What it means
F07940 is reported by the Sync-line-drive function when synchronizing the drive to the line supply ends in an error. The manuals describe it for S120/S150 and for G130/G150, and describe the same situation from two sides: after synchronization has been completed, the phase difference (r3808) is greater than the threshold for phase synchronism (p3813); or synchronization is interrupted by an OFF1 or OFF3 response or by the enable being withdrawn (p3802 = 0); on S120/S150 additionally, the phase difference cannot be held within the time limit (p3818). On S120/S150 the fault value in r0949 tells you in binary which of these tripped; the G130/G150 manual names the conditions without bit numbers.
Why it appears
- Synchronizing the drive to the line supply ran into an error; the two manuals name the triggers as follows.
- After synchronization had been completed, the phase difference (r3808) exceeded the threshold for phase synchronism (p3813) — on S120/S150 for longer than 1 second, and this is the condition the G130/G150 manual names first.
- An OFF1 or OFF3 response arrived while synchronizing was still running: on S120/S150 while the motor was being synchronized to the line supply, on G130/G150 while closed-loop phase control was active (r3819.6 = 1) or synchronism had already been reached (r3819.2 = 1).
- The enable was withdrawn (p3802 = 0) while synchronizing was still in progress (S120/S150), or while closed-loop phase control was still active (G130/G150, r3819.6 = 1).
- On S120/S150 only: within the time limit (p3818) the phase difference could not be continuously limited to the threshold value.
What to check
- Read the fault value r0949 in binary: bit 0, bit 1 or bit 2 shows which trigger applied on S120/S150. On G130/G150 compare the situations above directly.
- If the phase difference was the trigger (bit 0 or bit 2 on S120/S150): if required increase the threshold for phase synchronism (p3813), increase the phase controller limiting (p3811), and increase the threshold for the frequency difference (p3806). For G130/G150 the manual names increasing p3813 if required as the remedy.
- If OFF1/OFF3 or the enable interrupted synchronizing (bit 1): complete synchronizing before OFF1 or OFF3 — on S120/S150 wait for r03819.2 = 1, on G130/G150 for r03819.0 = 0 — and withdraw the enable (p3802 = 0) only once synchronism is reached (r3819.2 = 1).
- If the time limit was exceeded (bit 2): increase the synchronization time limit (p3818).
Reading the message value
- On S120/S150 the message value %1 is the fault value in r0949, interpreted binary:
- Bit 0 = 1: after synchronization has been completed, the phase difference (r3808) is greater than the threshold value for phase synchronism (p3813) for longer than 1 second.
- Bit 1 = 1: while synchronizing the motor to the line supply, an OFF1 or OFF3 response occurred, or the enable was withdrawn while synchronizing (p3802 = 0).
- Bit 2 = 1: within the time limit (p3818), the phase difference was not able to be continuously limited to the threshold value.
- For G130/G150 the manual prints no message value for this fault.
Parameters the manual names
- r0949 — fault value; read it in binary to identify which bit this fault set.
- r3808 — CO: Sync-line-drive phase difference; shows the phase difference that is compared against the threshold in p3813.
- p3813 — Sync-line-drive phase synchronism threshold value; increase it if the phase difference stays above it.
- p3811 — Sync-line-drive frequency limiting; increasing it gives the phase controller more limiting.
- p3806 — Sync-line-drive frequency difference threshold value; increase it alongside p3813 for the phase-difference causes.
- p3818 — Sync-line-drive synchronization time limit; extend it when synchronization cannot be completed within the set time.
- p3802 — BI: Sync-line-drive enable; keep it at 1 until synchronism is reached (r3819.2 = 1).
Acknowledging and restarting
The response is the same in both manuals: the drive coasts down (OFF2) and the fault can be acknowledged immediately before the drive will run again. Remove the cause first — for example, let synchronization complete (r3819.2 = 1) before issuing OFF1/OFF3 or withdrawing the enable (p3802 = 0) — then acknowledge the fault.
The same on every family
Every manual that describes F07940 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2888 |
| G130, G150 | OFF2 | IMMEDIATELY | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1616 |
The drives this code lives on
F07940 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07940 Sync-line-drive: Synchronizing error mean?
The drive could not synchronize to the line supply: after synchronizing, the phase difference (r3808) stayed above the p3813 threshold, an OFF1/OFF3 response or the removal of the enable (p3802 = 0) interrupted synchronizing, or the p3818 time limit elapsed.
How do I find the exact trigger of F07940?
On S120/S150 read the fault value r0949 in binary: bit 0 = phase difference above the threshold, bit 1 = OFF1/OFF3 or enable removed, bit 2 = time limit exceeded. The G130/G150 manual names these conditions without bit numbers.
Which parameters should I change against F07940?
For the phase-difference causes increase p3813, p3811 and p3806; if the time limit tripped the fault, increase p3818. Interruption causes are not a parameter issue: complete synchronizing before OFF1/OFF3 and keep the enable (p3802) at 1 until r3819.2 = 1.
How is F07940 reset?
The drive coasts down on this fault, the fault can be acknowledged immediately, and after the cause has been removed the drive can run again.