What it means
A35410 is the Terminal Module temperature alarm for channel 4: the temperature (r4105[4]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value set in p4102[8] to initiate this alarm. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or as a message without any reaction (N).
Why it appears
- The temperature measured via the temperature sensing of the TM150, r4105[4], has risen above the alarm threshold p4102[8].
What to check
- Allow the temperature sensor to cool down to below p4102[8] minus the hysteresis in p4118[4].
Reading the message value
- The alarm value (r2124, interpret decimal) contains the temperature actual value at the time the alarm was initiated, in 0.1 °C.
- For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[4] = 1, 4), the drive derives the temperature r4105[4] from the sensor resistance r4101[4]: if r4101[4] is greater than 1650 ohms, the temperature r4105[4] = 250 °C; if r4101[4] is 1650 ohms or less, the temperature r4105[4] = -50 °C.
Parameters the manual names
- r4105 (Suppl_temp ActV): the temperature actual value — here, the channel 4 temperature measured by the TM150 that has exceeded the alarm threshold.
- p4102 (fault threshold/alarm thresh., index [8]): the alarm threshold for this channel; the alarm initiates above it, and the sensor must cool back below it minus the hysteresis.
- p4100 (Sup_temp sens type, index [4]): the configured sensor type of the channel; 1 is a PTC thermistor, 4 a bimetallic NC contact.
- r4101 (TM120 R_sensor): the resistance of the connected sensor; for sensor types 1 and 4 it decides whether r4105[4] reads 250 °C or -50 °C.
- p4118 (TM150 thr hyst, index [4]): the hysteresis of the alarm threshold; the sensor must cool to below p4102[8] - p4118[4] before the alarm clears.
- r2124 (alarm value): read it as a decimal number to see the temperature actual value at the moment the alarm was initiated, in 0.1 °C.
Acknowledging and restarting
The alarm needs no acknowledgement: once the temperature sensor has cooled to below p4102[8] - p4118[4], it clears by itself. If the drive is configured to output the same condition as a fault (F), it is acknowledged immediately via POWER ON.
The same on every family
Every manual that describes A35410 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3228 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1891 |
The drives this code lives on
A35410 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A35410 mean?
The temperature measured on channel 4 of the Terminal Module 150 (TM150) temperature sensing, r4105[4], has exceeded the alarm threshold p4102[8]. The alarm value r2124 shows the temperature that was present when the alarm was initiated.
How do I clear alarm A35410?
No acknowledgement is required: let the temperature sensor cool down to below p4102[8] minus the hysteresis p4118[4], and the alarm clears itself. If the condition is output as a fault (F), it is acknowledged immediately via POWER ON.
Why does A35410 show 250 °C or -50 °C?
For the sensor types PTC thermistor and bimetallic NC contact (p4100[4] = 1, 4), the drive derives the temperature from the sensor resistance r4101[4]: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.
Which parameters belong to alarm A35410?
p4102[8] holds the alarm threshold and p4118[4] the hysteresis, r4105[4] is the measured temperature, r4101[4] the sensor resistance, and r2124 the alarm value with the temperature at initiation.