What it means
The Control Unit cannot read any parameters from the power unit, or no parameters are stored in the power unit at all — as far as the drive is concerned, there is no power unit present. The manuals describe this fault for the G120, G120XA, G130, G150, S120 and S150 in almost the same words, but each adds its own side conditions: the S120/S150 and G130/G150 entries name the DRIVE-CLiQ cable as a possible culprit, and the G120XA entry names a specific switch-on sequence. The drive itself takes no automatic action on this fault; it can be acknowledged immediately once the cause has been removed.
Why it appears
- The power unit parameters cannot be read, or no parameters are stored in the power unit.
- An incorrect topology was selected in the commissioning software or commissioning tool, and this parameterization was then downloaded to the Control Unit.
- S120, S150, G130 and G150: the DRIVE-CLiQ cable between the Control Unit and the power unit may be interrupted or defective.
- G120XA: the AC line supply was switched on much later than the external 24V power supply at X132.
What to check
- Carry out a POWER ON (switch-off/switch-on) for all components.
- On the S120, S150, G130 and G150, check the DRIVE-CLiQ cable between the Control Unit and the power unit.
- Check the power unit and replace it if necessary.
- Check the Control Unit and replace it if required.
- If the topology was wrong, correct it and download the parameters again using the commissioning software or commissioning tool.
- G120XA: power up in the order the manual gives —
switch on the AC line supply first and then the external 24V power supply at X132
. - G120XA: carry out a hardware reset (p0972) after the AC line supply is switched on.
Parameters the manual names
- r0200 (Power unit code number actual) — the display the manual cross-refers to for this fault; read it to see the power unit code number the drive is actually working with.
- p0972 (Drive unit reset) — on the G120XA, the hardware reset the manual orders once the AC line supply has been switched on.
Acknowledging and restarting
Acknowledgment is possible immediately, as soon as the cause has been removed. The central measure in every manual is the POWER ON — switch all components off and on again. On the G120XA the switch-on order matters: AC line supply first, then the external 24V supply at X132, followed by the hardware reset via p0972 after the AC line supply is on. Where the topology had been selected incorrectly, the parameters must be downloaded again with the commissioning software or tool before the fault will stay cleared.
What differs between the drive families
Straight from the manuals' own fields — F07800 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | NONE | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1132 |
| S120, S150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | Power Module | SINAMICS S120, S150 List Manual · p. 2862 |
| G130, G150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | Power Module | SINAMICS G130, G150 List Manual · p. 1594 |
| G120 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 880 |
The drives this code lives on
F07800 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07800 mean on a SINAMICS drive?
That the Control Unit cannot read the power unit parameters or that no parameters are stored in the power unit — the drive behaves as if no power unit were present.
Why does my G120XA show F07800 after power-up?
The manual names the case where the AC line supply is switched on much later than the external 24V power supply at X132. Switch the AC line supply on first, then the 24V supply, and carry out the hardware reset p0972 afterwards.
How do I clear F07800 on an S120 or G150?
Perform a POWER ON for all components, check the DRIVE-CLiQ cable between the Control Unit and the power unit, and then check — replacing if necessary — the power unit and the Control Unit.
Can a wrong topology in the commissioning software trigger F07800?
Yes. Every manual lists this as a case in which the fault occurs; after correcting the topology, the parameters must be downloaded to the Control Unit again.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.