Alarm · SINAMICS S120, S150

A07999Drive: Motor data identification cannot be activated

What it means

The drive issues A07999 when motor data identification is to be activated but cannot be selected: closed-loop control is still enabled on a SERVO drive object type. Before motor data identification can be selected, pulses must be suppressed for all SERVO drive objects. As long as any SERVO drive object keeps its closed-loop control enabled, the identification stays blocked and the alarm is present.

Why it appears

  • Closed-loop control is enabled on a SERVO drive object type — to select motor data identification, pulses must be suppressed for all SERVO drive objects.

What to check

  1. Withdraw the pulse enable on all drives.
  2. Re-activate the motor data identification.

Reading the message value

  • The drive stores the alarm value in r2124; it is to be interpreted as a decimal number.
  • The value identifies the drive object with enabled closed-loop control.

Parameters the manual names

  • r2124 — alarm value: read it as a decimal number to identify the drive object whose enabled closed-loop control is blocking the motor data identification.

The same on every family

Every manual that describes A07999 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2916

The drives this code lives on

A07999 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

Why can I not activate motor data identification on SINAMICS S120 or S150?

The drive reports A07999 because closed-loop control is still enabled on a SERVO drive object type. Motor data identification can only be selected when pulses are suppressed for all SERVO drive objects.

How do I clear alarm A07999?

Withdraw the pulse enable on all drives and then re-activate the motor data identification.

What does the r2124 alarm value of A07999 tell me?

Interpreted as a decimal number, it identifies the drive object on which closed-loop control is still enabled.