Alarm · SINAMICS G130, G150, S120, S150

A07593Encoder 1: Value range for position actual value exceeded

What it means

The position actual value of Encoder 1 is represented in a range from -2147483648 ... 2147483647. Message A07593 appears when this value range is exceeded, i.e. when the position actual value representation overflows. When the overflow occurs, the drive resets the 'referenced' or 'absolute encoder adjusted' status. The alarm value in r2124, interpreted as a decimal number, tells you which of three quantities actually overflowed. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or as a message without reaction (N). Both the S120/S150 and the G130/G150 manuals describe this message identically, so the explanation below applies to all four families.

Why it appears

  • The value range (-2147483648 ... 2147483647) for the position actual value representation was exceeded.
  • With the overflow, the 'referenced' or 'absolute encoder adjusted' status is reset.

What to check

  1. Read the alarm value in r2124 and interpret it as a decimal number; it distinguishes the three overflow situations described below.
  2. Alarm value 1: the position actual value (r2521) has exceeded the value range — check r2521.
  3. Alarm value 2: the encoder position actual value Gn_XIST2 (r0483) or the absolute value after the load gear (r2723) has exceeded the value range — check these two signals.
  4. Alarm value 3: the maximum encoder value multiplied by the factor that converts the absolute position (r0483, r2723) from increments to length units (LU) has exceeded the value range for displaying the position actual value. Reduce the position resolution and the conversion factor: reduce the length unit (LU) per load revolution for rotary encoders in p2506, and/or increase the fine resolution of absolute position actual values in p0419.
  5. In general, if required, reduce the traversing range or the position resolution.

Reading the message value

  • The alarm value is stored in r2124 and is to be interpreted as a decimal number.
  • 1: the position actual value (r2521) has exceeded the value range.
  • 2: the encoder position actual value Gn_XIST2 (r0483) or the absolute value after the load gear (r2723) has exceeded the value range.
  • 3: the maximum encoder value multiplied by the factor to convert the absolute position (r0483, r2723) from increments to length units (LU) has exceeded the value range for displaying the position actual value.

Parameters the manual names

  • r2124 — alarm value; read it here as a decimal number to identify which quantity overflowed.
  • r2521 — LR position actual value; this is the signal reported with alarm value 1.
  • r0483 — encoder actual position value Gn_XIST2; checked with alarm value 2 and one of the values whose conversion to LU overflows with alarm value 3.
  • r2723 — load gear absolute value; the alternative signal at alarm value 2 and, like r0483, part of the conversion concerned at alarm value 3.
  • p2506 — LR length unit (LU) per load path; reduce it to lower the LU per load revolution for rotary encoders when alarm value 3 is present.
  • p0419 — fine resolution of absolute position actual values (in bits); increase it as part of reducing the position resolution for alarm value 3.

Acknowledging and restarting

As an alarm, this message needs no acknowledgement and the drive takes no protective action while it is active; the entry clears once you deal with the overflow situation itself. Note that the overflow has cleared the 'referenced' or 'absolute encoder adjusted' status, so the axis is no longer referenced or absolutely adjusted. If the drive is configured to raise this condition as a fault (F), it trips the drive with OFF1 — OFF2 or OFF3 as alternatives — and the fault is acknowledged IMMEDIATELY; as a message without reaction (N) it behaves like the alarm, with neither a reaction nor an acknowledgement.

The same on every family

Every manual that describes A07593 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2855
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1589

The drives this code lives on

A07593 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07593 mean on a SINAMICS drive?

The position actual value of Encoder 1 has exceeded the permitted range of -2147483648 ... 2147483647. When the overflow occurs, the 'referenced' or 'absolute encoder adjusted' status is reset.

How do I find out which value caused A07593?

Read the alarm value in r2124 as a decimal number. Value 1 means r2521 overflowed, value 2 means r0483 (Gn_XIST2) or r2723, and value 3 means the conversion result from r0483/r2723 to LU exceeded the display range.

How do I fix A07593?

Reduce the traversing range or the position resolution. For alarm value 3 specifically, reduce p2506 (the length unit LU per load revolution for rotary encoders) and increase p0419 (the fine resolution of absolute position actual values).

Does A07593 stop the drive or need a reset?

As an alarm it requires no acknowledgement and the drive takes no action. If it is configured as a fault instead, the drive trips with OFF1 (OFF2/OFF3 as alternatives) and the fault is acknowledged IMMEDIATELY.