What it means
F01034 is raised during the units changeover: a reference parameter was changed, and the drive then attempted to re-calculate the affected parameters in the per-unit representation. For one of the parameters involved this was not possible with the value that had been selected, so the drive rejected the change and restored the original parameter value. The manuals print the fault as Units changeover: Calculation parameter values after reference value change
; several converter families title the same condition with the addition “unsuccessful”. The fault value in r0949 names the parameter concerned.
Why it appears
- A reference parameter was changed, and for one of the parameters involved the selected value could not be re-calculated in the per-unit representation.
- The change was rejected and the original parameter value was restored.
What to check
- Read the fault value in r0949 — it contains the number of the parameter whose value was not able to be re-calculated.
- Select the value of the reference parameter so that this parameter can be re-calculated in the per-unit representation.
- Before changing the reference parameter p0596, set the technology unit selection p0595 = 1.
Reading the message value
- r0949 holds the fault value:
Parameter whose value was not able to be re-calculated
. The message valueParameter: %1
shows the same — the drive inserts the number of the affected parameter for the placeholder. - The parameters the drive re-calculates in the per-unit notation after a reference change are p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003 and r2004; the fault value names the one that failed.
Parameters the manual names
- r0949 — fault value; read here which parameter could not be re-calculated.
- p0595 — technology unit selection; set p0595 = 1 before changing the reference parameter p0596.
- p0596 — technological unit reference quantity; the change of this reference parameter triggers the re-calculation.
- p0304 — rated motor voltage; one of the parameters re-calculated in the per-unit notation.
- p0305 — rated motor current; likewise re-calculated in per-unit notation when a reference parameter changes.
- p0310 — cylinder piston diameter; belongs to the same set of re-calculated parameters.
- p2000 — reference velocity; re-calculated in the per-unit representation.
- p2001 — reference voltage; re-calculated together with the other reference quantities.
- p2002 — reference pressure; involved in the per-unit re-calculation.
- p2003 — reference force; involved in the per-unit re-calculation.
- r2004 — reference power; involved in the per-unit re-calculation.
Acknowledging and restarting
The drive itself rolls the failed change back — the original parameter value is restored — and takes no automatic reaction beyond reporting the fault. Acknowledge the fault immediately. Once the reference parameter is selected so that the affected parameter can be re-calculated in the per-unit representation, and p0595 is set to 1 before p0596 is changed, the units changeover can be repeated.
What differs between the drive families
Straight from the manuals' own fields — F01034 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2563 |
| G130, G150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1377 |
| G120 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 824 |
| G120XA | NONE | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1101 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 382 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 392 |
The drives this code lives on
F01034 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01034 mean on a SINAMICS drive?
During the units changeover a reference parameter was changed, and one of the parameters involved could not be re-calculated in the per-unit representation with the selected value. The change was rejected and the original parameter value restored.
How can I see which parameter caused F01034?
The fault value in r0949 contains the number of the parameter whose value could not be re-calculated. The parameters re-calculated in per-unit notation are p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003 and r2004.
How do I fix fault F01034?
Select the reference parameter value so that the parameter named in r0949 can be re-calculated in the per-unit representation. Before changing the reference parameter p0596, set p0595 = 1, then repeat the change and acknowledge the fault immediately.
Does F01034 stop the drive?
The drive takes no automatic reaction to this fault; it only reports that the changeover step failed and rolls the change back. The fault can be acknowledged immediately.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.