Fault · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

F07924Drive: Torque/speed too high

What it means

F07924 is the load monitoring fault: the drive has detected a torque or speed that is too high for the monitored condition. What is monitored is set in p2193. With p2193 = 1 the drive checks the torque against a torque/speed envelope characteristic and raises the fault when the torque lies too high. With p2193 = 2 the drive compares the speed signal of an external encoder, interconnected in p3230, with its smoothed actual speed r2169 and raises the fault when the encoder speed lies too high. Both variants are described for G120 and G120XA; for S120/S150 and G130/G150 the manuals give the envelope deviation only, and for G115D and G120C they list the message title without further detail. The codes F07923 Drive: Torque/speed too low and F07925 Drive: Torque/speed out of tolerance are separate messages.

Why it appears

  • p2193 = 1: the torque deviates from the torque/speed envelope characteristic — it lies too high.
  • p2193 = 2: the speed signal from the external encoder (refer to p3230) deviates from the smoothed actual speed r2169 — it is too high. The manual describes this encoder comparison for G120 and G120XA; on S120/S150 and G130/G150 only the envelope deviation is given as the cause.

What to check

  1. Check the connection between the motor and the load.
  2. Adapt the parameterization to the actual load — with p2193 = 1 the torque/speed envelope characteristic, with p2193 = 2 the encoder speed interconnection in p3230.

Parameters the manual names

  • p2193 (load monitoring configuration): selects what the load monitoring compares for this fault — 1 = torque against the torque/speed envelope characteristic, 2 = external encoder speed against the actual speed.
  • p3230 (CI: load monitoring speed actual value): the interconnection through which the external encoder speed reaches the load monitoring; relevant when p2193 = 2.
  • r2169 (CO: actual speed smoothed): the drive's smoothed actual speed that serves as the reference value in the comparison when p2193 = 2.

Acknowledging and restarting

Depending on the configured reaction, the drive brakes along the ramp to a standstill (OFF1), coasts down (OFF2), executes a fast stop (OFF3) or takes no automatic action when this fault occurs. Once the cause has been removed, the fault can be acknowledged immediately — for example from the operator panel or the commissioning tool — and the drive can then be started again.

What differs between the drive families

Straight from the manuals' own fields — F07924 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G120OFF1 (NONE, OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)SINAMICS G120 · p. 888
G120XAOFF1 (NONE, OFF2, OFF3)IMMEDIATELYSINAMICS G120XA PN converter · p. 1139
S120, S150OFF1 (NONE, OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)MotorSINAMICS S120, S150 List Manual · p. 2883
G130, G150OFF1 (NONE, OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)MotorSINAMICS G130, G150 List Manual · p. 1611
G115DSINAMICS G115D distributed drive · p. 394
G120CSINAMICS G120C Converters · p. 385

The drives this code lives on

F07924 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07924 mean on a SINAMICS drive?

The load monitoring function has detected a torque or speed that is too high. With p2193 = 1 the torque lies above the torque/speed envelope characteristic; with p2193 = 2 the external encoder speed lies above the smoothed actual speed r2169.

How do I clear fault F07924?

Check the connection between the motor and the load and adapt the load monitoring parameterization to the actual load. The fault can then be acknowledged immediately and the drive restarted.

Which parameters are relevant for F07924?

p2193 selects the monitoring mode (1 = torque/speed envelope, 2 = encoder speed comparison), p3230 interconnects the external encoder speed, and r2169 holds the smoothed actual speed used as the reference.

Why does F07924 trigger with an external encoder?

When p2193 = 2, the load monitoring compares the encoder speed signal interconnected in p3230 against the drive's smoothed actual speed r2169; an encoder signal that deviates too high raises the fault.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals