What it means
A07991 announces that the motor data identification routine has been activated and will be carried out at the next switch-on command (ON). It is not a call to action: the manual's remedy is that none is necessary, because the alarm withdraws by itself once the routine has been completed or deactivated. Depending on the drive's configuration, the same condition can also be output with no reaction (N).
Why it appears
- The motor data identification routine is activated; it is carried out at the next switch-on command (ON).
- If rotating measurement is selected (see p1900, p1960), it will not be possible to save the parameter assignment until the motor data identification has been completed or deactivated. The manual prints this for the VECTOR and VECTOR_G drive objects and for G120.
- On the HLA drive object the entry carries the title Drive: Data identification activated: data identification is activated and performed at the next switch-on command, and the manual warns
When doing this, the drive moves.
What to check
- Do nothing beyond letting the routine run: the manual states the remedy is not necessary, and the alarm automatically disappears once the motor data identification has been completed successfully.
- If you want to abort the identification instead, deactivate it with p1900 = 0; for the SERVO and HLA drive objects the manual names p1910 = 0 or p1960 = 0 as the settings that withdraw the alarm.
- Heed the warning the manual adds for the SERVO and HLA drive objects: if a POWER ON or a warm restart is performed while motor data identification is selected, the identification request is lost, and if identification is still required it must be selected again manually after ramp-up.
Parameters the manual names
- p1900 — Motor data identification and rotating measurement: use it to select the identification; with rotating measurement selected the parameter assignment cannot be saved, and p1900 = 0 deactivates the identification so the alarm clears.
- p1910 — Motor data identification selection: named for the SERVO and HLA drive objects, where p1910 = 0 is one of the settings that ends the alarm.
- p1960 — Rotating measurement selection: named together with p1900 wherever rotating measurement is selected, and on the SERVO and HLA drive objects as the alternative setting p1960 = 0 that withdraws the alarm.
Acknowledging and restarting
No acknowledgement is required. The alarm is withdrawn automatically when the motor data identification (data identification on the HLA drive object) has been completed successfully, or when you deactivate the selection — p1900 = 0, or p1910 = 0 / p1960 = 0 for the SERVO and HLA drive objects. Note that a POWER ON or a warm restart performed with identification selected discards the request, so the identification would then have to be selected again manually after ramp-up.
What differs between the drive families
Straight from the manuals' own fields — A07991 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | NONE OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2) | NONE NONE IMMEDIATELY (POWER ON) IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1147 |
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2911 |
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2912 |
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2912 |
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1631 |
| G120 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 897 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 386 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 395 |
The drives this code lives on
A07991 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A07991 mean on a SINAMICS drive?
That the motor data identification routine has been activated and will be carried out at the next switch-on command (ON). On the HLA drive object the same alarm appears as 'Drive: Data identification activated', and the drive moves while the identification runs.
How do I clear or reset A07991?
No acknowledgement is required. The alarm disappears automatically once the motor data identification has been completed successfully, or immediately if you deactivate the identification with p1900 = 0 (p1910 = 0 or p1960 = 0 on the SERVO and HLA drive objects).
Why can I not save the parameter assignment while A07991 is active?
Because rotating measurement is selected (see p1900, p1960). The option to save returns once the motor data identification has been completed or deactivated.
What happens if the drive is powered down while A07991 is shown?
A POWER ON or a warm restart performed with motor data identification selected makes the identification request lost. If identification is still needed, it must be selected again manually after ramp-up.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals