Alarm · SINAMICS G130, G150, S120, S150

A35416TM: Temperature alarm threshold channel 10 exceeded

What it means

A35416 is issued by the temperature sensing of the Terminal Module 150 (TM150) when the temperature of channel 10, held in r4105[10], rises above the alarm threshold p4102[20]. As an alarm it triggers no protective response — the converter keeps running and the message only tells you that the channel-10 temperature has passed the set threshold. Depending on the drive's configuration, the same threshold condition can also be output as a fault (F) or as a message with no reaction (N).

Why it appears

  • The channel-10 temperature r4105[10] measured via the TM150 temperature sensing has exceeded the threshold p4102[20] that initiates this alarm.
  • For the sensor types "PTC thermistor" and "Bimetallic NC contact" (p4100[10] = 1, 4), the reported temperature is derived from the measured resistance r4101[10]: greater than 1650 ohms gives r4105[10] = 250 °C, 1650 ohms or less gives r4105[10] = -50 °C.

What to check

  1. Read the current channel-10 temperature in r4105[10] and compare it with the alarm threshold p4102[20].
  2. Let the sensor cool down — the manual's remedy is: Allow the temperature sensor to cool down to below p4102[20] - hysteresis (p4118[10]). Once this level is reached the alarm clears by itself, without acknowledgement.
  3. If p4100[10] = 1 or 4 (PTC thermistor or bimetallic NC contact), check the resistance in r4101[10]: above 1650 ohms the channel reports 250 °C, at 1650 ohms or less it reports -50 °C, so the reported value follows the resistance.

Reading the message value

  • The alarm value in r2124 holds the temperature actual value at the time the alarm was initiated.
  • Interpret r2124 as a decimal number; the value is given in steps of 0.1 °C.
  • The message value appears as the placeholder %1 and carries this temperature.

Parameters the manual names

  • r4105[10] — the channel-10 temperature actual value measured via the TM150 temperature sensing; read it to follow the cool-down.
  • p4102[20] — the alarm threshold of channel 10; the alarm initiates when r4105[10] rises above it and clears only once the temperature is below it again.
  • p4118[10] — the TM150 threshold hysteresis; the alarm clears once the temperature is below p4102[20] minus this hysteresis.
  • p4100[10] — the sensor type set for the channel; p4100[10] = 1, 4 covers "PTC thermistor" and "Bimetallic NC contact", the two types for which the resistance mapping applies.
  • r4101[10] — the sensor resistance at the Terminal Module (titled TM120 sensor resistance in the parameter chapter); for a PTC thermistor or bimetallic NC contact it decides whether 250 °C or -50 °C is reported.
  • r2124 — the alarm value; it stores the temperature at the time of initiation, interpreted as decimal in 0.1 °C.

Acknowledging and restarting

The alarm needs no acknowledgement: once the sensor has cooled below p4102[20] minus the hysteresis p4118[10], A35416 clears by itself. If the drive's configuration outputs the same condition as a fault instead, it is only acknowledged by a POWER ON.

The same on every family

Every manual that describes A35416 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3231
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1894

The drives this code lives on

A35416 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35416 mean on a SINAMICS drive?

It means the temperature measured through the Terminal Module 150 (TM150) on channel 10 (r4105[10]) has exceeded the alarm threshold p4102[20]. The drive takes no protective action; depending on configuration the condition can also appear as a fault or with no reaction.

How do I reset alarm A35416?

You do not have to acknowledge it — let the sensor cool down below p4102[20] minus the hysteresis p4118[10] and the alarm clears itself. Only when the condition is configured as a fault is a POWER ON required.

Why does A35416 report 250 °C?

With sensor type PTC thermistor or bimetallic NC contact (p4100[10] = 1, 4), the temperature is derived from the resistance in r4101[10]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or less it reports -50 °C.

Where can I read the temperature that triggered A35416?

In the alarm value r2124: interpret it as a decimal number; it holds the temperature actual value at the time of initiation in steps of 0.1 °C.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.