SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F07913Excitation current outside the tolerance range

What it means

F07913 tells you that the excitation current is no longer being held within its tolerated range: the difference between the actual value (r1641) and the setpoint (r1626) has grown larger than the threshold p3201 plus the hysteresis p3202, i.e. abs(r1641 - r1626) > p3201 + p3202. As soon as the deviation falls back below p3201, the underlying condition resets itself in the background — but a fault that has tripped must still be acknowledged before the drive will run again.

Why it appears

  • The excitation current actual value r1641 and the setpoint r1626 have drifted apart beyond the tolerated band: abs(r1641 - r1626) > p3201 + p3202.
  • The fault condition is considered cleared again as soon as abs(r1641 - r1626) drops below p3201.

What to check

  1. Check the parameterization this monitoring works with: p1640 (signal source of the excitation current actual value), p3201 (tolerance threshold) and p3202 (hysteresis).
  2. Check the interfaces to the excitation equipment — the setpoint at r1626 and the actual-value path configured in p1640.
  3. Check the excitation equipment itself.

Parameters the manual names

  • r1641 — excitation current actual value: shows what the drive currently measures, for comparison against the setpoint.
  • r1626 — CO: excitation current setpoint: the value the excitation current should reach; compare it with r1641 while the fault is present.
  • p3201 — excitation current tolerance threshold: the fault trips above p3201 + p3202, and the condition releases again below this threshold.
  • p3202 — excitation current tolerance hysteresis: the amount added to p3201 at which the fault trips.
  • p1640 — CI: signal source of the excitation current actual value: defines where the drive reads the measured excitation current from; check it when the interface to the excitation equipment is suspect.

Acknowledging and restarting

The drive coasts down (OFF2) when this fault trips. Acknowledge it immediately; the drive can then be restarted. Note that the monitored deviation already clears itself once abs(r1641 - r1626) is below p3201 — acknowledging removes the latched fault message from the drive.

The same on every family

Every manual that describes F07913 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2881
G130, G150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1610

The drives this code lives on

F07913 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07913 mean?

The excitation current actual value r1641 has deviated from the setpoint r1626 by more than the tolerance p3201 + p3202 allows. The drive coasts down (OFF2) and the fault must be acknowledged immediately.

How do I clear F07913?

Work through the checks — the parameterization of p1640, p3201 and p3202, the interfaces to the excitation equipment, and the equipment itself — so that abs(r1641 - r1626) falls below p3201, then acknowledge the fault immediately and restart the drive.

Why does F07913 remain even though the excitation current looks correct now?

The trip and release levels differ: the fault trips above p3201 + p3202 and only releases below p3201, and the fault message stays latched until it is acknowledged.

Which parameters belong to F07913?

p1640 (actual value signal source), p3201 (tolerance threshold) and p3202 (hysteresis) are the settings to check; r1626 and r1641 show the setpoint and actual value for comparison.

Codes next to this one