What it means
A35416 is issued by the temperature sensing of the Terminal Module 150 (TM150) when the temperature of channel 10, held in r4105[10], rises above the alarm threshold p4102[20]. As an alarm it triggers no protective response — the converter keeps running and the message only tells you that the channel-10 temperature has passed the set threshold. Depending on the drive's configuration, the same threshold condition can also be output as a fault (F) or as a message with no reaction (N).
Why it appears
- The channel-10 temperature r4105[10] measured via the TM150 temperature sensing has exceeded the threshold p4102[20] that initiates this alarm.
- For the sensor types "PTC thermistor" and "Bimetallic NC contact" (p4100[10] = 1, 4), the reported temperature is derived from the measured resistance r4101[10]: greater than 1650 ohms gives r4105[10] = 250 °C, 1650 ohms or less gives r4105[10] = -50 °C.
What to check
- Read the current channel-10 temperature in r4105[10] and compare it with the alarm threshold p4102[20].
- Let the sensor cool down — the manual's remedy is:
Allow the temperature sensor to cool down to below p4102[20] - hysteresis (p4118[10]).
Once this level is reached the alarm clears by itself, without acknowledgement. - If p4100[10] = 1 or 4 (PTC thermistor or bimetallic NC contact), check the resistance in r4101[10]: above 1650 ohms the channel reports 250 °C, at 1650 ohms or less it reports -50 °C, so the reported value follows the resistance.
Reading the message value
- The alarm value in r2124 holds the temperature actual value at the time the alarm was initiated.
- Interpret r2124 as a decimal number; the value is given in steps of 0.1 °C.
- The message value appears as the placeholder %1 and carries this temperature.
Parameters the manual names
- r4105[10] — the channel-10 temperature actual value measured via the TM150 temperature sensing; read it to follow the cool-down.
- p4102[20] — the alarm threshold of channel 10; the alarm initiates when r4105[10] rises above it and clears only once the temperature is below it again.
- p4118[10] — the TM150 threshold hysteresis; the alarm clears once the temperature is below p4102[20] minus this hysteresis.
- p4100[10] — the sensor type set for the channel; p4100[10] = 1, 4 covers "PTC thermistor" and "Bimetallic NC contact", the two types for which the resistance mapping applies.
- r4101[10] — the sensor resistance at the Terminal Module (titled TM120 sensor resistance in the parameter chapter); for a PTC thermistor or bimetallic NC contact it decides whether 250 °C or -50 °C is reported.
- r2124 — the alarm value; it stores the temperature at the time of initiation, interpreted as decimal in 0.1 °C.
Acknowledging and restarting
The alarm needs no acknowledgement: once the sensor has cooled below p4102[20] minus the hysteresis p4118[10], A35416 clears by itself. If the drive's configuration outputs the same condition as a fault instead, it is only acknowledged by a POWER ON.
The same on every family
Every manual that describes A35416 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3231 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1894 |
The drives this code lives on
A35416 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A35416 mean on a SINAMICS drive?
It means the temperature measured through the Terminal Module 150 (TM150) on channel 10 (r4105[10]) has exceeded the alarm threshold p4102[20]. The drive takes no protective action; depending on configuration the condition can also appear as a fault or with no reaction.
How do I reset alarm A35416?
You do not have to acknowledge it — let the sensor cool down below p4102[20] minus the hysteresis p4118[10] and the alarm clears itself. Only when the condition is configured as a fault is a POWER ON required.
Why does A35416 report 250 °C?
With sensor type PTC thermistor or bimetallic NC contact (p4100[10] = 1, 4), the temperature is derived from the resistance in r4101[10]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or less it reports -50 °C.
Where can I read the temperature that triggered A35416?
In the alarm value r2124: interpret it as a decimal number; it holds the temperature actual value at the time of initiation in steps of 0.1 °C.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.