Alarm · SINAMICS G130, G150, S120, S150

A35410TM: Temperature alarm threshold channel 4 exceeded

What it means

A35410 is the Terminal Module temperature alarm for channel 4: the temperature (r4105[4]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value set in p4102[8] to initiate this alarm. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or as a message without any reaction (N).

Why it appears

  • The temperature measured via the temperature sensing of the TM150, r4105[4], has risen above the alarm threshold p4102[8].

What to check

  1. Allow the temperature sensor to cool down to below p4102[8] minus the hysteresis in p4118[4].

Reading the message value

  • The alarm value (r2124, interpret decimal) contains the temperature actual value at the time the alarm was initiated, in 0.1 °C.
  • For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[4] = 1, 4), the drive derives the temperature r4105[4] from the sensor resistance r4101[4]: if r4101[4] is greater than 1650 ohms, the temperature r4105[4] = 250 °C; if r4101[4] is 1650 ohms or less, the temperature r4105[4] = -50 °C.

Parameters the manual names

  • r4105 (Suppl_temp ActV): the temperature actual value — here, the channel 4 temperature measured by the TM150 that has exceeded the alarm threshold.
  • p4102 (fault threshold/alarm thresh., index [8]): the alarm threshold for this channel; the alarm initiates above it, and the sensor must cool back below it minus the hysteresis.
  • p4100 (Sup_temp sens type, index [4]): the configured sensor type of the channel; 1 is a PTC thermistor, 4 a bimetallic NC contact.
  • r4101 (TM120 R_sensor): the resistance of the connected sensor; for sensor types 1 and 4 it decides whether r4105[4] reads 250 °C or -50 °C.
  • p4118 (TM150 thr hyst, index [4]): the hysteresis of the alarm threshold; the sensor must cool to below p4102[8] - p4118[4] before the alarm clears.
  • r2124 (alarm value): read it as a decimal number to see the temperature actual value at the moment the alarm was initiated, in 0.1 °C.

Acknowledging and restarting

The alarm needs no acknowledgement: once the temperature sensor has cooled to below p4102[8] - p4118[4], it clears by itself. If the drive is configured to output the same condition as a fault (F), it is acknowledged immediately via POWER ON.

The same on every family

Every manual that describes A35410 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3228
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1891

The drives this code lives on

A35410 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A35410 mean?

The temperature measured on channel 4 of the Terminal Module 150 (TM150) temperature sensing, r4105[4], has exceeded the alarm threshold p4102[8]. The alarm value r2124 shows the temperature that was present when the alarm was initiated.

How do I clear alarm A35410?

No acknowledgement is required: let the temperature sensor cool down to below p4102[8] minus the hysteresis p4118[4], and the alarm clears itself. If the condition is output as a fault (F), it is acknowledged immediately via POWER ON.

Why does A35410 show 250 °C or -50 °C?

For the sensor types PTC thermistor and bimetallic NC contact (p4100[4] = 1, 4), the drive derives the temperature from the sensor resistance r4101[4]: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.

Which parameters belong to alarm A35410?

p4102[8] holds the alarm threshold and p4118[4] the hysteresis, r4105[4] is the measured temperature, r4101[4] the sensor resistance, and r2124 the alarm value with the temperature at initiation.

Codes next to this one