Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A07981Drive: Enable signals for the rotating measurement missing

What it means

A07981 is an alarm that appears when a rotating measurement is to be performed but cannot begin. The rotating measurement cannot be started due to missing enable signals. The drive is being asked to run the measurement, but the enable signals it requires have not been applied, so the measurement never starts. Which enable signals are expected depends on the setting of p1959.13: with p1959.13 = 1, the rotating measurement checks the ramp-function generator enables and the speed controller integrator enables named below.

Why it appears

  • The rotating measurement cannot be started because the required enable signals are missing.
  • When p1959.13 = 1, two groups of enables are the ones that matter: the enable signals for the ramp-function generator (see p1140 ... p1142) and the enable signals for the speed controller integrator (see p1476, p1477).

What to check

  1. Acknowledge any faults that are present.
  2. Establish the missing enable signals: with p1959.13 = 1, the rotating measurement expects the ramp-function generator enables (p1140 ... p1142) and the speed controller integrator enables (p1476, p1477).
  3. Check r0002 (Control Unit operating display) and r0046 (missing enable signal) to see which enable signals are still missing.

Parameters the manual names

  • p1959 — data identification moving configuration: the enable checks for this alarm apply when p1959.13 = 1; confirm this bit first to know which enables the rotating measurement expects.
  • p1140 — BI: Enable ramp-function generator/inhibit ramp-function generator; one of the ramp-function generator enable signals (p1140 ... p1142) that must be established.
  • p1142 — BI: Enable setpoint/inhibit setpoint; also part of the ramp-function generator enable range p1140 ... p1142 named for this alarm.
  • p1476 — BI: Velocity controller hold integrator; an enable signal for the speed controller integrator that must be present.
  • p1477 — BI: Velocity controller set integrator value; the second speed controller integrator signal named for this alarm.
  • r0002 — Control Unit operating display; the manual names it, together with r0046, when establishing the missing enable signals.
  • r0046 — missing enable signal; shows the enable signal that is missing so you know what has to be established.

Acknowledging and restarting

A07981 itself does not require an acknowledgment from you. It is resolved by removing the cause: acknowledge any faults that are present and establish the missing enable signals — the rotating measurement can then be started.

What differs between the drive families

Straight from the manuals' own fields — A07981 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2900
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1625
G120NONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 893
G120XANONESINAMICS G120XA PN converter · p. 1143
G120CSINAMICS G120C Converters · p. 385
G115DSINAMICS G115D distributed drive · p. 395

The drives this code lives on

A07981 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A07981 mean?

It means the rotating measurement cannot be started because the enable signals it requires are missing. With p1959.13 = 1, the affected enables are those of the ramp-function generator (p1140 ... p1142) and the speed controller integrator (p1476, p1477).

How do I fix alarm A07981?

Acknowledge any faults that are present, then establish the missing enable signals. r0002 (Control Unit operating display) and r0046 (missing enable signal) show you what is still missing.

Does A07981 have to be acknowledged?

No, the alarm itself needs no acknowledgment. Only faults that are present have to be acknowledged before the rotating measurement is started again.

Which parameters belong to A07981?

p1959.13 decides which enable signals are checked: the ramp-function generator enables are p1140 ... p1142 and the speed controller integrator signals are p1476 and p1477. r0002 and r0046 help you find the missing enables.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.