What it means
A35417 is raised by the temperature sensing of the Terminal Module 150 (TM150) when the temperature measured on channel 11 (r4105[11]) rises above the alarm threshold set in p4102[22]. Depending on the drive configuration, the same condition can also be issued as a fault (F) or with no reaction (N). The alarm value r2124 holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.
Why it appears
- The temperature (r4105[11]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value that initiates this alarm (p4102[22]).
- For the sensor types "PTC thermistor" and "Bimetallic NC contact" (p4100[11] = 1, 4), the drive derives the temperature from the sensor resistance: if r4101[11] > 1650 ohms, then r4105[11] = 250 °C; if r4101[11] <= 1650 ohms, then r4105[11] = -50 °C — for these sensor types the reported temperature therefore takes one of these two fixed values according to the resistance.
What to check
- Read the channel-11 temperature actual value in r4105[11] and compare it with the alarm threshold in p4102[22].
- Read the alarm value r2124 (interpret decimal): it holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.
- If p4100[11] = 1 or 4 (PTC thermistor or bimetallic NC contact), check the sensor resistance r4101[11]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below it reports -50 °C.
- Let the temperature sensor cool down until the temperature is below p4102[22] - hysteresis (p4118[11]).
Reading the message value
- Alarm value r2124, interpret decimal: the temperature actual value at the time of initiation, in 0.1 °C.
Parameters the manual names
- r4105[11] — CO: spindle supplementary temperature actual value; the channel-11 temperature whose exceeding of the threshold initiates A35417.
- p4102[22] — spindle supplementary temperature fault threshold/alarm threshold; the alarm threshold that was exceeded and the reference for the cool-down target.
- p4100[11] — spindle supplementary temperature sensor type; = 1 or 4 means a PTC thermistor or a bimetallic NC contact is used, and then the temperature is derived from the resistance r4101[11].
- r4101[11] — sensor resistance (manual: TM120 sensor resistance); compare it with 1650 ohms to interpret the reported values of 250 °C or -50 °C.
- r2124 — alarm value; read it (interpret decimal) to see the temperature actual value at the time the alarm was initiated, in 0.1 °C.
- p4118[11] — TM150 fault threshold/alarm threshold hysteresis; subtracted from p4102[22] to obtain the temperature below which the alarm clears.
Acknowledging and restarting
The alarm requires no acknowledgement: it clears itself once the temperature sensor has cooled to below p4102[22] - hysteresis (p4118[11]). If the drive is configured to issue this condition as a fault instead, the drive takes no automatic action and the fault is acknowledged immediately by POWER ON.
The same on every family
Every manual that describes A35417 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3231 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1894 |
The drives this code lives on
A35417 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A35417 mean on a SINAMICS drive?
The Terminal Module 150 (TM150) reports that the temperature measured on channel 11 (r4105[11]) has exceeded the alarm threshold set in p4102[22].
How do I clear alarm A35417?
No acknowledgement is needed: let the temperature sensor cool down to below p4102[22] minus the hysteresis p4118[11] and the alarm clears itself. If the condition is configured as a fault, it is acknowledged immediately by POWER ON.
Why does A35417 show a temperature of 250 °C or -50 °C?
With the sensor types PTC thermistor or bimetallic NC contact (p4100[11] = 1, 4), the drive derives the temperature from the resistance r4101[11]: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.
Where can I see the temperature that triggered A35417?
In the alarm value r2124, interpreted as a decimal number — it holds the temperature actual value at the time of initiation in 0.1 °C.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A35xxx group · SINAMICS manuals · Siemens manuals