Alarm · SINAMICS G130, G150, S120, S150

A35413TM: Temperature alarm threshold channel 7 exceeded

What it means

A35413 is raised by the temperature sensing of the Terminal Module 150 (TM150): the temperature measured on channel 7 and held in r4105[7] has exceeded the alarm threshold stored in p4102[14]. The drive takes no automatic action on this alarm — it only signals that the threshold was crossed. Depending on how the drive is configured, the same condition can also be output as a fault or as a message with no reaction.

Why it appears

  • The temperature measured using the temperature sensing of the Terminal Module 150 (TM150), held in r4105[7], has exceeded the threshold value in p4102[14] that initiates this alarm.

What to check

  1. Read the actual temperature of channel 7 in r4105[7]. The alarm value r2124, interpreted decimal, shows the temperature present when the alarm was initiated (in 0.1 °C).
  2. If the sensor type in p4100[7] is set to PTC thermistor or Bimetallic NC contact (p4100[7] = 1 or 4), read the sensor resistance in r4101[7]: above 1650 ohms the drive sets r4105[7] to 250 °C, at 1650 ohms or below to -50 °C, so the displayed temperature follows directly from the resistance.
  3. Allow the temperature sensor to cool down to below p4102[14] minus the hysteresis in p4118[7]. The alarm then clears by itself.

Reading the message value

  • Alarm value r2124, interpret decimal: the temperature actual value at the time the alarm was initiated, given in 0.1 °C.

Parameters the manual names

  • p4102[14] — supplementary temperature alarm threshold: sets the channel 7 temperature at which A35413 is initiated; the sensor must cool below this value minus the hysteresis before the alarm clears.
  • p4118[7] — TM150 threshold hysteresis: determines how far below p4102[14] the temperature must fall for the alarm to clear.
  • r4105[7] — temperature actual value of channel 7 (parameter name Spindle supplementary temperature actual value, CO): the measured temperature that is compared against p4102[14].
  • p4100[7] — sensor type of channel 7: value 1 selects a PTC thermistor, value 4 a Bimetallic NC contact.
  • r4101[7] — sensor resistance measured at the terminal module: for the PTC and bimetallic sensor types it decides whether r4105[7] shows 250 °C or -50 °C.
  • r2124 — alarm value: stores the temperature at the time the alarm was initiated, in 0.1 °C, interpret decimal.

Acknowledging and restarting

No acknowledgment is required for the alarm: as soon as the sensor has cooled to below p4102[14] minus the hysteresis in p4118[7], the message clears on its own. If the drive is configured to issue the same condition as a fault, the fault is acknowledged immediately (POWER ON).

The same on every family

Every manual that describes A35413 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3229
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1893

The drives this code lives on

A35413 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What triggers alarm A35413 on SINAMICS?

The temperature measured on channel 7 of the Terminal Module 150 (TM150) temperature sensing — r4105[7] — has exceeded the alarm threshold p4102[14]. The drive takes no automatic action; it only reports the condition.

How do I clear alarm A35413?

Allow the temperature sensor to cool down to below p4102[14] minus the hysteresis in p4118[7]. No acknowledgment is needed; the alarm clears itself once the temperature has dropped.

Why does r4105[7] show exactly 250 °C or -50 °C?

For the sensor types PTC thermistor and Bimetallic NC contact (p4100[7] = 1 or 4) the temperature is derived directly from the resistance r4101[7]: above 1650 ohms the drive reports 250 °C, at 1650 ohms or below -50 °C.

Where can I read the temperature at which the alarm was raised?

In the alarm value r2124, interpreted decimal. It stores the temperature actual value at the time of initiation in 0.1 °C.