Alarm · SINAMICS G130, G150, S120, S150

A35412TM: Temperature alarm threshold channel 6 exceeded

What it means

A35412 indicates that the temperature measured through the temperature sensing of the Terminal Module 150 (TM150) on channel 6 — the actual value r4105[6] — has exceeded the alarm threshold stored in p4102[12]. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or without any reaction (N). As an alarm, the drive takes no automatic action; the message only reports the temperature condition.

Why it appears

  • The temperature r4105[6] measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value p4102[12] that initiates this alarm.
  • With sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), the drive derives the temperature in r4105[6] directly from the measured resistance r4101[6]: above 1650 ohms it reports 250 °C, at 1650 ohms or below it reports -50 °C, so the alarm follows this fixed two-step conversion.

What to check

  1. Read the temperature actual value r4105[6] of channel 6 and compare it with the alarm threshold p4102[12].
  2. Read the alarm value r2124 as a decimal number: it holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.
  3. If the sensor type is "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), read the resistance r4101[6]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below it reports -50 °C.
  4. Allow the temperature sensor to cool down until the measured temperature lies below p4102[12] minus the hysteresis p4118[6].

Reading the message value

  • Alarm value r2124, interpret decimal: the temperature actual value at the time the alarm was initiated, in 0.1 °C.

Parameters the manual names

  • r4105[6] — the temperature actual value of channel 6; read it to see the current temperature the TM150 is reporting for this alarm.
  • p4102[12] — the alarm threshold for channel 6; the alarm is initiated as soon as r4105[6] rises above this value.
  • p4118[6] — the hysteresis of the TM150 alarm threshold; the alarm only clears once the temperature is below p4102[12] − p4118[6].
  • p4100[6] — the sensor type of channel 6; value 1 means "PTC thermistor", value 4 "Bimetallic NC contact", and for these types the temperature is derived from the resistance in two fixed steps.
  • r4101[6] — the sensor resistance; for the sensor types above, more than 1650 ohms yields 250 °C, 1650 ohms or less yields -50 °C.
  • r2124 — the alarm value; read it as a decimal to obtain the temperature actual value at the moment of initiation in 0.1 °C.

Acknowledging and restarting

As an alarm, A35412 requires no acknowledgement: once the temperature sensor has cooled down so that the measured temperature is below p4102[12] minus the hysteresis p4118[6], the alarm clears itself. If the drive's configuration raises the same condition as a fault, it is acknowledged immediately by a POWER ON.

The same on every family

Every manual that describes A35412 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3229
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1892

The drives this code lives on

A35412 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does A35412 mean on a SINAMICS drive?

The temperature measured through the temperature sensing of the Terminal Module 150 (TM150), channel 6 (r4105[6]), has exceeded the alarm threshold p4102[12]. The drive takes no automatic action; depending on the configuration the same condition can also appear as a fault or without reaction.

How do I clear A35412?

Let the temperature sensor cool down until the measured temperature is below p4102[12] minus the hysteresis p4118[6]; the alarm needs no acknowledgement and disappears by itself. If it is configured as a fault, it is acknowledged by a POWER ON.

Why does the alarm show 250 °C or -50 °C?

With sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[6] = 1, 4), the drive derives the temperature from the resistance r4101[6]: above 1650 ohms it reports 250 °C, at 1650 ohms or below it reports -50 °C.

Which parameters belong to A35412?

p4102[12] (alarm threshold), p4118[6] (hysteresis), p4100[6] (sensor type), r4105[6] (temperature actual value), r4101[6] (sensor resistance) and r2124 (alarm value, in 0.1 °C).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A35xxx group · SINAMICS manuals · Siemens manuals