Alarm · SINAMICS G120, G130, G150, S120, S150

A07994Drive: motor data identification not performed

What it means

A07994 appears when vector control has been selected but the motor data identification has still not been performed for the drive data set that is currently active. On the G120 the alarm is also raised when the application class Standard Drive Control, STC (p0096 = 1) has been selected without a motor data identification.

The drive checks the condition when the drive data set is changed (see r0051). The manuals also note that a check is made — and the alarm output — when commissioning is exited and when the drive powers up (the S120/S150 manual words this as when the system runs up). Depending on the drive configuration, the same condition can also be issued as a fault (F) or as a message without reaction (N).

Why it appears

  • Vector control has been selected — p1300 >= 20 in the currently active drive data set — while motor data identification has still not been performed for that data set; r3925 shows the identification status.
  • The alarm is initiated when the drive data set is changed (see r0051) if both conditions apply to the data set being activated.
  • On the G120: the application class Standard Drive Control, STC (p0096 = 1) has been selected and motor data identification has still not been performed.
  • A check is also made — and the alarm output — when commissioning is exited and when the drive powers up (S120/S150: when the system runs up).

What to check

  1. Perform the motor data identification for the affected drive data set (p1900).
  2. If vector control is not actually required, parameterize U/f control instead (p1300 < 20).
  3. G120 only: if the alarm came from the application class, set p0096 = 0.
  4. Alternatively, switch over to a drive data set in which the conditions do not apply.

Parameters the manual names

  • p1900 — motor data identification and rotating measurement: use it to perform the identification that clears the alarm.
  • p1300 — open-loop/closed-loop control operating mode: p1300 >= 20 selects vector control and demands the identification, p1300 < 20 selects U/f control and removes the condition.
  • r3925 — identification final display: shows whether motor data identification has been performed in the actual drive data set.
  • p0096 — application class (G120): p0096 = 1 is Standard Drive Control, STC and requires motor data identification; setting p0096 = 0 is the G120 remedy when the application class caused the alarm.

Acknowledging and restarting

As an alarm, A07994 has no effect on the drive's operation and needs no acknowledgement: it clears itself once the condition no longer applies — after the motor data identification (p1900), after switching to U/f control (p1300 < 20), on the G120 after p0096 = 0, or after changing to a drive data set to which the conditions do not apply.

If the drive is configured to issue the same condition as a fault instead, the drive coasts down (OFF2) and the fault must be acknowledged immediately before it will restart.

What differs between the drive families

Straight from the manuals' own fields — A07994 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2913
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1632
G120NONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 897

The drives this code lives on

A07994 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07994 mean on a SINAMICS drive?

Vector control (p1300 >= 20) is selected in the active drive data set, but motor data identification has not been performed for it. On the G120, application class Standard Drive Control, STC (p0096 = 1) without identification also raises the alarm.

How do I clear A07994?

Perform the motor data identification with p1900, or parameterize U/f control (p1300 < 20) if vector control is not required; on the G120 you can also set p0096 = 0. Alternatively, switch to a drive data set in which the conditions do not apply.

Does A07994 have to be acknowledged?

No — as an alarm it has no effect on operation and clears itself once the condition is removed. If the drive issues the condition as a fault instead, it coasts down (OFF2) and must be acknowledged immediately before restarting.

Why does A07994 appear at power-up even though nothing was changed?

The manuals note that the check is also made when commissioning is exited and when the drive powers up (S120/S150: when the system runs up), so a data set parameterized without identification triggers the alarm at every start.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.