Alarm · SINAMICS G130, G150, S120, S150

A35414TM: Temperature alarm threshold channel 8 exceeded

What it means

A35414 reports that the temperature measured through the temperature sensing of the Terminal Module 150 (TM150) — the value in r4105[8] — has exceeded the alarm threshold stored in p4102[16]. The message concerns channel 8 of the Terminal Module's temperature sensing. As an alarm it only signals the condition; depending on how the drive is configured, the same condition can also be output as a fault (F) or without a reaction (N).

Why it appears

  • The temperature (r4105[8]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value that initiates this alarm (p4102[16]).
  • For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[8] = 1, 4), the drive derives the temperature straight from the sensor resistance: if r4101[8] > 1650 ohms it reports r4105[8] = 250 °C, and if r4101[8] ≤ 1650 ohms it reports r4105[8] = -50 °C. With these sensor types the alarm therefore follows from which side of 1650 ohms the measured resistance lies.

What to check

  1. Read the alarm value r2124 (interpret the number as a decimal): it holds the temperature actual value at the moment the alarm was initiated.
  2. If p4100[8] = 1 or 4 (sensor type "PTC thermistor" or "Bimetallic NC contact"), read the sensor resistance r4101[8]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below it reports -50 °C.
  3. Let the sensor cool until the measured temperature is below the alarm threshold minus the hysteresis; the drive then withdraws the message by itself.

Reading the message value

  • The alarm value r2124 holds the temperature actual value at the time the alarm was initiated; interpret the value as a decimal number in units of 0.1 °C.

Parameters the manual names

  • r4105 (CO: Spindle supplementary temperature actual value) — the temperature actual value of the TM150 channel; r4105[8] is the value that exceeded the threshold and raised this alarm.
  • p4102 (Spindle supplementary temperature fault threshold/alarm threshold) — the alarm threshold for this message; it initiates when r4105[8] exceeds p4102[16] and clears below p4102[16] - p4118[8].
  • p4100 (Spindle supplementary temperature sensor type) — the sensor type of the channel; "PTC thermistor" and "Bimetallic NC contact" correspond to p4100[8] = 1, 4.
  • r4101 (TM120 sensor resistance) — the measured sensor resistance; for PTC and bimetallic NC sensor types it decides between 250 °C and -50 °C at the 1650 ohms limit.
  • r2124 (Alarm value) — stores the temperature actual value at the time of initiation of this alarm; interpret the number as a decimal.
  • p4118 (TM150 fault threshold/alarm threshold hysteresis) — the hysteresis subtracted from the threshold; the sensor must cool below p4102[16] - p4118[8] before the alarm withdraws.

Acknowledging and restarting

The manual's remedy is: Allow the temperature sensor to cool down to below p4102[16] - hysteresis (p4118[8]). Once the measured temperature is below this value, the alarm clears by itself and no acknowledgement is needed. If the drive is configured to output the same condition as a fault instead, the acknowledgement is IMMEDIATELY (POWER ON), i.e. the drive must be powered up again before it can be restarted.

The same on every family

Every manual that describes A35414 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3230
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1893

The drives this code lives on

A35414 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35414 mean on a SINAMICS drive?

It reports that the temperature measured through the Terminal Module 150 (TM150), value r4105[8], has exceeded the alarm threshold in p4102[16]. As an alarm the drive takes no protective action of its own; the same condition can also be output as a fault or without a reaction, depending on the configuration.

How do I clear A35414?

Let the temperature sensor cool down to below p4102[16] minus the hysteresis p4118[8]; the alarm then clears by itself without acknowledgement. Only if the condition is configured as a fault is an immediate POWER ON acknowledgement required.

Why does A35414 report 250 °C or -50 °C?

With sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[8] = 1, 4) the drive derives the temperature directly from the resistance: r4101[8] above 1650 ohms gives 250 °C, r4101[8] at or below 1650 ohms gives -50 °C.

Where can I see the temperature that triggered A35414?

In the alarm value r2124, interpreted as a decimal number: it stores the temperature actual value at the time the alarm was initiated, in units of 0.1 °C.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A35xxx group · SINAMICS manuals · Siemens manuals