Alarm · SINAMICS G130, G150, S120, S150

A07597Encoder 2: Reference function interrupted

What it means

A07597 is the message Encoder 2: Reference function interrupted: a reference function that had been activated for Encoder 2 — either a reference mark search or a measuring probe evaluation — was interrupted while it was running. The manuals for the G130/G150 and S120/S150 families describe the message identically. Depending on how the drive is configured, the same condition can also be raised as a fault or as a message without any reaction.

Why it appears

  • An encoder fault has occurred; the encoder signals this with Gn_ZSW.15 = 1.
  • The position actual value was set during an activated reference function.
  • Reference mark search and measuring probe evaluation were activated at the same time (BI: p2508 and BI: p2509 = 1 signal).
  • The activated reference function (reference mark search or measuring probe evaluation) was deactivated (BI: p2508 and BI: p2509 = 0 signal).

What to check

  1. Check the causes listed above and resolve them.
  2. Reset the control: put BI p2508 and BI p2509 to 0 signal.
  3. Activate the requested function again — the reference mark search or the measuring probe evaluation.

Parameters the manual names

  • p2508 — the binary input (BI) that activates the reference mark search. For this message it matters twice: p2508 and p2509 must not be at 1 signal simultaneously, and p2508 must be returned to 0 signal so the control can be reset.
  • p2509 — the binary input (BI) that activates the measuring probe evaluation. Handle it together with p2508: switching both to 1 signal interrupts the function, and the reset of the control is done with 0 signal on both inputs.

Acknowledging and restarting

The remedy is not a panel acknowledgement but a reset of the control: resolve the cause, apply 0 signal to BI p2508 and BI p2509, then activate the requested function (reference mark search or measuring probe evaluation) again. If the drive is configured to issue the condition as a fault, it reacts with OFF1 (OFF2, OFF3) and the fault must be acknowledged IMMEDIATELY before it can be restarted; as a message without reaction no acknowledgement is required.

What differs between the drive families

Straight from the manuals' own fields — A07597 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Application/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2856
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1591

The drives this code lives on

A07597 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07597 mean on a SINAMICS drive?

It reports that the reference function of Encoder 2 — a reference mark search or a measuring probe evaluation — was interrupted while it was active. Depending on the configuration, the same condition can also appear as a fault or without any reaction.

Why does A07597 occur?

The manual lists four causes: an encoder fault (Gn_ZSW.15 = 1), the position actual value was set during an activated reference function, reference mark search and measuring probe evaluation were switched on together (BI: p2508 and p2509 = 1 signal), or the activated function was deactivated (both to 0 signal).

How do I clear A07597?

Resolve the underlying cause, then reset the control by putting BI p2508 and p2509 to 0 signal and activate the requested function again. If the condition was raised as a fault, it must be acknowledged IMMEDIATELY.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.