What it means
F07807 means the converter has detected a phase-phase short-circuit or a ground fault at the motor-side output terminals. The pulses are blocked immediately (OFF2), so the motor coasts down uncontrolled, and the fault must be acknowledged before the drive will run again. The drive stores the fault value in r0949 — read it as a decimal number; the decoding below tells you which phases are involved and, for a ground fault, the pulse number and the current component (this value appears as the message value %1 on an S120/S150). The G115D and G120C manuals list the same condition simply as a detected short-circuit and refer to interchanged line and motor cables. The ground fault test only functions when the motor is stationary.
Connecting to a motor that is either not de-energized or partially de-energized is therefore possibly detected as a ground fault.
Why it appears
- A phase-phase short-circuit or a ground fault at the motor-side output terminals of the converter.
- Interchanged line and motor cables — this is identified as a motor-side short-circuit.
- A motor that is either not de-energized or partially de-energized when connected is possibly detected as a ground fault.
- On a G120 or G120XA the fault value can additionally indicate an interrupted motor cable phase (values 5–7) or a short-circuit with hardware shutdown (value 8).
- On an S120 or S150, fault value 0 means a problem with the current measurement/current that is impressed.
What to check
- Check the motor-side converter connection for a phase-phase short-circuit.
- Rule out interchanged line and motor cables.
- Check for a ground fault.
- Check the motor cable connections — this step is printed for the G120 and G120XA.
- For a ground fault:
do not enable the pulses when connecting to a rotating motor without the "Flying restart" function activated (p1200)
. - Increase the de-energization time (p0347).
- Increase the pulse suppression delay time (p1228) to ensure standstill — the G120XA manual calls this the pulse cancellation delay time.
- If required, deactivate the monitoring (p1901).
Reading the message value
The fault value is in r0949, interpret decimal. The G130/G150 manual decodes the values 1–4 plus the two ground-fault patterns; the cable and hardware-shutdown values are given for G120 and G120XA; S120/S150 additionally decodes 0.
- 0 — problem with the current measurement/current that is impressed (S120/S150).
- 1 — short-circuit, phase UV.
- 2 — short-circuit, phase UW.
- 3 — short-circuit, phase VW.
- 4 — ground fault with overcurrent.
- 5 — motor cable phase U interrupted (G120, G120XA).
- 6 — motor cable phase V interrupted (G120, G120XA).
- 7 — motor cable phase W interrupted (G120, G120XA).
- 8 — short-circuit with hardware shutdown (G120, G120XA).
- 1yxxx — ground fault with current in phase U detected (y = pulse number, xxxx = component of the current in phase V in per mille).
- 2yxxx — ground fault with current in phase V detected (y = pulse number, xxxx = component of the current in phase U in per mille).
Parameters the manual names
- r0949 — fault value: read it as a decimal number to identify the shorted phases or the ground-fault pulse number and current component.
- p1200 — flying restart operating mode: activate it before pulses are enabled onto a possibly rotating motor.
- p0347 — motor de-excitation time: increase this de-energization time when a ground fault was detected.
- p1228 — pulse suppression delay time: increase it to ensure the motor is at standstill.
- p1901 — test pulse evaluation configuration: deactivate the monitoring here if required.
Acknowledging and restarting
The drive trips the moment the condition is detected and the motor coasts. After the short-circuit or ground fault has been found and removed, acknowledge the fault — it can be acknowledged immediately — and restart the drive. If the motor may still be rotating at the restart, first activate the flying restart function (p1200) as described under Checks.
What differs between the drive families
Straight from the manuals' own fields — F07807 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120 | OFF2 (NONE) | IMMEDIATELY | Ground fault / inter-phase short-circuit detected (7) | — | SINAMICS G120 · p. 882 |
| S120, S150 | OFF2 (NONE) | IMMEDIATELY | Ground fault / inter-phase short-circuit detected (7) | Motor | SINAMICS S120, S150 List Manual · p. 2864 |
| G120XA | OFF2 (NONE) | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1133 |
| G130, G150 | OFF2 (NONE) | IMMEDIATELY | Ground fault / inter-phase short-circuit detected (7) | Motor | SINAMICS G130, G150 List Manual · p. 1596 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 394 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 385 |
The drives this code lives on
F07807 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does F07807 mean on a SINAMICS drive?
A phase-phase short-circuit or a ground fault was detected at the motor-side output terminals of the converter. The fault value in r0949 shows where, for example value 1 = short-circuit, phase UV.
Can swapped cables trigger F07807?
Yes. Interchanging the line and motor cables is identified as a motor-side short-circuit, so rule this out before looking further.
Why does F07807 appear when I connect the motor?
The ground fault test only functions when the motor is stationary; a motor that is not de-energized or only partially de-energized is possibly detected as a ground fault.
How is F07807 cleared?
Check the motor-side connection for a phase-phase short-circuit, rule out interchanged line and motor cables, and check for a ground fault. For a ground fault, increase p0347 and p1228 and, if required, deactivate the monitoring via p1901, then acknowledge the fault.