Fault · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

F30005Power unit: Overload I2t

What it means

F30005 (Power unit: Overload I2t) is raised when the I2t thermal image of the power unit reaches its limit: the overload utilization in r0036 stands at 100 %. The drive tracks the thermal loading of the power unit continuously from the output current; when the power unit draws more than its permissible rated current for an inadmissibly long time, or the application exceeds the permissible load duty cycle, the thermal image saturates and the drive trips. The stored fault value shows the I2t utilization in r0949 as a decimal number, where 16384 corresponds to 100 %. The manuals describe the same condition and the same causes for the power unit everywhere; they differ only in the extra remedy steps they print.

Why it appears

  • The power unit was overloaded — the I2t utilization in r0036 has reached 100 %.
  • The permissible rated power unit current was exceeded for an inadmissibly long time.
  • The permissible load duty cycle was not maintained.

What to check

  1. Reduce the continuous load on the drive.
  2. Adapt the load duty cycle so that the permissible load duty cycle of the power unit is maintained.
  3. Check the rated currents of the motor and the power unit against each other; the manual names the rated power unit power (r0206) and the rated motor power (p0307) alongside this step.
  4. Reduce the current limit (p0640) — a step printed by the G120, G120XA, G115D and G120C manuals.
  5. During operation with the U/f characteristic, reduce the integral time of the current limiting controller (p1341) — again printed by the G120, G120XA, G115D and G120C manuals.
  6. Increase p0294 — the I2t overload alarm threshold of the power unit; the VECTOR drive objects of the G130/G150 and S120/S150 manuals additionally list this step.

Reading the message value

  • The drive writes the fault value into r0949; interpret it as a decimal number.
  • The value is the I2t utilization of the power unit, scaled so that 100 % = 16384.

Parameters the manual names

  • r0036 — shows the current I2t utilization of the power unit; F30005 is raised when it reaches 100 %.
  • r0949 — holds the fault value of F30005; read it as the decimal I2t utilization (100 % = 16384) to see how far the thermal image was loaded.
  • p0640 — current limit; reduce it so the power unit draws less current.
  • p1341 — integral time of the current limiting controller; reduce it when the drive operates with the U/f characteristic.
  • p0294 — I2t overload alarm threshold of the power unit; the G130/G150 and S120/S150 entries for the VECTOR drive objects advise increasing it.
  • r0206 — rated power unit power; displayed when checking that the power unit rating matches the motor.
  • p0307 — rated motor power; the counterpart to r0206 when comparing motor and power unit ratings.

Acknowledging and restarting

The drive opens OFF2: the power unit switches off and the motor coasts to a standstill. The fault has to be acknowledged before the drive will run again, and it can be acknowledged immediately. If the load condition that drove r0036 to 100 % is still present, the drive trips again as soon as the thermal image fills up once more — remove the overload before restarting.

What differs between the drive families

Straight from the manuals' own fields — F30005 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G120OFF2IMMEDIATELYPower electronics faulted (5)SINAMICS G120 · p. 906
G130, G150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS G130, G150 List Manual · p. 1650
G130, G150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS G130, G150 List Manual · p. 1650
S120, S150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS S120, S150 List Manual · p. 2938
G120XAOFF2IMMEDIATELYSINAMICS G120XA PN converter · p. 1152
S120, S150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS S120, S150 List Manual · p. 2939
G115DSINAMICS G115D distributed drive · p. 396
G120CSINAMICS G120C Converters · p. 387

The drives this code lives on

F30005 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F30005 mean on a SINAMICS drive?

The I2t thermal overload model of the power unit has reached 100 % (r0036 = 100 %): the permissible rated power unit current was exceeded for too long, or the permissible load duty cycle was not maintained.

How do I clear F30005 and restart the drive?

The drive trips with OFF2 and coasts; the fault can be acknowledged immediately. Remove the overload first — if r0036 fills back up to 100 %, the drive trips again.

Which parameters matter for F30005?

r0036 shows the I2t utilization and r0949 the fault value (100 % = 16384). Depending on the manual, reduce the current limit p0640, reduce p1341 during U/f operation, or increase the alarm threshold p0294.

Why does F30005 keep coming back?

Because the continuous load or the load duty cycle still exceeds what the power unit permits. Reduce the load, adapt the duty cycle, and check that the rated currents of motor and power unit match (r0206, p0307).