Fault · SINAMICS G130, G150, S120, S150

F07914Flux out of tolerance

What it means

F07914 (fault, “Flux out of tolerance”) is raised when the difference between the flux actual value r0084 and the total flux setpoint r1598 exceeds the configured tolerance: abs(r0084 - r1598) > p3204 + p3205. The condition is only turned into a fault after the delay time in p3206 has expired, so brief excursions do not trip the drive; as soon as the deviation falls back below p3204, a pending cause is reset again.

Why it appears

  • The difference between the flux actual value r0084 and the total flux setpoint r1598 has exceeded the tolerance: abs(r0084 - r1598) > p3204 + p3205.
  • The fault is only issued once the delay time in p3206 has expired; the cause is reset again for abs(r0084 - r1598) < p3204.

What to check

  1. Check the parameterization of the tolerance values p3204 and p3205.
  2. Check the interfaces to the excitation equipment: the excitation current setpoint signal r1626 and the signal source p1640 for the excitation current actual value.
  3. Check the excitation equipment itself.
  4. Check the flux control, in particular the settings in p1590, p1592 and p1597.
  5. Check the control for oscillation and take appropriate countermeasures, for example optimize the speed control loop or parameterize a bandstop filter.

Parameters the manual names

  • r0084 — CO: Flux actual value; read it together with r1598 to see how far the flux has actually deviated.
  • r1598 — CO: Total flux setpoint; the reference value against which r0084 is compared.
  • p3204 — Flux outside the tolerance threshold value; the fault trips above p3204 + p3205 and the cause resets again below p3204, so check this setting first.
  • p3205 — Flux outside the tolerance hysteresis; verify it together with p3204 when checking the tolerance parameterization.
  • p3206 — Flux outside tolerance delay time; the fault is only issued after this time has expired.
  • r1626 — CO: Excitation current setpoint; check this signal when verifying the interface to the excitation equipment.
  • p1640 — CI: Excitation current actual value signal source; check this link as part of the excitation-equipment interface check.
  • p1590 — Flux controller P gain; check the setting when verifying the flux control.
  • p1592 — Flux controller integral time; check the setting together with p1590 when verifying the flux control.

Acknowledging and restarting

The drive responds to this fault with a coast-down (OFF2). Eliminate the cause first; the fault can then be acknowledged immediately, after which the drive can be restarted. The underlying condition clears by itself once abs(r0084 - r1598) falls below p3204, but the fault message itself still has to be acknowledged.

The same on every family

Every manual that describes F07914 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2881
G130, G150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1610

The drives this code lives on

F07914 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07914 mean on my SINAMICS drive?

It reports “Flux out of tolerance”: the difference between the flux actual value r0084 and the total flux setpoint r1598 exceeds the tolerance p3204 + p3205, and the fault is issued once the delay time in p3206 has expired.

How do I clear fault F07914?

Remove the cause first — work through the checks for the tolerance parameterization (p3204, p3205), the excitation equipment interfaces (r1626, p1640) and the flux control. The drive has tripped with a coast-down (OFF2); after the cause is corrected the fault can be acknowledged immediately and the drive restarted.

Which parameters belong to F07914?

The tolerance threshold p3204, the hysteresis p3205 and the delay time p3206 define the fault; r0084 and r1598 show the flux deviation; r1626 and p1640 belong to the excitation interface; p1590, p1592 and p1597 belong to the flux control.

Why does F07914 appear only after some time?

The drive only issues the fault after the delay time in p3206 has expired, and a pending cause is reset again as soon as the deviation falls below p3204.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.