What it means
A35412 indicates that the temperature measured through the temperature sensing of the Terminal Module 150 (TM150) on channel 6 — the actual value r4105[6] — has exceeded the alarm threshold stored in p4102[12]. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or without any reaction (N). As an alarm, the drive takes no automatic action; the message only reports the temperature condition.
Why it appears
- The temperature r4105[6] measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value p4102[12] that initiates this alarm.
- With sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), the drive derives the temperature in r4105[6] directly from the measured resistance r4101[6]: above 1650 ohms it reports 250 °C, at 1650 ohms or below it reports -50 °C, so the alarm follows this fixed two-step conversion.
What to check
- Read the temperature actual value r4105[6] of channel 6 and compare it with the alarm threshold p4102[12].
- Read the alarm value r2124 as a decimal number: it holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.
- If the sensor type is "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), read the resistance r4101[6]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below it reports -50 °C.
- Allow the temperature sensor to cool down until the measured temperature lies below p4102[12] minus the hysteresis p4118[6].
Reading the message value
- Alarm value r2124, interpret decimal: the temperature actual value at the time the alarm was initiated, in 0.1 °C.
Parameters the manual names
- r4105[6] — the temperature actual value of channel 6; read it to see the current temperature the TM150 is reporting for this alarm.
- p4102[12] — the alarm threshold for channel 6; the alarm is initiated as soon as r4105[6] rises above this value.
- p4118[6] — the hysteresis of the TM150 alarm threshold; the alarm only clears once the temperature is below p4102[12] − p4118[6].
- p4100[6] — the sensor type of channel 6; value 1 means "PTC thermistor", value 4 "Bimetallic NC contact", and for these types the temperature is derived from the resistance in two fixed steps.
- r4101[6] — the sensor resistance; for the sensor types above, more than 1650 ohms yields 250 °C, 1650 ohms or less yields -50 °C.
- r2124 — the alarm value; read it as a decimal to obtain the temperature actual value at the moment of initiation in 0.1 °C.
Acknowledging and restarting
As an alarm, A35412 requires no acknowledgement: once the temperature sensor has cooled down so that the measured temperature is below p4102[12] minus the hysteresis p4118[6], the alarm clears itself. If the drive's configuration raises the same condition as a fault, it is acknowledged immediately by a POWER ON.
The same on every family
Every manual that describes A35412 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3229 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1892 |
The drives this code lives on
A35412 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does A35412 mean on a SINAMICS drive?
The temperature measured through the temperature sensing of the Terminal Module 150 (TM150), channel 6 (r4105[6]), has exceeded the alarm threshold p4102[12]. The drive takes no automatic action; depending on the configuration the same condition can also appear as a fault or without reaction.
How do I clear A35412?
Let the temperature sensor cool down until the measured temperature is below p4102[12] minus the hysteresis p4118[6]; the alarm needs no acknowledgement and disappears by itself. If it is configured as a fault, it is acknowledged by a POWER ON.
Why does the alarm show 250 °C or -50 °C?
With sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), the drive derives the temperature from the resistance r4101[6]: above 1650 ohms it reports 250 °C, at 1650 ohms or below it reports -50 °C.
Which parameters belong to A35412?
p4102[12] (alarm threshold), p4118[6] (hysteresis), p4100[6] (sensor type), r4105[6] (temperature actual value), r4101[6] (sensor resistance) and r2124 (alarm value, in 0.1 °C).