
10 List Manual, 09/2020, A5E33839529
Fundamental safety instructions 1
Content
1.1 General safety instructions 12
1.2 Warranty and liability for application examples 12
1.3 Security information 13
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 11
1 Fundamental safety instructions
1.1 General safety instructions
1.1 General safety instructions
WARNING
Danger to life if the safety instructions and residual risks are not observed
If the safety instructions and residual risks in the associated hardware documentation are not
observed, accidents involving severe injuries or death can occur.
• Observe the safety instructions given in the hardware documentation.
• Consider the residual risks for the risk evaluation.
WARNING
Malfunctions of the machine as a result of incorrect or changed parameter settings
As a result of incorrect or changed parameterization, machines can malfunction, which in turn
can lead to injuries or death.
• Protect the parameterization against unauthorized access.
• Handle possible malfunctions by taking suitable measures, e.g. emergency stop or
emergency off.
1.2 Warranty and liability for application examples
Application examples are not binding and do not claim to be complete regarding configuration,
equipment or any eventuality which may arise. Application examples do not represent specific
customer solutions, but are only intended to provide support for typical tasks.
As the user you yourself are responsible for ensuring that the products described are operated
correctly. Application examples do not relieve you of your responsibility for safe handling when
using, installing, operating and maintaining the equipment.
SINAMICS G120 Control Units CU240B-2/CU240E-2
12 List Manual, 09/2020, A5E33839529
1 Fundamental safety instructions
1.3 Security information
1.3 Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is necessary and
only when appropriate security measures (e.g. firewalls and/or network segmentation) are in
place.
For additional information on industrial security measures that can be implemented, please
visit:
Industrial security (https://www.siemens.com/industrialsecurity)
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customer’s exposure to
cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed at:
Industrial security
(https://new.siemens.com/global/en/products/services/cert.html#Subscriptions).
Further information is provided on the Internet:
Industrial Security Configuration Manual
(https://support.industry.siemens.com/cs/ww/en/view/108862708)
WARNING
Unsafe operating states resulting from software manipulation
Software manipulations (e.g. viruses, trojans, malware or worms) can cause unsafe operating
states in your system that may lead to death, serious injury, and property damage.
• Keep the software up to date.
• Incorporate the automation and drive components into a holistic, state-of-the-art industrial
security concept for the installation or machine.
• Make sure that you include all installed products into the holistic industrial security
concept.
• Protect files stored on exchangeable storage media from malicious software by with
suitable protection measures, e.g. virus scanners.
• On completion of commissioning, check all security-related settings.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 13
1 Fundamental safety instructions
1.3 Security information
SINAMICS G120 Control Units CU240B-2/CU240E-2
14 List Manual, 09/2020, A5E33839529
Parameters 2
Content
2.1 Overview of parameters 16
2.2 List of parameters 30
2.3 Parameters for data sets 563
2.4 BICO parameters (connectors/binectors) 574
2.5 Parameters for write protection and know-how protection 585
2.6 Quick commissioning (p0010 = 1) 587
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 15
2 Parameters
2.1 Overview of parameters
2.1 Overview of parameters
2.1.1 Explanation of the parameter list
Basic structure of the parameter descriptions
The data in the following example have been chosen at random. The table below contains all
the information that can be included in a parameter description. Some of the information is
optional.
The "List of parameters (Page 30)" has the following layout:
- - - - - - - - - - - - Start of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
pxxxx[0...n] BICO: Full parameter name / abbreviated name
CU/PM variants Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(x), U, T Scaling: p2002 Dyn. index: CDS, p0170
Unit group: 6_2 Unit selection: p0505 Function diagram: 8070
Min Max Factory setting
0.00 [Nm] 10.00 [Nm] 0.00 [Nm]
Description: Text
Values: 0: Name and meaning of value 0
1: Name and meaning of value 1
2: Name and meaning of value 2
etc.
Recommendation: Text
Index: [0] = Name and meaning of index 0
[1] = Name and meaning of index 1
[2] = Name and meaning of index 2
etc.
Bit array: Bit Signal name 1 signal 0 signal FP
00 Name and meaning of bit 0 Yes No 8060
01 Name and meaning of bit 1 Yes No -
02 Name and meaning of bit 2 Yes No 8052
etc.
Dependency: Text
See also: pxxxx, rxxxx
See also: Fxxxxx, Axxxxx
Danger: Warning: Caution: Safety notices with a warning triangle
Notice: Safety notice without a warning triangle
Note: Information that might be useful.
- - - - - - - - - - - - End of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
The individual pieces of information are described in detail below.
SINAMICS G120 Control Units CU240B-2/CU240E-2
16 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
pxxxx[0...n] Parameter number
The parameter number is made up of a "p" or "r", followed by the parameter number and the
index or bit field (optional).
Examples of the representation in the parameter list:
• p... Adjustable parameters (read and write)
• r... Display parameters (read only)
• p0918 Adjustable parameter 918
• p2051[0...13] Adjustable parameter 2051, indices 0 to 13
• p1001[0...n] Adjustable parameter 1001, indices 0 to n (n = configurable)
• r0944 Display parameter 944
• r2129.0...15 Display parameter 2129 with bit field from bit 0 (smallest bit) to bit 15
(largest bit)
Other examples of notation in the documentation:
• p1070[1] Adjustable parameter 1070, index 1
• p2098[1].3 Adjustable parameter 2098, index 1 bit 3
• p0795.4 Adjustable parameter 795, bit 4
The following applies to adjustable parameters:
The parameter value as delivered is specified under "Factory setting" with the relevant unit in
square brackets. The value can be adjusted within the range defined by "Min" and "Max".
The term "linked parameterization" is used in cases where changes to adjustable parameters
affect the settings of other parameters.
Linked parameterization can occur, for example, as a result of the following actions and
parameters:
• Setting the PROFIBUS telegram (BICO interconnection)
p0922
• Setting component lists
p0230, p0300, p0301, p0400
• Automatically calculating and pre-assigning
p0340, p3900
• Restoring the factory settings
p0970
The following applies to display parameters:
The fields "Min", "Max" and "Factory setting" are specified with a dash "-" and the relevant unit
in square parentheses.
Note
The parameter list can contain parameters that are not visible in the expert lists of the particular
commissioning software (e.g. parameters for trace functions).
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 17
2 Parameters
2.1 Overview of parameters
BICO: Full parameter name/Abbreviated name
The following abbreviations can appear in front of the BICO parameter name:
• BI: Binector Input
This parameter is used for selecting the source of a digital signal.
• BO: Binector Output
This parameter is available as a digital signal for interconnection with other
parameters.
• CI: Connector Input
This parameter is used for selecting the source of an "analog" signal.
• CO: Connector Output
This parameter is available as an "analog" signal for interconnection with other
parameters.
• CO/BO: Connector/Binector Output
This parameter is available as an "analog" and digital signal for interconnection
with other parameters.
Note
A BICO input (BI/CI) cannot be interconnected with just any BICO output (BO/CO, signal
source).
When interconnecting a BICO input using the commissioning software, only the corresponding
possible signal sources are listed.
Function diagrams 1020 ... 1030 explain the symbols for BICO parameters and how to deal
with BICO technology.
CU/PM variants
Indicates for which Control Units (CU) and/or Power Modules (PM) the parameter is valid. If no
CU or PM is listed, then the parameter is valid for all variants.
The following information relating to "CU" and "PM" can be displayed under the parameter
number:
Table 2-1 Information in the "CU/PM variants" field
CU/PM variants Meaning
All Control Units have this parameter.
CU240B-2 CU240B-2
CU240B-2_DP CU240B-2 with PROFIBUS interface
CU240E-2 CU240E-2
CU240E-2_DP CU240E-2 with PROFIBUS interface
CU240E-2_DP_F CU240E-2 with PROFIBUS interface and extended integrated safety
functions
CU240E-2_F CU240E-2 with extended integrated safety functions
CU240E-2_PN CU240E-2 with PROFINET interface
CU240E-2_PN_F CU240E-2 with PROFINET interface and extended integrated safety
functions
SINAMICS G120 Control Units CU240B-2/CU240E-2
18 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
Table 2-1 Information in the "CU/PM variants" field, continued
CU/PM variants Meaning
PM230 Power Module for pumps and fans (3 AC 400 V)
PM240 Power Module for standard applications with dynamic braking
PM240
3 AC 400 V
PM240-2
1 AC / 3 AC 230 V; 3 AC 400 V; 3 AC 690 V
PM240P-2
3 AC 400 V; 3 AC 690 V
PM250 Power Module (3 AC 400 V with energy recovery)
PM260 Power Module (3 AC 690 V with energy recovery)
PM340 Power Module for standard applications with dynamic braking
(1 AC 230 V)
Access level
Specifies the minimum access level required to be able to display and change the relevant
parameter. The required access level can be set using p0003.
The system uses the following access levels:
• 1: Standard (not adjustable, included in p0003 = 3)
• 2: Extended (not adjustable, included in p0003 = 3)
• 3: Expert
• 4: Service
Parameters with this access level are password protected.
Note
Parameter p0003 is CU-specific (belongs to the Control Unit).
A higher access level will also include the functions of the lower levels.
Calculated
Specifies whether the parameter is influenced by automatic calculations.
p0340 determines which calculations are to be performed:
• p0340 = 1 includes the calculations from p0340 = 2, 3, 4, 5.
• p0340 = 2 calculates the motor parameters (p0350 ... p0360, p0625).
• p0340 = 3 includes the calculations from p0340 = 4, 5.
• p0340 = 4 only calculates the controller parameters.
• p0340 = 5 only calculates the controller limits.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 19
2 Parameters
2.1 Overview of parameters
Note
For p3900 > 0, p0340 = 1 is also called automatically.
After p1900 = 1, 2, p0340 = 3 is also called automatically.
Parameters with a reference to p0340 after "Calculated" depend on the Power Module being
used and the motor. In this case, the values at "Factory setting" do not correspond to the actual
values because these values are calculated during the commissioning. This also applies to the
motor parameters.
Data type
The information on the data type can consist of the following two items (separated by a slash):
• First item
Data type of the parameter
• Second item (for binector or connector input only)
Data type of the signal source to be interconnected (binector-/connector output).
Parameters can have the following data types:
• Integer8 I8 8-bit integer number
• Integer16 I16 16-bit integer number
• Integer32 I32 32-bit integer number
• Unsigned8 U8 8 bits without sign
• Unsigned16 U16 16 bits without sign
• Unsigned32 U32 32 bits without sign
• FloatingPoint32 Float 32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO-output
parameter (signal source), the following combinations are possible when creating
BICO-interconnections:
SINAMICS G120 Control Units CU240B-2/CU240E-2
20 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
Table 2-2 Possible combinations of BICO interconnections
BICO input parameter
CI parameter BI parameter
BICO output parameter Unsigned32 / Unsigned32 / Unsigned32 / Unsigned32 /
Integer16 Integer32 FloatingPoint32 Binary
CO: Unsigned8 x x – –
CO: Unsigned16 x x – –
CO: Unsigned32 x x – –
CO: Integer16 x x r2050 –
CO: Integer32 x x r2060 –
CO: FloatingPoint32 x x x –
BO: Unsigned8 – – – x
BO: Unsigned16 – – – x
BO: Unsigned32 – – – x
BO: Integer16 – – – x
BO: Integer32 – – – x
BO: FloatingPoint32 – – – –
Legend: x: x: BICO interconnection permitted
–: –: BICO interconnection not permitted
rxxxx: BICO interconnection is only permitted for the specified CO parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 21
2 Parameters
2.1 Overview of parameters
Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be changed only in
the specified drive unit state and that the change will not take effect until the unit switches to
another state. One or more states are possible.
The following states are available:
• C(x) Commissioning C: Commissioning
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C: Can be changed for all settings p0010 > 0.
• C(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
• U Operation U: Run
Pulses are enabled.
• T Ready T: Ready to run
The pulses are not enabled and the status "C(x)" is not active.
Normalization
Specification of the reference variable with which a signal value is automatically converted for
a BICO interconnection.
The following reference variables are available:
• p2000 … p2007: Reference speed, reference voltage, etc.
• PERCENT: 1.0 = 100 %
• 4000H: 4000 hex = 100 % (wort) or 4000 0000 hex = 100 % (double word)
• p0514: specific normalization
Refer to the description for p0514[0…9] and p0515[0…19] to p0524[0…19]
SINAMICS G120 Control Units CU240B-2/CU240E-2
22 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
Dyn. index (dynamic index)
For parameters with a dynamic index [0...n], the following information is specified here:
• Data set (if available).
• Parameter for the number of indices (n = number - 1).
The following information can be contained in this field:
• "CDS, p0170" (Command Data Set, CDS count)
Example:
p1070[0] main setpoint [command data set 0]
p1070[1] main setpoint [command data set 1], etc.
• "DDS, p0180" (Drive Data Set, DDS count)
Data sets can only be created and deleted when p0010 = 15.
Note
Information on the data sets can be taken from the following references:
Operating Instructions SINAMICS G120 Inverter with CU240B-2 and CU240E-2 Control Units.
Unit group and unit selection
The standard unit of a parameter is specified in square parentheses after the values for "Min",
"Max", and "Factory setting".
For parameters where the unit can be switched over, the specifications for "Unit group" and
"Unit selection" determine the group to which this parameter belongs and with which parameter
the unit can be switched over.
Example:
Unit group: 7_1, unit selection: p0505
The parameter belongs to unit group 7_1 and the unit can be switched over using p0505.
All the potential unit groups and possible unit selections are listed below.
Table 2-3 Unit group (p0100)
Unit group Unit Choice for p0100 = Reference variable for %
0 1 2
7_4 Nm lbf ft Nm -
14_6 kW hp kW -
2
25_1 kg m lb ft2 kg m2 -
27_1 kg lb kg -
28_1 Nm/A lbf ft/A Nm/A -
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 23
2 Parameters
2.1 Overview of parameters
Table 2-4 Unit group (p0505)
Unit group Unit Choice for p0505 = Reference variable for %
1 2 3 4
2_1 Hz % Hz % p2000
3_1 1 rpm % 1 rpm % p2000
5_1 Vrms % Vrms % p2001
5_2 V % V % p2001
5_3 V % V % p2001
6_2 Arms % Arms % p2002
6_5 A % A % p2002
7_1 Nm % lbf ft % p2003
7_2 Nm Nm lbf ft lbf ft -
14_5 kW % hp % r2004
14_10 kW kW hp hp -
21_1 °C °C °F °F -
21_2 K K °F °F -
39_1 1/s2 % 1/s2 % p2007
Table 2-5 Unit group (p0595)
Unit group Unit Choice for p0595 = Reference variable for %
Value Unit
9_1 The values that can be set and the technological units are shown in p0595.
Function diagram
The parameter is included in this function diagram. The structure of the parameter function and
its relationship with other parameters is shown in the specified function diagram.
SINAMICS G120 Control Units CU240B-2/CU240E-2
24 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
Parameter values
Min Minimum value of the parameter [unit]
Max Maximum value of the parameter [unit]
Factory setting Value when delivered [unit]
In the case of a binector/connector input, the signal source of the
default BICO interconnection is specified. A non-indexed connector
output is assigned the index [0].
A different value may be displayed for certain parameters (e.g. p1800)
at the initial commissioning stage or when establishing the factory
settings.
Reason:
The setting of these parameters is determined by the operating
environment of the Control Unit (e.g. depending on device type, power
unit).
Description
Explanation of the function of a parameter.
Values
Lists the possible values of a parameter.
Recommendation
Information about recommended settings.
Index
The name and meaning of each individual index is specified for indexed parameters.
The following applies to the values (Min, Max, Factory setting) of indexed adjustable
parameters:
• Min, Max:
The adjustment range and unit apply to all indices.
• Factory setting:
When all indices have the same factory setting, index 0 is specified with the unit to
represent all indices.
When the indices have different factory settings, they are all listed individually with the unit.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 25
2 Parameters
2.1 Overview of parameters
Bit field
For parameters with bit fields, the following information is provided about each bit:
• Bit number and signal name
• Meaning for signal states 0 and 1
• Function diagram (FP) (optional).
The signal is shown on this function diagram.
Dependency
Conditions that must be fulfilled in conjunction with this parameter. Also includes special effects
that can occur between this parameter and others.
Where necessary, "Refer to:" indicates the following information:
• List of other relevant parameters to be considered.
• List of faults and alarms to be considered.
Safety guidelines
Important information that must be observed to avoid the risk of physical injury or material
damage.
Information that must be observed to avoid any problems.
Information that the user may find useful.
Danger The description of this safety notice can be found at the beginning of this
manual, see "Legal information (Page 4)".
Warning The description of this safety notice can be found at the beginning of this
manual, see "Legal information (Page 4)".
Caution The description of this safety notice can be found at the beginning of this
manual, see "Legal information (Page 4)".
Notice The description of this safety notice can be found at the beginning of this
manual, see "Legal information (Page 4)".
Note Information that the user may find useful.
SINAMICS G120 Control Units CU240B-2/CU240E-2
26 List Manual, 09/2020, A5E33839529
2 Parameters
2.1 Overview of parameters
2.1.2 Number ranges of parameters
Note
The following number ranges represent an overview for all the parameters available for the
SINAMICS drive family.
The parameters for the product described in this List Manual are described in detail in "List of
parameters (Page 30)".
Parameters are grouped into the following number ranges:
Table 2-6 Number ranges for SINAMICS
Range Description
From To
0000 0099 Display and operation
0100 0199 Commissioning
0200 0299 Power section
0300 0399 Motor
0400 0499 Encoder
0500 0599 Technology and units, motor-specific data, probes
0600 0699 Thermal monitoring, maximum current, operating hours, motor data,
central probe
0700 0799 Control Unit terminals, measuring sockets
0800 0839 CDS, DDS data sets, motor changeover
0840 0879 Sequence control (e.g. signal source for ON/OFF1)
0880 0899 ESR, parking, control and status words
0900 0999 PROFIBUS/PROFIdrive
1000 1199 Setpoint channel (e.g. ramp-function generator)
1200 1299 Functions (e.g. motor holding brake)
1300 1399 U/f control
1400 1799 Closed-loop control
1800 1899 Gating unit
1900 1999 Power unit and motor identification
2000 2009 Reference values
2010 2099 Communication (fieldbus)
2100 2139 Faults and alarms
2140 2199 Signals and monitoring
2200 2359 Technology controller
2360 2399 Staging, hibernation
2500 2699 Position control (LR) and basic positioning (EPOS)
2700 2719 Reference values, display
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual, 09/2020, A5E33839529 27
2 Parameters
2.1 Overview of parameters
Table 2-6 Number ranges for SINAMICS, continued
Range Description
From To
2720 2729 Load gearbox
2800 2819 Logic operations
2900 2930 Fixed values (e. g. percentage, torque)
3000 3099 Motor identification results