Alarm · SINAMICS G130, G150, S120, S150

A01691SI Motion: Ti and To unsuitable for DP cycle

What it means

A01691 is raised when the DP cycle of the PROFIBUS communication is used as the actual value acquisition cycle for the SI Motion safe movement monitoring functions and the configured communication times Ti and To do not fit this cycle. Depending on the drive's configuration, the same condition can also be issued as a fault.

Why it appears

  • The configured times for the PROFIBUS communication are not permitted, while the DP cycle serves as the actual value acquisition cycle for the safe movement monitoring functions.
  • With isochronous PROFIBUS, the sum of Ti and To is too high for the selected DP cycle. The DP cycle should be at least 1 current controller cycle greater than the sum of Ti and To.
  • Without isochronous PROFIBUS, the DP clock cycle must be at least 4x the current controller clock cycle.
  • If this alarm is not observed, the message C01711 or C30711 – with the value 1020 ... 1021 – can occur sporadically.

What to check

  1. Configure Ti and To low so that they are suitable for the DP cycle, or increase the DP cycle time.
  2. Alternative when SI monitoring integrated in the drive is enabled (p9601/p9801 > 0): use the actual value acquisition cycle p9511/p9311 and set it independently from the DP cycle. The actual value sensing clock cycle must then be at least 4x the current controller clock cycle; a clock cycle ratio of at least 8:1 is recommended.

Parameters the manual names

  • p9601 – SI enable functions integrated in the drive (Control Unit): shows whether the integrated SI monitoring is enabled, which decides whether the alternative actual value acquisition cycle may be used.
  • p9801 – SI enable functions integrated in the drive (Motor Module): the corresponding setting to check together with p9601.
  • p9511 – SI Motion actual value sensing cycle clock (Control Unit): the alternative actual value acquisition cycle, set independently from the DP cycle.
  • p9311 – SI Motion actual value sensing clock cycle (Motor Module): the corresponding cycle, likewise set independently from the DP cycle.

Acknowledging and restarting

The message appears as an alarm and requires no acknowledgement; while it is active, the drive takes no automatic reaction. If the drive's configuration raises the same condition as a fault instead, POWER ON is required to acknowledge it before the drive can be restarted. Adjust Ti and To or the DP cycle as described above so that the message does not reappear.

The same on every family

Every manual that describes A01691 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2670
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1458

The drives this code lives on

A01691 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01691 mean on a SINAMICS drive?

It is raised by the SI Motion safe movement monitoring functions when the DP cycle of the PROFIBUS communication serves as their actual value acquisition cycle and the configured times Ti and To do not fit that cycle.

How do I fix A01691?

Configure Ti and To low enough to suit the DP cycle, or increase the DP cycle time. If SI monitoring integrated in the drive is enabled (p9601/p9801 > 0), you can alternatively use the actual value acquisition cycle p9511/p9311 set independently from the DP cycle.

Does A01691 require an acknowledgement?

No, as an alarm it requires no acknowledgement and the drive takes no automatic reaction. If the drive is configured to issue the same condition as a fault, POWER ON is required to acknowledge it.

Why do C01711 or C30711 with value 1020 or 1021 occur sporadically?

The manuals note that this can happen when alarm A01691 is not observed, i.e. when the unsuitable Ti and To times are left unchanged.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.