Fault · SINAMICS G130, G150, S120, S150

F07937Drive: Speed deviation between motor model and external speed

What it means

F07937 is raised by the drive's speed monitoring. The monitoring continuously compares two speed actual values: the smoothed speed of the motor model (r2169) and the external speed actual value at the actual-value input of the speed controller (r1443). If the absolute value of the difference between the two exceeds the tolerance threshold p3236 for longer than permitted by p3238, the fault is raised. No message value is output with this fault. Depending on how the drive is configured, the same condition can also be output with no reaction (N).

Why it appears

  • The interconnection or the scaling of the external encoder signal is incorrect (p1440, p2000).
  • The speed encoder for the external encoder signal is faulty.
  • The polarity or the gain of the encoder signal is incorrect.
  • The smoothing time constant for the model speed used by the monitoring is set too high (p2157).
  • The smoothing time constant or the threshold values used by the monitoring are set too low (p3236, p3238).

What to check

  1. Check that the external speed matches the motor speed (compare p1440 and r1443).
  2. Check the polarity of the external speed (r1443).
  3. Check the interconnection of the connector input and the scaling of the signal (p1440, p2000).
  4. If no external encoder signal is being used: check the speed signal r0061. If it shows significant ripple, check the speed encoder and, if required, increase p0492.
  5. The monitoring itself is set up in p2149 (monitoring configuration).

Parameters the manual names

  • r2169 — the smoothed actual speed of the motor model; one of the two signals this monitoring compares.
  • r1443 — the speed actual value at the actual-value input of the speed controller (the external speed); the second compared signal, to be checked alongside r2169.
  • p3236 — speed threshold value 7: the tolerance threshold the speed difference may not exceed.
  • p3238 — how long the deviation between motor-model speed and external speed is tolerated before the fault is raised.
  • p1440 — interconnects the external speed signal to the actual-value input; check this interconnection.
  • p2000 — reference speed / reference frequency; the scaling against which the external signal is evaluated.
  • r0061 — the unsmoothed actual speed; check it when no external encoder signal is used.
  • p0492 — maximum speed difference per sampling cycle; increase it if r0061 shows significant ripple.
  • p2149 — monitoring configuration, where this comparison is configured.

Acknowledging and restarting

When the fault trips, the drive switches off and the motor coasts to a standstill; the reaction can be configured differently. Acknowledgement is immediate: once the cause has been corrected, the fault can be acknowledged straight away, without any special sequence, and the drive restarted. Where the condition is configured to be output with no reaction (N), the drive neither trips nor expects an acknowledgement — reaction and acknowledgement are then both NONE.

What differs between the drive families

Straight from the manuals' own fields — F07937 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150OFF2 (NONE, OFF1, OFF3)IMMEDIATELYApplication/technological function faulted (17)MotorSINAMICS G130, G150 List Manual · p. 1616
S120, S150OFF2 (NONE, OFF1, OFF3)Application/technological function faulted (17)MotorSINAMICS S120, S150 List Manual · p. 2887

The drives this code lives on

F07937 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What triggers fault F07937 on SINAMICS G130, G150, S120 and S150?

The absolute difference between the motor model's smoothed speed (r2169) and the external speed actual value (r1443) exceeded the threshold p3236 for longer than the time set in p3238.

How do I clear and restart after F07937?

Correct the external speed signal first — check that it matches the motor speed, its polarity (r1443) and its interconnection and scaling (p1440, p2000). The fault is then acknowledged immediately and the drive restarted.

I am not using an external encoder — why do I still get F07937?

In that case check the speed signal r0061; if it shows significant ripple, check the speed encoder and increase p0492 if required.

Which parameters define the F07937 monitoring?

The threshold p3236 and the permitted duration p3238 define when the fault is raised, the smoothing is affected by p2157, and the monitoring configuration sits in p2149.