What it means
A35413 is raised by the temperature sensing of the Terminal Module 150 (TM150): the temperature measured on channel 7 and held in r4105[7] has exceeded the alarm threshold stored in p4102[14]. The drive takes no automatic action on this alarm — it only signals that the threshold was crossed. Depending on how the drive is configured, the same condition can also be output as a fault or as a message with no reaction.
Why it appears
- The temperature measured using the temperature sensing of the Terminal Module 150 (TM150), held in r4105[7], has exceeded the threshold value in p4102[14] that initiates this alarm.
What to check
- Read the actual temperature of channel 7 in r4105[7]. The alarm value r2124, interpreted decimal, shows the temperature present when the alarm was initiated (in 0.1 °C).
- If the sensor type in p4100[7] is set to PTC thermistor or Bimetallic NC contact (p4100[7] = 1 or 4), read the sensor resistance in r4101[7]: above 1650 ohms the drive sets r4105[7] to 250 °C, at 1650 ohms or below to -50 °C, so the displayed temperature follows directly from the resistance.
- Allow the temperature sensor to cool down to below p4102[14] minus the hysteresis in p4118[7]. The alarm then clears by itself.
Reading the message value
- Alarm value r2124, interpret decimal: the temperature actual value at the time the alarm was initiated, given in 0.1 °C.
Parameters the manual names
- p4102[14] — supplementary temperature alarm threshold: sets the channel 7 temperature at which A35413 is initiated; the sensor must cool below this value minus the hysteresis before the alarm clears.
- p4118[7] — TM150 threshold hysteresis: determines how far below p4102[14] the temperature must fall for the alarm to clear.
- r4105[7] — temperature actual value of channel 7 (parameter name Spindle supplementary temperature actual value, CO): the measured temperature that is compared against p4102[14].
- p4100[7] — sensor type of channel 7: value 1 selects a PTC thermistor, value 4 a Bimetallic NC contact.
- r4101[7] — sensor resistance measured at the terminal module: for the PTC and bimetallic sensor types it decides whether r4105[7] shows 250 °C or -50 °C.
- r2124 — alarm value: stores the temperature at the time the alarm was initiated, in 0.1 °C, interpret decimal.
Acknowledging and restarting
No acknowledgment is required for the alarm: as soon as the sensor has cooled to below p4102[14] minus the hysteresis in p4118[7], the message clears on its own. If the drive is configured to issue the same condition as a fault, the fault is acknowledged immediately (POWER ON).
The same on every family
Every manual that describes A35413 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3229 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1893 |
The drives this code lives on
A35413 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What triggers alarm A35413 on SINAMICS?
The temperature measured on channel 7 of the Terminal Module 150 (TM150) temperature sensing — r4105[7] — has exceeded the alarm threshold p4102[14]. The drive takes no automatic action; it only reports the condition.
How do I clear alarm A35413?
Allow the temperature sensor to cool down to below p4102[14] minus the hysteresis in p4118[7]. No acknowledgment is needed; the alarm clears itself once the temperature has dropped.
Why does r4105[7] show exactly 250 °C or -50 °C?
For the sensor types PTC thermistor and Bimetallic NC contact (p4100[7] = 1 or 4) the temperature is derived directly from the resistance r4101[7]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below -50 °C.
Where can I read the temperature at which the alarm was raised?
In the alarm value r2124, interpreted decimal. It stores the temperature actual value at the time of initiation in 0.1 °C.