Alarm · SINAMICS G120, G130, G150, S120, S150

A01669SI Motion: Unfavorable combination of motor and power unit

What it means

A01669 is the SI Motion message for an unfavorable combination of motor and power unit: the combination in use is not suitable for running the safe motion monitoring functions without an encoder. The concrete criterion is the current ratio — the ratio of the power unit rated current (r0207[0]) to the rated motor current (p0305) is greater than 5. Depending on how the drive is configured, the same condition can also be output as a fault (F) or with no reaction (N). The manuals describe the code with the same cause and remedy for every family on this page, so the following applies to all of them.

Why it appears

  • The motor and power unit combination in use is not suitable for using the safe motion monitoring functions without an encoder.
  • The ratio of the power unit rated current (r0207[0]) to the rated motor current (p0305) is greater than 5.
  • The drive notes that if this alarm is not observed, message C01711 or C30711 — with the value 1041 ... 1044 — can occur sporadically.

What to check

  1. Read the alarm value r2124 as a decimal number: it names the motor data set that caused the message.
  2. For that motor data set, compare the power unit rated current (r0207[0]) with the rated motor current (p0305) — the ratio is greater than 5, which is what makes the combination unsuitable for the safe motion monitoring functions without an encoder.
  3. Use a suitable power unit with a lower power rating or a motor with a higher power rating.

Reading the message value

  • r2124 (interpret the value as decimal): number of the motor data set, which caused the fault.

Parameters the manual names

  • r0207[0] — power unit rated current; together with p0305 it forms the ratio that decides whether the motor/power unit combination is suitable.
  • p0305 — rated motor current; check this value for the motor data set that r2124 names.
  • r2124 — alarm value; read it as a decimal number to identify the motor data set which caused the message.

Acknowledging and restarting

In the alarm form the drive executes no stop and nothing has to be acknowledged; the message keeps coming back until a suitable combination of motor and power unit is in use. In the fault form the message is acknowledged immediately — for example by switching POWER ON — after which the drive can be restarted; if a stop reaction (OFF1, OFF2 or OFF3) is set for the fault form, the drive is restarted after that stop and the acknowledgement.

What differs between the drive families

Straight from the manuals' own fields — A01669 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2648
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1447
G120NONENONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 847

The drives this code lives on

A01669 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A01669 mean?

It reports that the connected combination of motor and power unit is not suitable for using the safe motion monitoring functions without an encoder. The ratio of the power unit rated current (r0207[0]) to the rated motor current (p0305) is greater than 5.

How do I fix A01669?

Use a suitable power unit with a lower power rating or a motor with a higher power rating. The alarm value r2124 tells you which motor data set is affected.

Which motor data set triggered A01669?

The alarm value r2124, interpreted as a decimal number, contains the number of the motor data set which caused the fault.

Why do C01711 or C30711 appear after A01669?

The drive warns that if A01669 is not observed, message C01711 or C30711 with the value 1041 ... 1044 can occur sporadically.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals