Fault · SINAMICS G130, G150, S120, S150

F07928Internal voltage protection initiated

What it means

F07928 is raised when the Motor Module signals that the motor is short-circuited through the power semiconductors — the signal r1239.5 = 1 — while the internal voltage protection is selected (p1231 = 3). In this state the pulses cannot be enabled, and the armature short-circuit function of the Motor Module is the mechanism behind the fault. The manual describes the code identically for the Power Module on S120/S150 and on G130/G150, so everything below applies to all four families.

Why it appears

  • The Motor Module has signalled that the motor is short-circuited through the power semiconductors; the condition is stored as r1239.5 = 1.
  • The internal voltage protection is selected (p1231 = 3), so the pulses cannot be enabled and the drive trips with OFF2.

What to check

  1. Check whether your Motor Module supports the autonomous internal voltage protection: r0192.10 = 1 in the power unit firmware properties means it does. In that case the Motor Module decides by itself, from the DC link voltage, whether the armature short-circuit is activated.
  2. With the autonomous function, the armature short-circuit is activated and OFF2 is initiated as soon as the DC link voltage exceeds 800 V. The armature short-circuit is withdrawn once the DC link voltage falls below 450 V.
  3. If the motor is still in a critical speed range, the armature short-circuit is re-activated as soon as the DC link voltage again exceeds the threshold of 800 V, so expect the fault to return in this situation.
  4. If the autonomous internal voltage protection is active (r1239.5 = 1) and the line supply returns with the DC link voltage between 450 V and 800 V, the armature short-circuit is withdrawn after 3 minutes. Wait for this time before expecting the drive to enable pulses again.

Parameters the manual names

  • p1231 — Armature short-circuit / DC braking configuration (ASC/DCBRK config): this is where the internal voltage protection is selected; the fault presupposes the setting p1231 = 3.
  • r0192 — Power unit firmware properties 1 (PU FW properties 1): read bit r0192.10 here; a value of 1 shows that the Motor Module supports the autonomous internal voltage protection.

Acknowledging and restarting

The fault must be acknowledged immediately once the condition has cleared, and the drive does not start again until it has been acknowledged. The underlying condition clears by itself: the armature short-circuit is withdrawn when the DC link voltage falls below 450 V, or — if the autonomous internal voltage protection is active (r1239.5 = 1) and the line supply has returned with the DC link voltage between 450 V and 800 V — after 3 minutes. Only then can the pulses be enabled again and the drive restarted.

The same on every family

Every manual that describes F07928 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYApplication/technological function faulted (17)Power ModuleSINAMICS S120, S150 List Manual · p. 2884
G130, G150OFF2IMMEDIATELYApplication/technological function faulted (17)Power ModuleSINAMICS G130, G150 List Manual · p. 1613

The drives this code lives on

F07928 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07928 mean?

The Motor Module is signalling that the motor is short-circuited through the power semiconductors (r1239.5 = 1) while the internal voltage protection is selected (p1231 = 3). The pulses cannot be enabled, so the drive trips with OFF2.

Which parameters are relevant for F07928?

p1231 (ASC/DCBRK config) selects the internal voltage protection with the value 3, and bit r0192.10 in r0192 (PU FW properties 1) shows whether the Motor Module supports the autonomous internal voltage protection.

At which DC link voltage is the armature short-circuit activated and withdrawn?

It is activated, with an OFF2 response, when the DC link voltage exceeds 800 V and withdrawn when it falls below 450 V. If the motor is still in a critical speed range, it is re-activated once the DC link voltage again exceeds 800 V.

How is F07928 cleared?

Wait until the armature short-circuit is withdrawn — once the DC link voltage has fallen below 450 V, or after 3 minutes when the autonomous protection is active and the line supply has returned with the DC link voltage between 450 V and 800 V — and then acknowledge the fault immediately.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.