What it means
F01031 is raised when, with the "OFF in REMOTE" mode active, no sign-of-life has been received within 3 seconds. The manuals for G130, G150, S120 and S150 describe the fault with the same cause, and no message value is supplied with it. The affected drive object is switched off along the response the table shows for it, and the message must be acknowledged immediately before the drive can run again.
Why it appears
- While the "OFF in REMOTE" mode is active, no sign-of-life reached the drive within 3 seconds.
What to check
- Check that the data cable is properly connected at the serial interface for the Control Unit (CU) and at the operator panel.
- Check the data cable that runs between the Control Unit and the operator panel.
Acknowledging and restarting
The fault must be acknowledged immediately. Once the data cable fault has been found and removed, an immediate acknowledgement is all the manual describes for clearing F01031; no further reset step is given.
What differs between the drive families
Straight from the manuals' own fields — F01031 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF1 (NONE, OFF2) Servo: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2) Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2) Hla: OFF3 (NONE, OFF1, OFF2, STOP2) | IMMEDIATELY | Communication error to the higher-level control system (9) | None | SINAMICS S120, S150 List Manual · p. 2562 |
| G130, G150 | Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2) Infeed: OFF1 (NONE, OFF2) | IMMEDIATELY | Communication error to the higher-level control system (9) | None | SINAMICS G130, G150 List Manual · p. 1376 |
The drives this code lives on
F01031 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What causes SINAMICS fault F01031?
The drive was in "OFF in REMOTE" mode and received no sign-of-life within 3 seconds.
How do I fix F01031?
Check the data cable connection at the serial interface for the Control Unit (CU) and at the operator panel, then check the cable between the Control Unit and the operator panel, and acknowledge the fault immediately.
Does F01031 need a special reset?
No. The manual only requires the message to be acknowledged immediately once the cable problem is corrected.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.